7.3.2
SWITCHGEARS (GENERAL FEATURES)
(a) 33 kV
The 33 kV
switchgear panel comprise of:
i) 2 Nos. of 33
kV, 1250 A/1500 MVA vacuum incoming circuit breakers.
ii) 1 No. of 33 kV, 1250 A/1500 MVA bus section
vacuum circuit breakers
iii)
8 Nos.
of 33 kV, 1250 A/1500 MVA outgoing vacuum circuit breakers.
The switchgears
shall feed all ROP and PREFRE transformers and shall also extend main power
supply to proposed UNCF project at 33 kV level through 2 nos. under ground
cables. The switchgears shall be of draw
out type and are dust and vermin proof with IP-52 enclosure. Access to circuit
breakers' operating mechanism shall be through compartment doors provided with
hinges and key-type locks. Instruments and relays are mounted on hinged type
panels. Different components shall be housed in different compartments to
enhance their accessibility for maintenance.
Various
metering devices shall be provided for monitoring the performance of the 33 kV
switchgear. Technical particulars of 33 KV indoor VCB switchgear are listed in
Table V.
Numerical Protective devices (relays) shall
also be installed on the switchgear for protection against various fault
conditions.
SALIENT
FEATURES OF NUMERICAL RELAYS
-Multiprocessor architecture with parallel
processing offers high speed of fault detection at
competitive
price.
-Decentralized modular approach with a separate processor for each task
admits of ease of
modification
or addition.
-Since relay settings are software governed,
modifications can be made over a large dynamic
range without any physical modification.
- Reliability and security are greatly
enhanced.
-Algorithm dependent performance of relay is
predictable to a high degree of accuracy.
-User friendly yet highly capable.
- Increased Communication ability.
(b) 415 VOLTS
415 V class-IV switchgear panel in sub-station shall
comprise of :
i) 2 Nos. of 415 V, 4000 A/46 MVA incoming air circuit
breakers.
ii) 1 No. of 415 V, 4000 A/46 MVA bus section air
circuit breaker
iii) 36 Nos. of outgoing feeders comprising of 415 V
ACBs and MCCBs.
iv) 2 Nos.of 2000 A tie-line air circuit breakers for
PREFRE switchgears.
v) 2 Nos.1000 A air circuit breakers for SFSF
switchgears.
vi) 2 Nos. 630A MCCBs for AWTF.
7.3.3 BUS DUCT
(GENERAL FEATURES)
2 Nos. of 415 V, 4000 Amps, 46 MVA, 3 Phase,TPN
compact bus duct shall be laid between medium voltage switchgears and 33 /0.433
KV transformers.
Busduct system
shall be low impedance, sandwich epoxy resin insulated type construction of
approved manufacturer, current ratings as detailed on the drawings/schedules
and complying to degree of protection IP54. The duct is so fabricated that it
shall be in a position to withstand, without damage, pressures (internal/
external) resulting from maximum fault condition. The busduct shall have heat
and fire resistant surface that would prevent corrosion. A readily accessible
ground strip shall run along the entire length of the duct. The ground conductor running along the bus
duct shall be of copper of minimum size 50x6 mm2 . The ground bus
(50x6 sq.mm copper strip) shall be provided with clamp type terminals at the
end for connection with earth mat system. The busduct supports shall withstand
thermal and mechanical stresses.
The Busbar shall
be designed and manufactured to comply with BS EN 60439-1&-2 (IEC 439) and IS-8623 (1&2). This should
be suitable for up to 1100 volt, 3 phase, 4 wire, 50Hz system, and capable of
withstanding prospective fault level currents of 65kA rms.
The bus duct
insulation shall be epoxy / mica-polyster insulated class F type of 1000V
grade, coated concentrically over the entire length of the conductor. The
insulation shall be non-toxic, chemically inert, stable material and also
fire-retardant. The insulator shall posses sufficient mechanical strength to
withstand the forces due to momentary short circuit and mechanical shocks
generated by 65 kA short circuit current.
The bus duct
enclosure shall be 1.6 mm thick CRCA sheet housing with epoxy powder coating.
The epoxy paint thickness over the enclosure shall be minimum 50 micron. The
enclosure should provide excellent rigidity and mechanical strength. The degree
of protection shall be IP-54. The bus-duct system should carry rated current up
to an ambient temperature of 40°C. Maximum temperature rise admissible
shall be limited to the insulation class-B when loaded with continuous rated
current.
Class-IV non-safety related systems of ROP
are listed in the following table:
Group-A Non Safety
Related Systems
|
Group-B Non Safety
Related Systems
|
CLASS-IV NPCC PANEL
MCC –1 (V1 + V2 SUPPLY FAN)
|
MCC –2 (V1 + V2 SUPPLY FAN)
|
MCC (PCW–RUNNING)
|
MCC (PCW –STANDBY)
|
MCC (FHA - NORMAL )
|
|
MCC
(A/G + MUA-2 )
|
|
MCC (MUA-3 + DM WATER AREA )
|
|
MCC (A/G + HUT BASIN)
|
|
MCC
(MUA – 1)
|
|
MCC (NO2 GAS AREA)
|
|
MCC (TSA-1)
MCC (TSA-3)
MCC (TSA-2)
MCC (DECONTAMINATION ROOM )
MCC (AHU -RECONVERSION
LAB))
|
|
MCC (FORMALDEHYDE
AREA )
BOILER & COMPRESSOR MCC
CHILLER MCC
HIGH BLOCK –MLDB-N & 6 Nos. LIGHT.
