DESIGN OF EARTHING SYSTEM
A suitably designed
earthing has been provided as a safety measure for the electrical system of
ROP.
Soil Resistivity
The measured value
of 100 ohm-m has been taken for the calculation of the step and touch
potentials.
Fault current
levels
System Voltage
|
Short circuit
level
|
415 V
|
50kA
|
Fault Current Duration
The fault duration
of 0.5 sec is considered for sizing of
earthing conductor.
Jointing Method
Joints of
equipment earthing conductor with main earthing conductor & main earthing
conductor to electrodes should be designed such that it resists deterioration
and fusing of brazed / bolted joints under the most adverse condition of fault
current magnitude and fault duration.
The maximum
allowable temperatures for copper and steel are as follows : (The information
of steel are given for comparison)
Copper
|
For brazed joints
|
-
450 deg C
|
|
For bolted joints
|
-
250 deg C
|
Steel
|
For welded joints
|
-
620 deg C
|
|
For bolted joints
|
-
310 deg C
|
Corrosion allowance
The degree of corrosion for copper in soil is negligible,
whereas corrosion of steel in most soils increases with the decrease in
resistivity of soil. Since the soil resistivity data of proposed site indicates
values above 100 ohm meter at 0.6 to 1m depth the intensity of corrosion
expected is very mild and no corrosion allowance is normally required. However,
to ensure the reliability of underground steel earthing conductors corrosion
allowance of 15% is to be considered, in case steel is used as an earthing
conductor. The steel above the ground level is galvanised to protect from the
atmospheric corrosion.
Depth of burial of conductor
The earthing grids may be buried at a depth varying
from 0.6 to 1m. By increasing the depth of burial from 0.6 to 1, the reduction
obtained in length of buried conductors is not considerable, as compared with
the cost of excavations. In locations where extra cost of excavation is not
required, the depth of burial is taken as 1m. The conductor will be laid along
the width in the ground, in case flat conductor are adopted.
Applicable codes/classification
I) IS 3043 - 1989 Code of practice for earthing.
II) IEEE Std.
80 - 1986 Guide for safety in
alternating current substation grounding.
Material Selection
The two important
factors considered while selecting the material for the earthing conductors
are:
i) resistance to corrosion in the
surrounding medium .
ii) conductivity (so that the voltage drop in the
conductor is negligible in comparison to
that in the soil).
The Parameters of Copper & Steel are
indicated for comparison in Table XV.
Copper is an
ideal earthing conductor material as it meets all the requirements.
Installation and handling of copper conductors are easy because of their small
size and cross section. Hence copper has been chosen as the material for the
main earthing conductor in the plant. For the earthing of cable trays, fences
and lighting posts, steel has been used.
Since steel is not resistant to corrosion to the same extent as copper,
a corrosion allowance of 15% has been considered to ensure the reliability of
underground steel earthing conductors.
The steel above the ground level is galvanised to protect it from
atmospheric corrosion.
Earthing
provided in the main process building as well as in the sub-station is made of
annealed, soft drawn type bare copper conductor. Stranded Copper conductors
have been used for formation of earthing grid and also for connections from
equipment to earthing grid.
Standard procedures / formulae as recommended in
IEEE-80 and IS 3043 have been used for the calculation of various parameters
used in the design of the earthling system.
These include cross section area of earthling conductor, permissible and
actual values of step & touch
potentials,
resistance of earthing grid, distribution of zero
phase sequence current between earth wire and ground mat etc.
Layout of
earthing
Total length of
buried conductor required to control the step and touch potentials is about 10
km. Spacing of parallel conductors for formation of the grid is about 10m. The earthing grids are buried in the soil at
a depth varying from 0.6 to 1.0m based on soil resistivity value of above 100
ohmmeter at the plant site at these depths.
i) Outdoor earthing
Grounding loop of copper conductor of 190 square mm size
has been laid at a distance of about 1.5m around sub-stations, main process
building, service building and other allied structures at a depth of about 1m.
The grounding loop in each area is connected to the adjacent grounding loop of
another area by a minimum of two independent copper conductors of 190 square mm
size. Copper plate electrodes 6 mm thick & 600 square mm area are located
along the run of the earthing loop.
Transformer neutral, lightning arresters, down
conductors of lightning protection system & communication circuits are all
directly connected to the plate electrodes.
These electrodes in turn are connected to the plant's earthing
system. Earth leads from transformers'
neutral are connected to two separate earth electrodes. Facility has been provided to disconnect the
earth electrodes from rest of the system to enable measurement of the
resistance of the earth electrodes.
Properly treated earth pits have also been provided at suitable
locations near transformer neutral grounds for the discharge of lightning
current.
ii) Indoor
earthing
2x95 square mm copper conductor lay in each floor of
the building form the main earthing loop inside the buildings. This is connected to the outdoor earthing
loop at least at two points. Horizontal run of the conductor in each floor is
provided by placing the conductor between layers of reinforced steel with a
provision of 100mm covers. In the
vertical run along the wall, column, ceiling etc., the conductors are cleaned
along the surface at regular intervals.
iii) Equipment earthing
Tails from the main earthing system and/ or the
earthing rods provided near the equipment are connected to the earthing
terminals of the equipment.
