7.4 CLASS -III POWER SUPPLY SYSTEM
7.4.1 415 V
SWITCHGEARS
415 V class-III
switchgear panel in sub-station shall comprise of :
i) 2 Nos. of 415 V, 2500 A/46 MVA incoming air
circuit breakers.
ii) 2 Nos. of
415V, 1600 A/46MVA incoming air circuit breakers.
iii)2 Nos. of
415V, 2500 A/46 MVA bus section air circuit breakers
iv)2 Nos. of 415
V, 1000 A/46 MVA spare air circuit breakers.
v) 28 Nos. of
outgoing feeders comprising of ACBs and MCCBs.
vi) 2 Nos
630A MCCBs for SFSF.
vii)2 Nos. 630A
MCCBs for AWTF.
Technical
specification of PCC (NPCC and EPCC) panels is enclosed vide Table-VIII.
7.4.2 DIESEL GENERATORS
Two numbers of diesel generator sets of capacity
1010kVA each conforming to ISO 3046 shall be installed in sub-station for
providing 415V, 50Hz grounded AC power supply to the plant's safety related
loads during normal power failure/ outage conditions. The DG sets shall have the capability to
start from cold condition, reach synchronous speed and be ready to take the
load, without undue stress, in about 10 seconds from the initiation of start impulse. The generators shall
be capable of accepting their maximum rated load in
single or multi steps. When the machine
is running in no-load condition at the rated voltage and speed, the transient
voltage drop at its terminals on starting the exhaust fan motor drawing a huge
starting current at 0.3 power
factor shall
not exceed 10% of the rated voltage. When the machine is running at 80% load at
0.8 power factor at the rated voltage and speed, the corresponding voltage drop
on starting the same motor shall not exceed 15%. The response of the regulator and excitation
system shall be such
that following a step
application or rejection of rated load at rated power factor and
subsequent to the drop or alternator rise of sub-transient voltage, the generator
will recover its set voltage within 0.5 second.
The alternator shall be capable of taking momentary overload. Rating of the two DG sets shall be so chosen
that the entire emergency load of the plant can be continuously fed even if one
of the sets fails.
The control panel design shall include microprocessor
based fast and reliable control system.
The DG sets shall be provided with an independent cooling tower. Each DG set shall also be provided with an
independent day tank of 2500 ltr. capacity for storing the fuel. On
consideration of fire safety, these tanks shall be located outside of the room in which the DG
sets are installed. In
addition to the
local storage of fuel, supply of fuel for 7-day continuous operation of one DG
set, from the bulk storage facility shall also be made available.
In the event of
normal power failure, the DG set will start automatically. The entire essential base loads like plant
lighting, health & safety instruments, plant communication equipments etc.,
shall be fed within 30 seconds. The
design envisages manual connection of bulk loads like exhaust and off-gas fans
one by one in a pre-set sequence to protect the generator from the effects of
surge currents arising immediately after connecting a bulk load.
Technical specification of DG set is enclosed vide
Table-IX.
The Safety related power supply system is categorized
into two groups, Group-A and Group-B. Power Supply System belonging to Group A
Safety Related System and Group B Safety Related System are identified in the
following table:
Group-A Safety Related
Systems
|
Group-B Safety Related
Systems
|
CLASS-III EPCC PANEL (GROUP-A)
MCC –1 (E2 FAN)
|
CLASS-III EPCC PANEL (GROUP-B)
MCC –2 (E2 FAN)
|
MCC –1 (OFF GAS FAN)
|
MCC –2 (OFF GAS FAN)
|
MCC-E (FHA)
MCC
(E- COMPRESSOR)
|
|
HIGH BLOCK-MLDB-E & 6 NOs. LIGHTING PDBs
|
|
UPS SET – 1
|
UPS SET – 2
|
UPS DB- 1
|
UPS DB – 2
|
DC SWITCHBOARD-1
1 No. LIGHTING PDB
|
DC SWITCHBOARD-2
|
7.4.3 OPERATING PHILOSOPHY OF CLASS-III POWER SYSTEM
7.4.3.1 In case of loss of power
supply on one bus-section of EPCC (Emergency Power Control Centre), power
supply to the affected bus-section shall be restored by starting the DG set of
that section automatically/ manually.
