7.6 CLASS-I POWER SUPPLY SYSTEM
7.6.1 BATTERY BANK :The batteries form part of the essential,
uninterrupted class-I, 110V DC power
supply system.
When the AC supply is not available to the battery-charger through class III
power supply,
the batteries will take over the function of feeding
DC power to plant's critical loads like switch gear controls,
indications & annunciation and the emergency
lighting along the evacuation routes in active areas. Two battery
banks, each of 110V (nominal), 425 AH, 56 cell YKP 35
Plante type, shall be installed in sub-station . The
advantage of Plante type batteries are:
a) Higher discharge voltage and discharge capacity.
b) Low gassing rates.
c) Long life.
d) Capacity for fast recharging without affecting
life.
e) High performance (low internal resistance).
f) High energy output.
g) Low maintenance.
h) Compact and light weight.
i) High reliability for standby applications.
j) Lesser fall in capacity with time.
k) Continuous renewal of active material in service.
l) Minimum float currents & corrosion rate.
m) Higher scrap value.
n) Transparent
SAN containers allow for visual monitoring & prompt remedial action.
Each battery
bank shall be designed to supply the entire class I power requirement of 350
amps for a period of 30 minutes at high discharge rates without affecting the
life of the batteries. All the control
equipment connected to the DC bus shall operate satisfactorily from 93V to 121V
(85-110% of nominal voltage). The trip
coils of breakers of 33KV/433V switchgears shall operate
between 55V and 137V (50-125% of nominal
voltage). The batteries shall be capable
of feeding DC power within the required voltage limits. The brief specification
of battery bank system is given in Table-XI. During boost charging of a set of
batteries through ‘Float cum Boost charger’, all the DC loads will be supplied
through standby Float charger/ other ‘Float charger’. The brief specification
of battery-charger system is given in Table-XII.
All such loads will be transferred to the other
battery-charger / battery set in order to protect them from high boost charging
voltage. Sizing of the batteries shall
be done as per IEEE-485.
7.6.2 OPERATING PHILOSOPHY OF CLASS-I POWER SYSTEM
7.6.2.1 During normal condition, 110V class-I
loads of ROP facility will be fed through Battery charger.
7.6.2.2 In case of non-availability of class-III
supply to Battery charger, class-I loads of facility shall be fed through 110V
DC Battery Bank of ROP substation.
7.6.2.3 In case of failure of battery bank of a
group, the loads of this group shall be fed by closing the bus coupler breaker
of DC PDB of ROP substation.
7.7 DISTRIBUTION NETWORK
This system shall deal with power, control
wiring and earthing system network for entire plant. It is envisaged to upgrade
the electrical control system by installing drawout type MCCs/ PCCs, FRLS
cables and by segregating class-IV, class-III and control cables/ panels inside
the plant for enhancing safety and reliability of electrical system
7.7.1 POWER
DISTRIBUTION BOARDS (PDBs) AND MOTOR
CONTROL CENTRES
(MCCs)
NON DRAWOUT TYPE PANELS (GENERAL FEATURES)
The AC
motor control centres (MCCs) and power
distribution boards (PDBs) are designed for 415V,
3Phase, 4Wire, 50Hz supply. The PDBs and
the MCCs are self standing cubicle type made of 2/2.5mm thick sheet
steel. The boards are single front/
double front type with front doors having concealed hinges and
neoprene gaskets. The cubicles are dust tight, vermin and insect
proof IP51 enclosure with ventilation hood.
Six to eight cubicle module, stacked one over the other, form one vertical panel. Each module
is an outgoing SFU or a starter or an incomer or a buscoupler. The
aluminium busbars are located in horizontal and vertical bus
bar chamber. Proper insulation
barriers have been provided to eliminate all dangers of personnel contact
with live bus. The panels are provided
with cable alley and the cables enter the alley either from top or bottom
of the alley as specified. Ground
bus of adequate size has been provided along the entire
length of the boards. Apart
from the ground bus, a scrape earth has also been provided for
drawout modules. Two nos. of
earthing bolts have been provided for connection
with plant's ground grid. Space heater with thermostat
has also been provided to prevent condensation inside the pan.
The lighting and
power distribution boards are non-drawout type located
in various electrical rooms distributed over
the entire plant.
The MCCs
shall conform to IS 13947 (Part 4 : Low voltage electromechanical contactors
and motor starters. The various operational facilities provided on the starter
modules are :
a)
Local or remote control facility through lockable local/remote
selector switch.
b) Stopping
facility at both remote and local station irrespective of L/R
selector switch position.
c) Interlock by-pass facility provided for
pre-commissioning trial runs, should be dis-
connected prior
to plant operation.
d)
Overload reset facility through push
button without opening the module door.
e) On/off and auto-trip indications are also
provided on all starter module.