POWER DBs
3 NOS. LIGHTING PDBs
1 No. AIR HANDLING UNIT POWER-
DISTRIBUTION BOARD
|
|
7.3.4 OPERATING
PHILOSOPHY OF CLASS-IV POWER SYSTEM
7.3.4.1 In case of loss of power supply on one
bus-section of NPCC (Normal Power Control Centre), power supply to the other
bus-section shall be restored by closing the bus-coupler breaker of NPCC
automatically/ manually.
7.3.4.2 In case of failure of incomer breaker of an MCC or the cable
incomer of MCC or upstream breaker of corresponding NPCC, standby motor shall be
started from the corresponding group of MCC.
7.3.4.3 In case of failure of any motor-starter or the outgoing feeder
of an MCC, standby motor shall be started from the corresponding group of MCC.
7.4 CLASS -III POWER SUPPLY SYSTEM
7.4.1 415 V
SWITCHGEARS
415 V class-III
switchgear panel in sub-station shall comprise of :
i) 2 Nos. of 415 V, 2500 A/46 MVA incoming air
circuit breakers.
ii) 2 Nos. of
415V, 1600 A/46MVA incoming air circuit breakers.
iii)2 Nos. of
415V, 2500 A/46 MVA bus section air circuit breakers
iv)2 Nos. of 415
V, 1000 A/46 MVA spare air circuit breakers.
v) 28 Nos. of
outgoing feeders comprising of ACBs and MCCBs.
vi) 2 Nos
630A MCCBs for SFSF.
vii)2 Nos. 630A
MCCBs for AWTF.
Technical
specification of PCC (NPCC and EPCC) panels is enclosed vide Table-VIII.
7.4.2 DIESEL GENERATORS
Two numbers of diesel generator sets of capacity
1010kVA each conforming to ISO 3046 shall be installed in sub-station for
providing 415V, 50Hz grounded AC power supply to the plant's safety related
loads during normal power failure/ outage conditions. The DG sets shall have the capability to
start from cold condition, reach synchronous speed and be ready to take the
load, without undue stress, in about 10 seconds from the initiation of start impulse. The generators shall
be capable of accepting their maximum rated load in
single or multi steps. When the machine
is running in no-load condition at the rated voltage and speed, the transient
voltage drop at its terminals on starting the exhaust fan motor drawing a huge
starting current at 0.3 power
factor shall
not exceed 10% of the rated voltage. When the machine is running at 80% load at
0.8 power factor at the rated voltage and speed, the corresponding voltage drop
on starting the same motor shall not exceed 15%. The response of the regulator and excitation
system shall be such
that following a step
application or rejection of rated load at rated power factor and
subsequent to the drop or alternator rise of sub-transient voltage, the generator
will recover its set voltage within 0.5 second.
The alternator shall be capable of taking momentary overload. Rating of the two DG sets shall be so chosen
that the entire emergency load of the plant can be continuously fed even if one
of the sets fails.
The control panel design shall include microprocessor
based fast and reliable control system.
The DG sets shall be provided with an independent cooling tower. Each DG set shall also be provided with an
independent day tank of 2500 ltr. capacity for storing the fuel. On
consideration of fire safety, these tanks shall be located outside of the room in which the DG
sets are installed. In
addition to the
local storage of fuel, supply of fuel for 7-day continuous operation of one DG
set, from the bulk storage facility shall also be made available.
In the event of
normal power failure, the DG set will start automatically. The entire essential base loads like plant
lighting, health & safety instruments, plant communication equipments etc.,
shall be fed within 30 seconds. The
design envisages manual connection of bulk loads like exhaust and off-gas fans
one by one in a pre-set sequence to protect the generator from the effects of
surge currents arising immediately after connecting a bulk load.
Technical specification of DG set is enclosed vide
Table-IX.
The Safety related power supply system is categorized
into two groups, Group-A and Group-B. Power Supply System belonging to Group A
Safety Related System and Group B Safety Related System are identified in the
following table:
Group-A Safety Related
Systems
|
Group-B Safety Related
Systems
|
CLASS-III EPCC PANEL (GROUP-A)
MCC –1 (E2 FAN)
|
CLASS-III EPCC PANEL (GROUP-B)
MCC –2 (E2 FAN)
|
MCC –1 (OFF GAS FAN)
|
MCC –2 (OFF GAS FAN)
|
MCC-E (FHA)
MCC
(E- COMPRESSOR)
|
|
HIGH BLOCK-MLDB-E & 6 NOs. LIGHTING PDBs
|
|
UPS SET – 1
|
UPS SET – 2
|
UPS DB- 1
|
UPS DB – 2
|
DC SWITCHBOARD-1
1 No. LIGHTING PDB
|
DC SWITCHBOARD-2
|
7.4.3 OPERATING PHILOSOPHY OF CLASS-III POWER SYSTEM
7.4.3.1 In case of loss of power
supply on one bus-section of EPCC (Emergency Power Control Centre), power
supply to the affected bus-section shall be restored by starting the DG set of
that section automatically/ manually.
7.4.3.2 In case of failure of incomer breaker
of an MCC or the cable incomer of MCC or upstream breaker of corresponding
EPCC, standby motor shall be started from the corresponding group of MCC.
7.4.3.3 In case of failure of any
motor-starter or the outgoing feeder of an MCC, standby motor shall be started
from the corresponding group of MCC.
No comments:
Post a Comment