7.4.3.2 In case of failure of incomer breaker
of an MCC or the cable incomer of MCC or upstream breaker of corresponding
EPCC, standby motor shall be started from the corresponding group of MCC.
7.4.3.3 In case of failure of any
motor-starter or the outgoing feeder of an MCC, standby motor shall be started
from the corresponding group of MCC.
7.5 CLASS-II POWER SYSTEM
Two nos., 230V,
single phase, 50 KVA each UPS systems (UPS A & UPS B) are provided for
class-II loads of ROP project. Both UPS systems are seismically qualified. The
class-II load includes control & instrumentation loads, nuclear
instruments, Public address system and control room lighting. Maximum demand of
all Class-II loads connected to the UPS is 50 KVA. The class II system has 100
percent standby capacity, as each UPS unit is adequate to cater to entire class
–II i.e 50 KVA load. Uninterruptible Power Supply is On-line, Three Phase
Input, Single Phase Output, IGBT based System. The UPS maintains continuity of
electrical power within the defined limits (5 milli second) on failure of AC
source. The system consists of a solid-state converter (rectifier) with Battery
Charger; PWM IGBT based inverter, 30 nos of SMF batteries block of 12V each
providing 60 minutes back up, Static Bypass switches (2 nos in each system) and
manual maintenance switch. Technical specification of UPS system is enclosed
vide Table-X.
The scheme is
shown in the drawing A3/NRG (P)/E&I/ESS/06/01-R0 (CLASS II POWER SUPPLY
SCHEME) enclosed. There are three nos of class-II switchgear panels viz IPDB-1,
IPDB-2 and PDB. UPS A feeds IPDB-1 and IPDB-1 in turn feeds IPDB-2. UPS B feeds
PDB. The UPS system A is backed up by UPS B through static bypass switch
(VTT2A) and UPS B is backed up by its bypass line through static bypass switch
(VTT2B). These switches operate automatically in order to maintain the continuity
of the power supply. The loads of PDB connected to UPS B are those, which are
not affected even when inverter of UPS B fails, as these loads have built in
batteries as a back up source of power.
GENERAL
DESCRIPTION:
1. UPS system -A
It feeds I&C system,
emergency control panel, nuclear instruments, PA system etc. The system is
installed in UPS room along with power distribution board (IPDB-1 & IPDB-2)
at third floor, high block building of ROP.
2. UPS system -B
It feeds loads
like fire alarm system, Tel exchange, Control room lighting, High block
lighting, etc. The system is installed in the UPS room at
third floor, high block building of ROP.
SYSTEM
DESCRIPTION:
Each UPS system
consists of following major components:
A) 12 Pulse
Rectifier with buck boost converter.
B) PWM Inverter
utilizing IGBT as switching device
C) Electronic
Static Bypass Switch.
D) Manual
Maintenance Bypass Switch.
E) Microprocessor
based Control and Data Monitoring System.
FUNCTIONAL
DESCRIPTION:
The UPS supplies stable and conditioned AC
power to the class II loads. The Rectifier converts AC Input voltage to DC
voltage. This DC voltage is used for inverter input as well as it is fed to
DC-to-DC converter (IGBT based float cum boost Charger) for charging the
battery bank. With the inbuilt charger control circuit, the batteries are
always maintained in fully charged
condition.