Materials and the size used for equipment earthing in
the plant is indicated in Table XVI.
iv) Earthing of motors
The frames of all electric motors are connected to the
grounding system by two distinct paths. Sizes of the grounding leads have been
decided based on the power ratings of the motors.
v) Earthing of electrical panels
The internal earthing bus of each electrical panel s
connected at both ends to the plant's ground system by means of an earthing
conductor.
vi) Instrumentation earthing
All the instrument chasis and housings have been
connected to the plant's earthing network with earthing conductors of suitable
sizes. The signal ground (Zero signal
reference point) has been insulated from the chassis ground in all the control
equipment. Within any one measuring
system the signal ground is connected to the plant's ground at only one
point. The signal shield is connected
to the zero signal reference potential at only one point namely where the
signal source is earthen. (Applicable
for low-level signals such as thermocouples).
The overall shield is connected to ground at only one end of a cable
run.
vii) Earthing of cable armour
The metallic
sheaths of single conductor power cables carrying AC is grounded at one end
only. Rest of the sheath is kept insulated from ground in order to eliminate
circulating current inside the sheath.
The metallic sheath of a three-phase cable is connected to plant's
ground bus at both the ends.
viii) Earthing of other structuresAll steel
structures accessible to personnel such as metal enclosures, cable trays, steel
stairways etc., are connected to the plant's earthing system. Security fences and lighting posts are
earthen independently through conductors of galvanised steel.
7.7.9
LIGHTNING PROTECTION SYSTEM :
The Lightning protection system shall be
designed as per guidelines of IS–2309 : 1989 – Code of practice for protection
of buildings and allied structures against lightning and Indian Electricity
Rules. All the structures in PREFRE complex, including the stack, shall be
covered in the lightning protection scheme adopted for ROP Project. The
lightning current is discharged to earth without passing through the structures
or causing damage by fire, flash-over etc. The lightning protection –
system shall consist of horizontal roof
conductors with air termination and down conductors, made of copper, for the
main plant and allied buildings. The tall structures like stack and boiler
chimney
shall be provided with vertical rods
connected together by horizontal roof conductors and down conductors, all made
of copper. Vertical rods are provided to
give additional protection. All the down
conductors are connected to the earth electrodes. The earthing electrodes of the lightning
protection system are interconnected with the main earthing grid of the plant.
Design of the lightning system
The lightning protection system for ROP has been
designed generally in accordance with the code of practice IS 2309-1989.
The main buildings of the plant namely the Low Block,
the High Block and the Stack have been provided with independent lightning
protection systems.
Lightning protection system for the stack is designed
with vertical air termination and horizontal
conductor on roof periphery.
7.8 ELECTRICAL FIRE PROTECTION
Various design provisions made in Electrical system of
ROP Project for prevention and propagation of fire in critical areas are
summarized herein under:-
7.8.1 CONTROL ROOM
Fire retardant low smoke (FRLS) cables are used for
control wiring of all the systems in control room.Power wiring and control
wiring are segregated through separate cable trays and/or conduits. Cables used
for power wiring is departed suitably.
Load factors used in design of such cables are restricted to 50% only to
avoid overloading of cables under any circumstances.
Cable fire sealing will also be provided for cables
entering in the control room in due course of time.
7.8.2 CELL AREAS
No electrical installations are made in any cell
except dissolver cells. Electrical cables used in dissolver cells are fire
retardant low smokes, radiation resistant CSPE sheathed type. Dissolver cell
loads (crane, lighting etc.) shall be fed by class-IV power supply. Cable fire
sealing will be provided for all the cables entering dissolver cell for
containing spread of cable fire.
Electric motors used in dissolver cells are totally enclosed
type and will not catch fire generated outside. Dissolver cell lighting is
connected through a special shielding plugs, which is not likely to catch
and/or transmit fire to any other object, whatsoever.
Load factors used in design of such cables are
restricted to 50% only to avoid overloading of cables under any circumstances.
7.8.3 DAY TANKS
Concrete fire barriers with 3 hours fire rating shall
be provided between day tanks for DG sets. The fire barrier shall be provided
between day tanks upto a height of 1 m above the top of day tank.
7.8.4 PLANT AREAS
Cable fire
sealing and fire resistant coating will be provided for al the cables installed
in important plant areas viz. FHA, laboratories, tank space, MUA, access
galleries, sampling corridors etc. for prevention and propagation of electric
cable fires.
Power and control cables are segregated and separated
in different cable trays to prevent propagation of fire from power to control
cables. Control cables are installed at bottom most tier of cable trenches in
perforated covered cable trays for the same reasons.
No comments:
Post a Comment