Thursday, 23 April 2015

TECHNICAL PARTICULARS OF THE DIESEL ENGINE & AUXILIARY SYSTEM

1.    DIESEL ENGINE

1.1 Basic type                                                              IC type, 4 strokes, vertical single acting, with electronic fuel control governor & STC Injector.

1.2 Rating                                                                    Net Engine output  (prime power) 1180 BHP/ 880 KWm           

1.3 Make & Cat. No                                                    Cummins India Ltd., KTA-38-G5

1.4 Catalogue Rating                                                    Prime power continuous rating

1.5 Reference standards for generator sets                                ISO 8528, 3046/1
BS-5514, 4999,5000
IEC 34/1

1.6 Diesel engine BHP                                                   1180 BHP with 10 % margins
(1010 KVA)

1.7 Engine Weight                                                       4500 Kg

1.8 Dimensions of DG set                                                         5.7 X 2.2 X 3.3  mtrs. Approx.

1.9 Foundation size                                                     6.7 X 3.2 Mtrs. Approx.

1.10 Room dimensions                                                7.4 ( L) x 6 (W) x 8 (H) mtrs.

1.11  Rating under    a) Catalogue rating a  NTP       1180 BHP     
condition                    
                                  b) site conditions                       1180 BHP
                                  c) test bed condition                  1180 BHP

1.12    Rotation direction (viewed from free end)        CW from coupling end

1.13 Type of start                                                        Motor Driven compressor type (Air Start)

1.14 Engine Noise level (dB)                                       110 dBA at 1 mtr distance

1.15 Engine Noise level with accoustic(dB)                75 dBA

1.16   Operating speed                                                 1500 RPM

1.17    Max over speed permissible                             1800 RPM

1.18    Number of strokes per cycle                             4 strokes

1.19    Number of cylinders                                         12 Cylinders

1.20    Air cylinder capacity                            1 kl cap for 3 nos. of start and DG lockout

1.21   Operating pressure                                             150 PSIG

1.22   Arrangement of cylinders                                  60 degree, Vee with rigid gray cast iron cylinder block complete with integral oil and water galleries

1.23   Bore                                                                   159 mm

1.24   Stroke                                                                               159 mm

1.25   Compression ratio                                              13.9:1

1.26   Maximum period for which the diesel can                       3 Min.
          operate without cooling water after starting

1.27 Maximum firing pressure                                     10.56 Kg/cm² (g)

1.28   Mean piston speed                                             7.9 mps

1.29 Brake mean effective pressure at                         10.46 K Pa
       rated load(BMEP)
1.30   Cyclic irregularity                                              < 1 / 75 %

1.31   Maximum engine rating                                     880 KW + 10% over load

1.32   Overload capacity                                             10 % overload for 1 hour in 12 hours

1.33   Combined shaft system critical Speeds               2100  RPM

1.34   Turbocharger critical speeds                              1,00,00 RPM

1.35   Firing order (viewed from power                       1R-6L-5R-2L-3R-4L-6R-1L-2R-5L-4R-3L
          take of end)

1.36   Jacket Water temperature rise at  rated load     70 C to  95 C

1.37 Minimum time of operation without
        cooling water availability during start up 3 min

1.37  
       a) Raw water Flow rate                                         673  lpm

       b) Raw water Temp. rise                                       43.3 C
     
      c) Raw water inlet temp.                                        33.3 C

1.38  Jacket water temp. to & from engine                 95ºC

1.39   Fuel system injector pressure                             10.56 Kg/cm² (g)

1.40  Fuel consumption at rated load                           201 gms / KWHR (± 5%)

1.41 Fuel specification for engine                                 Grade no.2D as perASTM D975/ IS-   
                                                                        1460 2000

1.42 Lubricating system oil pressure at pump              3.2 – 4.9 Kg/cm² (g)
        discharge

1.43 Lubricating oil consumption at rated Load           0.18 lph / kWh

1.44 Time for diesel engine to start / run without         3 minutes
         supply of raw water       

1.45   Maximum time required to start the                15 Sec.
       diesel from normal preheated condition
       to bring up to rated speed and load upto
       its capacity without exceeding voltage
       and frequency limits.