Protection scheme envisages following devices for all
motors of rating above 25 kW:
Short circuit protection through fuse.
Overload
protection through bi-metallic overload relay.
Overload protection for high inertia motors through
saturable reactor core overload relays.
Single phasing protection through negative phase
sequence single phasing preventer.
Protection against high winding temperature through
thermisters and thermister relays.
DRAWOUT TYPE PANELS (GENERAL FEATURES)
Drawout
type MCCs have been provided for all
utility, air-conditioning and ventilation
equipment which
have motors of rating 15 KW and above. For
access gallery motors where the level of radioactivity
is high, the MCCs are installed in general corridors for ease of maintenance
and interchangeability. All squirrel cage motors of
fractional HP rating to 90 kW rating are fed through
Direct-On-Line starters except some 90 KW exhaust
system motors which
are on class-III power supply. The
transformers are so designed that the system can take the
inrush current load during starting of any motor without a dip in
the system voltage. The 90
KW exhaust system motors have star delta starters/ VVVF drives
as they are to be started and operated on
DG set when normal power supply is not available. Running
hour meter shall be provided for all the
utility & services system motors. In drawout modules the
outgoing and incoming contacts are drawout type and
the control terminals are sliding type. The trolleys have three positions
i.e., "service", "test" and
"isolate". Outgoing
power and control wires are terminated in cable
alley or in marshalling box. The power
distribution details of all major MCCs
is listed in Table XIII. Technical particulars of MCCs are listed in
Table-XIV. High Inertia motors shall be provided with suitable protections to
avoid operation of the overload relays during
its pro-longed starting time. Such motors may be provided with suitable
pulleys to avoid long starting time. Microprocessor based motor protection
relays are envisaged for motors of rating 90kW and above.
7.7.2 PROTECTION & PROTECTION COORDINATION
The protection scheme and protection
co-ordination for the entire electrical systems shall be provided as per
IEEE-242, 1986 and current industrial practices. The following protections will
be provided:
For 415V System
(a) Incoming ACB/MCCB feeders to MCCs
- All incoming ACB/MCCB
feeders to MCCs shall be provided with Over current, Short circuit and
Earth fault Releases.
·
All
feeders from PCCs to MLDBs / PDBs and MCCs are provided with over load and
short-circuit protections. Feeders to MCCs will be provided with Breaker with
microprocessor/ thermo-magnetic based releases depending on their ratings.
(b) Motor feeders
· For protection of motor of rating below 25
kW, fuses and thermal bi-metal relay will be provided.
· For protection of motor of rating between
25 kW and 90kW, fuses, thermal bi-metal relay, single phasing protection relay,
thermistor relay, and space heater will be provided.
· For protection of motor of rating ≥ 90 KW,
fuses, motor protection relay (M.P.R.) and space heater shall be provided.
· Type-2 coordination will be provided for
all motor starters.
7.7.3 H.T./L.T. Cables
H.T./L.T. cables conforming to IS 7098/1554, ASTM-D
2843, 2863 and IEC-754(I) shall be used. EPR insulated, CSPE sheathed Radiation
resistant cables shall be used for ROP cell cranes, cell lights/plug sockets,
CCTV systems etc. The radiation resistant cable can withstand a cumulative dose
of 100 MR.
415V SYSTEM
The cabling system is divided into two
categories as follows:
i)
Cables connected through circuit breaker
ii)Cables
connected through fuse.
The cables protected by circuit breakers
are designed on the basis of short circuit duty. But the cables which are protected by current
limiting HRC fuses, shall not be designed on the above basis as the fault
cleaning time of HRC fuses is less than a cycle resulting in the limiting
action of let through current. These
cables are sized only on the following considerations:
i. Continuous current carrying capacity
considering 100% load factor.
ii. Derating factors has been considered as
per IS 1961 and leading cable
manufacturers’ recommendations.
iii. Maximum
conductor temperature as per IS: 1961
iv.
Voltage
drop in the cables between the transformer and switchgear and between
switchgear and motor control centre is limited to 2% under full load condition. The voltage drop
in the cables between motor control centre and motor terminal is limited
to 3% under full load conditions.
Voltage
dip during starting is limited to 15% at motor terminals.
(a) 110 V DC POWER CABLES
110 V DC power cables are on the normal
current carrying capacity and voltage drop not exceeding 2.5% under normal
conditions. The feeders are protected by
fuses/MCCBs.