When
the AC input voltage drops below the specified limits (+10%) or in case
of power failure, the Inverter will continue to supply power to the equipment
load up to one hour utilizing the battery as power source. The continuity of power to safety related
loads can further be maintained through static bypass in case any UPS fails /
trips. The transfer of loads from UPS A to UPS B takes place without any
interruptions. Loads connected to UPS B
are automatically transferred through static bypass switch to isolation
transformer, in case of failure of UPS B. Provision for
manual by pass (MB) operation also exists for facilitating maintenance of each
UPS by transferring the load to the by pass line.
OPERATING PHILOSOPHY:
UPS – A
feeds IPDB-1 & IPDB-2 and UPS – B feeds PDB loads. The inverter output of
UPS – A is connected to the inverter output of UPS-B through static switch
(STATIC BYPASS SWITCH VTT2A). Inverter output of UPS – B has its own bypass
line connected through static switch (Static Bypass Switch VTT2B) to class III
power through transformer. There is also class III bypass line through 3 phase
to single phase transformer connected to UPS A through Manual Bypass Switch (MBS).
The
scheme is shown in the drawing A3/NRG (P)/E&I/ESS/06/01-R0 (CLASS II POWER
SUPPLY SCHEME) enclosed annexure I. The operating philosophy of UPS-A &
UPS-B systems under different conditions is described below.
1.
Normal
operation:
UPS -A feeds IPDB-1 & IPDB-2
and UPS – B feeds PDB. Circuit breakers CB 1, CB2, CB3, CB-4, CB5, CB-6, static
Bypass Switch (VTT1A), static Bypass Switch (VTT1B), switch (S8A & S8B ) and out put circuit breaker
(Q3A & Q3B) remain closed. Static Bypass Switch (VTT2A), Static Bypass
Switch (VTT2B), CB7 and CB8 remain opened. MBS shall be at X position. Circuit breakers (Q21A & Q21B) are kept
closed to keep 3Ø to1Ø transformer warm. MBS will be operated under
administrative control. Audio – Visual annunciators are provided for showing ON
and OFF status of UPS A and UPS B in ROP main control room.
2. Rectifier failure :
If
rectifier section of UPS A fails, UPS-A feeds IPDB-1 & IPDB-2 through its
battery & inverter. Subsequently batteries start discharging and on “LOW
BATTERY” (87.5 % of rated voltage) signal, automatically static Bypass Switch
(VTT1A) gets open and static Bypass Switch (VTT2A) gets closed within 5 milli
seconds. UPS – B starts feeding load of UPS -A in addition to PDB. The rectifier
failure is displayed on LCD through 4 lines of 16 characters along with audio –
visual annunciation provided in the mimic of UPS Panel (inverter cubicle). The
same annunciation for failure is also duplicated in ROP substation through
substation PC. Circuit breakers positions remain same as described under point
no 1.
If
rectifier section of UPS B fails, their batteries of UPS-B feed PDB through its
inverter. Subsequently batteries start discharging and on “LOW BATTERY” (87.5 %
of rated voltage) signal, static bypass switch (VTT1B) gets open and static
bypass switch (VTT2B) gets closed automatically within 5 milli seconds. The PDB
is fed through the bypass line of UPS –B. The rectifier failure is displayed on
LCD through 4 lines of 16 characters along with audio – visual annunciation
provided in the mimic of UPS Panel (inverter cubicle). The same annunciation
for failure is also duplicated in ROP substation through substation PC. Circuit
breakers positions remain same as described in point no 1.
If
rectifier sections of UPS A and UPS B fail simultaneously then automatically
loads will get transferred to their respective batteries. Subsequently
batteries of UPS A and
UPS B
will start discharging. On “LOW BATTERY” (87.5 % of rated voltage) signal of
UPS A, the corresponding loads will be transferred to UPS –B. On “LOW BATTERY”
(87.5 % of rated voltage) signal of UPS B, the loads will be transferred to
bypass line of UPS B.
The corresponding loads can also be fed
through class III bypass line under administrative control through Manual
Bypass Switch (MBS) , if felt necessary.