1.46   Maximum allowable lubricating oil temperature.    105°C
      
1.47   Ventilation air requirement
                        Temp. rise -  5 oC ambient           1200 lph.    
                        Temp. rise - 10 oC ambient          7800 lph.

1.48   Capacity of hoist provided for   normal maintenance    5 Tons

1.49  Engine management system                               shall be provided in PCC (Power Command    Control Panel)

1.50 Seismic requirements                                           (as per IS 1893)

1.50 Emission norms compatibility                              meeting latest CPCB emission norms

1.55 Overload capacity for 1 hr in 12 consecutive
         hours of operation,                                                         10%

1.56  Duration of no load operation                       Half an hour in 12 hours(Cumulative 2 hours in 3 month)
1.57 Duration of 30%load                                                          30 minute

1.58 Parellel operation of DG set as required.                        Provided

1.59 Sequence of loads to be applied to DG Set                     As per tender

2.0 TECHNICAL PARTICULARS OF GENERATOR AND EXCITATION SYSTEM

2.1 GENERATOR AND ACCESSORIES

Type                                                    Brush less, revolving field

Make                                                  STAMFORD

Catalogue no.                                       HCK634Z2

Rating                                                  1100 KVA

Prime power continuous output rating (Under site condition)            800  KW.

Alternator weight                                 2270 Kg

No. of phases                                      3 phase, 4 wire

Winding connection                             Y (Star)

Overload capacity for 1 hour in
12 consecutive hours of operation       10%
           
Rated Frequency                                  50 Hz

Winding                                               Double layer type (lap)
                                                            Dual coated class 200 copper wires
                                                            Epoxy coated winding

Winding pitch                                      Skewed stator 2/3 winding pitch

Winding leads                                           6

Stampings                                            low silicon stamping with 90-degree orientation

Damper winding                                                Continuous

Design ambient temperature               45 °C

Derating factor for site condition        3 %

Power factor                                        0.8 lag

Rated voltage/Voltage at terminal
Block                                                   415 Volts.

Rated current per phase                        1330 Amps

Short circuit current per phase                3 x Ifl  for 3 second
Limits of voltage adjustments                 ± 5 %

Frequency adjustment                                +/- 5%

Type of cooling                                  Natural air

Cooling Air                                          1.614 m3 / s

Bearing Drive End                               Ball 6224 – 2RS (ISO)

Bearing on non drive end                    Ball 6317 – 2RS (ISO)

Types of Enclosure                              IP 23

Speed                                                   1500 RPM

Frequency                                            50 Hz.

Over speed permissible for 2 minutes             20 %

Field current at rated output and Voltage         2 Amps & 72 volt

Insulation                                             Stator              H
                                                            Rotor               H

Temperature rise restricted                   Class F

Over load capability for 1 hours in                  : 10 %
12 consecutive hours of operation
 without undue heating of the
 alternator or any other mechanical
trouble.

Momentary over load current permissible           150% for 15 second

Permissible transient voltage dip under
starting of highest rating motor                                    15%

Steady state voltage regulation (0.5-1%)                    0.50%

Harmonic loading of generator                                      70% of rated capacity

Telephonic Influence factor                                        2 %

Generator parameters

Synchronous Reactances xd, xq                    201% & 129 %

Transient Reactance Xd'                                   12 %

Sub transient Reactance Xd"                            9 %

Sub transient Reactance Xq"                            18 %

Zero sequence reactance Xo,                            2 %

Negative sequence reactance X2                      14 %

Leakage reactance                                           9%

Time constant                
Sub transient time constant      0.015 S
Transient time constant            0.045 S
OC field time constant 3.17 sec
Armature time constant            0.026 S

Short circuit ratio                                             0.497

Waveform deviation factor on load                 10% L to L

High harmonic load capability                                       2.5 %

Sustain short circuit current                             300 % for 3 sec.

Resistance of main field winding at
operating temperature                          0.00384 Ohms

Full load efficiency                                               95.4 %

Specified operating conditions over 45° C ambient                 class F

Generator Constructional Details  (referred GA drawing enclosed)

Air gap length                                                  3 mm

Terminal box arrangement and                     Extension Box
recommended cable for connections

Main Exciter

Type of exciter                        Brush less type with rotating diodes complete with revolving armature A.C exciter, permanent magnet generator (PMG) type pilot exciter.