(b) 24 V/48 V DC POWER CABLES
24 V/48 V DC power cables are sized on the
normal current carrying capacity and voltage drop not exceeding 2.5% under
normal conditions. The feeders are
protected by fuses.
(c) 240/110
V DC AND 110 V, 24/48 V DC CONTROL CABLES
(i) P.T. circuits
Voltage transformer leads shall be checked
for voltage drop which shall be limited to within 0.5% for commercial metering
and 3% for other purposes.
(ii) C.T. circuits
Voltage drop criterian not applicable
however, suitable size should be selected so as to avoid high burden on CT
secondary.
(iii) Control circuits
Voltage drop
need not be considered.
(d) FIRE RESISTANCE, LOW SMOKE (FRLS) ELECTRIC CABLES
SELECTION CRITERIA
These cables
have improved performance in case of fire as follows:
i) Lesser smoke generation.
ii) Lesser acid gas generation.
iii) Higher critical temperature.
iv) Higher oxygen index.
v) Increased flame resistance.
GENERAL FEATURES OF FRLS CABLE
Polymeric materials like PVC, XLPE are often modified
with suitable additives to make them flame retardant and to restrict the smoke
generation from them during burning with flame or smouldering. The flame
retardancy of a polymeric material is measured by determining oxygen index and
temperature index of the material. By oxygen index it is meant that part i.e.
percentage of the oxygen needed in the ambient atmosphere that will support
combustion of the material. Materials
which ignite in air have oxygen, index below 21 (Normal atmospheric air
contains 21% of oxygen). Therefore,
higher the oxygen index better is the flame resistance. By temperature index it is meant at what
ambient temperature, the material will ignite in air i.e. at oxygen
concentration of 21 parts.
(e) HALOGEN
FREE FLAME RETARDANT (HFFR) WIRES
GENERAL FEATURES-
All electrical wiring of ROP project shall be done by HFFR wires. HFFR is a
Poly-olefinic compound with small amount of Al(OH)3 HFFR wires have
following advantages over FRLS wires.
(i) The smoke emitted is almost negligible.
(ii) The smoke is transparent and non-toxic.
(iii)Unlike PVC, the smoke emitted is non corrosive.
(iv)The insulation does not burn readily and does not
melt and drip to spread fire.
(v)Absence of smoke, toxic fumes and uninterrupted
power supply enable safe evacuation of trapped people and efficient fire
fighting.
(vi)Critical Oxygen Index is around 35%.
(vii)Temperature index is more than 3000C.
(viii)Smoke density (light absorption) is less than
10%.
(ix)Acid gas generation is less than 5%.
(x) Flammability test as per IEC-332-1 and IS
694:1990.
(xi)Enviro Care Compounds A/S (ECC) confirms that
HFFR is environmental friendly, in that they do not contain neither heavy
metals nor halogens. HFFR is based on copolymers of
(xii)Polyolefins and have high loading of inorganic
filler.
(xiii)Not UV degradable.
(xiv) Could be recycled as most of the thermoplastic
polymers.
7.7.4 Cable Support System And Cable Routing
Cables are laid in galvanised steel cable trays.
Ladder type cable trays are generally used for power cables and perforated type
cable trays are used for control cables. All safety related power and control
cable trays are covered with GI sheet.
Diverse routes and physical
separation have been followed for safety related Group-A and Group-B
cable trays.
Cable trays of ladder
and perforated types and associated accessories such as coupler plates, tees,
elbow etc. will be fabricated from Hot rolled 14 gauge (2 mm thick) hot dip
galvanised steel. Cable tray cover will be fabricated from 16 gauge perforated
(1.6 mm thick) galvanised M.S. sheets.
Cable trays will be
supplied in standard length of 2500 mm and clear inside width of trays will be
as follows:
Perforated type trays : 150,
300, 450 and 600 mm
Ladder type trays : 150, 300, 450, 600 and 750 mm
7.7.4.1 Cable trays are supported by steel support
structure attached to the building at suitable locations.
7.7.4.2 Cable trays are installed so that at least
250mm vertical clearance is available between bottom of bottom tray and bottom
of top tray. Cable tray containing class-IV power cables are placed at the top
followed by safety related power cables and control cable tray at the bottom.
Separation between non safety and safety related cable trays and also between
redundant circuits of safety related systems is maintained by suitable
separation distance, barriers etc.