3. Inverter failure :
If
Inverter of UPS A fails and Inverter of UPS B is healthy, automatically Static
bypass switch (VTT1A) gets opened and Static bypass switch (VTT2A) gets closed
within 5 milli seconds. UPS – B starts feeding load of UPS -A in addition to
PDB. The inverter failure is displayed on LCD through 4 lines of 16 characters along
with audio – visual annunciation provided in the mimic of UPS Panel (inverter
cubicle). The same annunciation for failure is also duplicated in ROP
substation through substation PC. Circuit breakers positions remain same as
described under point no 1.
If
Inverter of UPS B fails, automatically static bypass switch (VTT1B) gets opened
and static bypass switch (VTT2B) gets closed within 5 milli seconds. The PDB is
fed through the bypass line UPS –B. The inverter failure is displayed on LCD
through 4 lines of 16 characters along with audio – visual annunciation
provided in the mimic of UPS Panel (inverter cubicle). The same annunciation
for failure is also duplicated in ROP substation through substation PC. Circuit
breakers positions remain same as described under point no 1.
If
inverter sections of UPS A and UPS B fail simultaneously, the loads will be
transferred to bypass line of UPS B automatically.
The corresponding loads can also be fed
through class III bypass lines under administrative control through Manual
Bypass Switch (MBS) if felt necessary.
4. Failure of battery or Battery circuit breaker
of UPS :
In such cases, loads of UPS A and loads of
UPS B will continue to be fed by input class – III power supply through
rectifier and inverter. In this case if class III power or rectifier or
inverter of corresponding UPS A fails, then the loads gets transferred to UPS B
automatically within 5 milli second. If
the circuit breaker Q1B or rectifier or inverter of corresponding UPS B fails,
then the loads gets transferred to bypass line of UPS B automatically within 5
milli second as mentioned in point no 2 and 3. The failure of battery or
battery circuit breaker is displayed on LCD through 4 lines of 16 characters
along with audio – visual annunciation provided in the mimic of UPS Panel
(inverter cubicle). The same annunciation for failure is also duplicated in ROP
substation through substation PC.
5. UPS –A is under maintenance and UPS – B is
feeding loads of UPS A
When the UPS A is taken under maintenance,
circuit breaker CB-1 is opened manually. The mean time to repair (MTTR) is 8
hours. Under this scenario, if
Rectifier
section of UPS B fails, and then Battery – B will feed loads automatically.
Since battery back up is for one hour, all-necessary plant shut down operations
related to load of UPS - A and UPS - B will be carried out within this time.
Subsequently, the entire loads get transferred to by pass lines of UPS B
automatically.
Inverter
section of UPS B fails, automatically Static Bypass Switch (VTT1B) gets opened
and Static Bypass Switch (VTT2B) gets closed within 5 milli seconds. The entire
load is fed through the bypass line UPS –B.
Above
5.1 and 5.2 conditions are considered as total class –II power failure and
plant operations are to be stopped.
6. UPS –B is under maintenance and UPS – A is
feeding IPDB-1 & IPDB –2 and load of
UPS B is fed through the bypass line of UPS B
Under this scenario, If
Rectifier
section of UPS A fails, then automatically its battery feeds load. Since
battery back up is for one hour, all-necessary plant shut down operations
related to load of UPS A and B will be carried out within this time.
Subsequently, the entire loads get transferred to by pass lines of UPS B
automatically.
Inverter
section of UPS A fails, automatically the load of UPS A is fed through the
bypass line UPS –B.
By pass lines of UPS A can be energised by
closing Manual Bypass Switch (MBS) under administrative control, if felt
necessary.
Above condition is considered as total
class –II power failure and plant
operations are to be stopped.