Rated voltage                          72 Volts

Rated current                          2.0 Amps

Insulation class            Stator             Class H
                                     Rotor             Class H

Automatic Voltage Regulator

Literature on AVR, Exciter, generator                          Enclosed

Type of regulator                                                         Solid State (Automatic voltage regulator).
AVR shall have cross compensation feature.

Make                                                                           NUPART

Transient and steady state voltage variation                 within ±0. 5 % (as per IS 4722)

Burden of AVR                                                           < 5 VA

Dead band of regulator (if any )                                  Zero

Voltage setting range                            : 1 %.

Steady state accuracy                           : +/- 1%

Response time                                     :Less then 100 milli sec. 

Response of voltage regulator & excitation system.
Maximum period to recover the generator voltage
to the set value of step rejection of Rated load at
rated power factor                                                                               < 10 Second

Time period for which  generator shall be capable
of withstanding Without injury a 3 phase short
ckt at rated KVA and power factor at 5 %
Over voltage with fixed excitation                                                       3 second

Voltage adjustment                                                                               ± 10% 

Voltage setting range of regulator                                                        ± 0.5%
 
Steady state accuracy of the voltage regulator
from no load to full load                                                                     As per IS 4722

Quadrature droop circuit shall be  provided to limit the reactive KVA during parallel operation

TEMPERATURE DETECTORS

No.                              : Minimum 2 nos  resistance type temperature detector for phase and 2 nos. on bearing

Type                            : PT-100    (RTDs & BTDs )
           
SPACE HEATERS

Capacity                      : 60 Watt  rated 240W , 50 Hz

 Number                      : 4 nos.

3. CONTROL PANEL

Type of control panel            Vertical free standing, floor mounting Indoor type
                                                Make : Powerica

Type of control system            24 V DC

Material                                   CRCA sheet steel (2 mm thick), dust weather and vermin proof powder coated epoxy painting.

Degree of protection                IP 54 (AS PER IS 2147)

Cable entry                              bottom

Overload capacity                    10 %

Design ambient air temperature              45 C

HRC Fuse breaking capacity                            80 KA

HRC Fuse continuous current rating                2A/6A/10A/16A

Colors of the finish paints

  a) Outside                                Siemens Grey as per IS-5

  b) Inside                                 Siemens Grey as per IS-5

The final finish shall be with powder coated painting.

Control Cabinet                       compartmentalised into sections segregated by sheet metal barriers

Control panels                      Minimum 2 sections
Control panel shall containing :
i) Instrument panels                

ii) Annunciators                       

            iii) Starter / Aux MCC panels                      

            iv) Synchroscope                      

            v) Bus-bar panels                    

LCD display on electronic control panel                      water temperature, oil pressure, engine RPM, Engine          (Engine mounted panel)                                              run hour meter

, , , ,
Type of synchroscope                                                 Cummins make provided in GCU (Generator control unit)

Type of AMF                                                               Provided in (Generator control unit)

PC compatibility                                                          Control panel is PLC based and PC compatible, GCU provided with RS 485 indication port

DG incomer breaker                                                    ACB (EDO Type) L & T Make provided in AMF panel

Starters for DG auxiliaries                                           provided in DG panel

TECHNICAL PARTICULARS OF CONTROL, INSTRUMENTATION & PROTECTION

Scheme of AMF (Auto Mains Failures)
Under the normal condition, all the ac loads will be fed by the `mains' power supply. The proposed D.G. Sets will be connected to the emergency load buses, which will also be fed by the `mains' power supply under normal condition and the D.G. sets will serve as stand-by. In the event of `mains' power failure, all breaker on that bus will be opened up automatically and starting impulses shall be given to the respective D.G. Sets. Once the set has run upto the rated speed and has developed rated voltage it shall be automatically connected to the respective emergency bus. Emergency loads shall then be switched on automatically / manually in a predetermined sequence on this bus. When mains power supply is restored, the D.G. set will be synchronised to  it and shall be subsequently switched off manually. Similarly, sometimes  the D.G. sets will be required to run in parallel with each other for facilitating proper load distribution and uninterrupted load transfer.