7.7.4.3 Independence between safety
related systems and non safety related systems
Safety related electrical systems are
designed to perform during and after design basis event whereas non-safety
related systems are not normally designed for this condition. Hence failure of non-safety related systems
should not cause failure of safety related systems. Independence between safety related systems
and non safety related systems is achieved by means of
a) Electrical
isolation
b) Physical
separation
7.7.4.4 Independence between redundant
safety related electrical systems
Safety related electrical systems are grouped into two
redundant groups (Group-A and Group-B). Independence between these redundant
groups is maintained so as to prevent simultaneous failure of both the groups
due to common cause failure. Independence between redundant safety related
systems is achieved by means of the following:
a) Electrical
isolation
b)
Physical
separation
7.7.4.5 Physical separation
Physical separation is provided for equipments and also for circuits.
In areas where both safety related and non-safety related loads/systems are
located, physical separation is required between them. The following measures
are planned in such cases in the order of preference as indicated below:
a)
Physical
separation is maintained by keeping minimum 900 mm horizontal distance, or
b) Vertical clearance of 250 mm is maintained
between ‘safety related cable trays’ and ‘non safety related cable trays’, or
c) Safety related cable trays are routed in
covered solid bottom trays below non safety related cable trays, or
d) Fire barriers having 3 hrs.
rating are provided between safety and non safety related circuits, or
e) Where separation distances/barriers
mentioned above are not possible due to layout constraints, following measures
are taken:
* The non-safety related cable tray systems
are considered as safety related and designed to the same standards as
applicable for safety systems.
* The cables used for those non-safety
systems are designed, manufactured, inspected and tested to the same standards
as those applicable for safety systems.
* Safety related cable trays are covered and located below
non-safety related cable trays.
Any short circuits/open circuits in the non-safety
circuits due to failure of connected non-safety equipment may result in damages
to these non-safety circuits. However
any such damage will be limited to non-safety areas only as fire barriers are
provided between safety and non-safety areas.
In view of the above, it is considered that
faults/failures originating from non-safety related systems close to safety
system will not have adverse influence on safety related systems.
7.7.5 Fire proof
Sealing of Cable penetration
Cables/
cable tray openings in walls and floors or through pipe sleeves from one area
to another or one elevation to another will be sealed by a fire-proof sealing
system. The fire-proof sealing system (FPSS) will effectively prevent the
spread of fire from the flaming to non-flaming side, in the event of fire.
7.7.6 Fire
Barriers/Fire Stops And Fire Breaks For Cables
7.7.6.1 Fire barriers/fire stops and fire
breaks are provided along the run of
cables in cable vaults/galleries,
cable shafts, cable tunnels/trenches and cable trays to prevent spread of fire
from one area to other and to contain the damage. Indian standard IS:12459 –
1788 code of Practice for fire safety in cable runs is the basis for the design
of fire barriers and fire breaks.
7.7.6.2 Fire barriers/fire
stops rated for 3 hour fire rating as per IS-12458-1988. Method of fire
resistance test of fire
stops¢ are provided at the following locations.
a) At the openings in walls when cables
cross from one building to other, one redundant area to other, and openings in
floor when cable trays cross from one floor to other
b) Entry and exit of cable trenches for
safety related equipment
c) And where the physical separation
between redundant safety related open type cable trays is less than acceptable
value.
d) At every 30 meters length in a cable
trench/tunnel
e) Fire barriers will be provided above
panels/MCCs to segregate them from cable trays carrying redundant group of
cables.
7.7.7 Mode of
Laying
7.7.7.1 Cables outside areas of ROP sub-station will
be directly buried.
7.7.7.2 Cables inside sub-station will be laid in trenches or overhead cable trays.
7.7.7.3 Power cables will be laid in GI ladder type
trays. Control cables will be laid in GI perforated trays.
Cable
trays will be supported from slabs/walls as found suitable. Vertical trays and
all outdoor
cable
trays will be provided with removable
covers. Power and control cables will be laid in
separate
trays and distinct route for different class of supply cables will be followed
to the extent
possible.
7.7.7.4 Street
lighting cables will be directly buried along the street with appropriate cable
route marking.
7.7.8 EARTHING SYSTEM/NETWORK
The basic
objectives of an earthing system are :
a) ensure avoidance of personnel exposure to electric
shocks in the plant premises.
b) provide adequate current carrying capacity, both in
magnitude and duration, to accept
ground fault
current of the system.
c) facilitate the operation of protective relays and
equipment by providing low resistance
path to
earth return currents.
The earthing
system shall be designed as per IS-3043 (code of practice for earthing) and
IEEE-80 for the electrical sub-station and plant areas. Earthing network of
sub-station shall be suitably extended to the plant areas for equipment
earthing. Stranded copper conductor shall be used as the main earthing material
Two distinct paths of earthing shall be provided for all the equipments. The
required cross-sectional area of earthing conductor has been calculated for
copper for 0.5 second duration for a fault level of 50 kA at 415 volts.
No comments:
Post a Comment