- Class-II bus fault on anyone of class
– II distribution (IPDB’s) panel:
When there is a fault (short circuit) on any bus, the outgoing breaker
CB-3, CB-4 of corresponding UPS (A or B) trip on over current. Failure is
displayed on LCD through 4 lines of 16 characters along with audio – visual annunciation
provided in the mimic of UPS Panel (inverter cubicle). The same annunciation
for failure is also duplicated in ROP substation through substation PC. Then
power supply to the respective loads connected to the affected bus will not be
available. Under this condition all process transfers will get automatically
stopped, all pumps will stop, solenoid valves will get de-energized/ closed and
plants will go under safe shut down state as analyzed under black out
condition. Fire Alarm System, Telephone exchange has their own batteries as a
back up source of power for 4 hours.
8 Failure of class-III power supply
8.1 Failure of DG-1
On the failure of DG-1, UPS-A feed IPDB-1 & IPDB-2 through its
battery & inverter. Subsequently
batteries start discharging and on “LOW BATTERY” (87.5 % of rated voltage)
signal, automatically static Bypass Switch (VTT1A) gets opened and Static
Bypass Switch (VTT2A) gets closed within 5 milli seconds UPS- B starts feeding
load of UPS- A in addition to PDB. The Incomer of the UPS A failure is
displayed on LCD through 4 lines of 16 characters along with audio – visual
annunciation provided in the mimic of UPS Panel (inverter cubicle). The same
annunciation for failure is also duplicated in ROP substation through substation
PC.
8.2 Failure of DG-2
On the failure of DG-2 the batteries of UPS-B feed PDB through its
inverter. Subsequently batteries start discharging and since battery back up is
1 hour, so by opening CB-4, CB5 and by closing CB-7, CB-8 manually, PDB is fed
by UPS-A through tie line between IPDB-1 and IPDB-2. This will lead to
temporary interruption of UPS power supply to the loads connected to PDB,
including Fire Alarm System and Telephone Exchange. The FAS has a built in
battery having capacity of operating upto 4 hours, hence the interruption of
UPS supply will not affect its performance. Also an independent Public address
system is provided for the plant so short interruption does not affect the
performance of the system. The Incomer of the UPS B failure is displayed on LCD
through 4 lines of 16 characters along with audio – visual annunciation
provided in the mimic of UPS Panel (inverter cubicle). The same annunciation
for failure is also duplicated in ROP substation through substation PC.
9
Failure of input circuit breakers
9.1
Failure of CB-1 of UPS A :
On the failure of CB-1, UPS-A feed IPDB-1 & IPDB-2 through its
battery & inverter. Subsequently
batteries start discharging and on “LOW BATTERY” (87.5 % of rated voltage)
signal, automatically static Bypass Switch (VTT1A) gets opened and Static
Bypass Switch (VTT2A) gets closed within 5 milli seconds UPS- B starts feeding
load of UPS- A in addition to PDB. The CB1 failure is displayed on LCD through
4 lines of 16 characters along with audio – visual annunciation provided in the
mimic of UPS Panel (inverter cubicle). The same annunciation for failure is
also duplicated in ROP substation through substation PC.
9.2 Failure of CB-2 of
UPS B :
On the failure of CB-2 the batteries of UPS-B feed PDB through its
inverter. Subsequently batteries start discharging and since battery back up is
1 hour, so by opening CB-4, CB5 manually and by closing CB7 & CB8, PDB is fed by UPS-A through tie line between
IPDB-1 and IPDB-2.
Failure of CB-2 is displayed on LCD through 4 lines of 16 characters
along with audio – visual annunciation provided in the mimic of UPS Panel
(inverter cubicle). The same annunciation for failure is also duplicated in ROP
substation through substation PC. This condition is similar to condition 8.2 as
mentioned above and it will be applicable.
10 Failure of input supply to both UPS A &
B simultaneously:
On the simultaneous failure of incoming supply to both UPS, both UPS
will work on their respective battery for 1 hour and plant has to be shut down
in the planned manner. In this condition both UPS will be out of synchronism.
On the failure of inverter of UPS A, loads get transferred to healthy inverter
of UPS B with a break of about 5 m sec.
No comments:
Post a Comment