The Switchgear has two bus sections i.e. bus section – 1 & bus section –2 coupled by 2 nos. bus-couplers, which are normally open. Bus-section –1 & bus-section –2 are fed from normal main power through breaker 1 & 2 respectively, which are normally closed. DG set I & DG set II are connected to these two buses through breaker 4 & 5 respectively, which close only when DG sets starts & develop rated voltage. Each DG set shall operate & feed loads as specified later. Each DG set shall have independent control panel, starting system, fuel oil system & there shall be nothing common between these two sets. DG set shall have four modes of operation selectable through switch located on AMF control panel. These modes are a) Manual b) Auto c) Test & d) Stop / Isolated.

Manual mode :- In manual mode it shall be possible to start & stop DG set through push buttons provided on AMF panel. After set develops rated  voltage, breaker 1 & 2 shall be tripped manually. Breaker 4 & 5 shall be closed to connect loads to DG set, only if breaker 1 & 2 are tripped.

Auto mode:- In auto mode, DG sets shall always be ready to start upon failure of normal power. Readiness of sets shall be continuously monitored by sensing condition of starting air compressor, availability of raw cooling water, availability of fuel & same shall be displayed on annunciator as “DG set ready to start”. In case of failure of power or under voltage on emergency bus section 1 and / or bus section 2 respective normal breaker shall trip & respective DG set shall start automatically. 3 phase, 4 wire supply line connection shall be provided for use of DG set vender from bus section 1 & bus section 2. DG vender shall use this supply for monitoring healthiness of voltage at emergency bus section namely bus section 1 & bus section 2  & start DG set as & when required using under voltage relay.

Test mode:- In test mode, set shall start & stop on commands from AMF panel. No load will be connected to DG set. Set shall trip after a preset time if not stopped manually. Facility for dummy loading of DG sets shall exists without affecting plant operation.

Stop / isolated mode: - DG shall not start.      

Time: The sets shall be ready to feed loads in maximum of 10 sec from the instant of failure of normal power supply, during auto mode of operation. Loads will be connected to the generator sequentially either through PLC or relay based system.

Permissible voltage dip during switching on loads to DG sets; It is required to start the loads in sequence to limit transient voltage dip at bus section 1 & 2 to 15 % of 415 volts. This is necessary to ensure that remote control contactor picks up reliably during auto start of DG sets. The supplier shall ensure TVD (Transient voltage dip) at bus does not fall below above limit at any stage of switching the loads.

Class III switchgear - AMF panel DG set breakers CB4, CB5 and bus section breaker CB3 will be kept open and power supply from each incomer  (CB1, CB2) will be confined to the respective bus section. Provision exists for the selection of auto/manual mode of starting the DG sets.

GENERATOR CONTROL UNIT (GCU)
GCU control panel provided with DG set shall have following features:

a)      Digital governing, voltage regulation, synchronizing, load sharing and paralleling with main bus (Grid)
b)      Protection of alternator against over current protection
c)      Analogue and digital AC output metering
d)      Battery monitoring system to check weak battery condition
e)      Digital alarm and status message display
f)       Genset engine monitoring system
g)      Smart stealing control feature
h)      Network capability
i)        IP 54 protection
j)        PC compatibility

PROTECTION

     The Diesel Generator set shall be tripped under the following conditions:
  i)  110 V D.C. control supply failure.

ii) Over speed of Diesel Generator set as sensed by tachogenerator and mechanical Overspeed trip mechanism.

  iii)  Low lube oil pressure after engine has attained 90% speed.

  iv) Excitation failure due to tripping of field AC, CB or failure to build up voltage.

  v)  Fuel oil pressure low after 90% speed.

  vi) Fire detector device actuated.

  vii) Incomplete start after a preset time.

 viii)  Low level in fuel tank

   ix)  High lube oil  temperature.

    x)  High jacket water temperature sensed by thermostat.

   xi)  Restricted earth fault protection.

  xii)  Reverse power protection.

 xiii)  Negative phase sequence protection

  xiv)  Over-current protection.

   xv)  DG earth fault.

  xvi)  Output overvoltage.

xvii)   Emergency stop.

xviii)  Output under voltage.

xviv)  Under frequency.

Alarm and Indications

Local-Alarm on Diesel Control Panel

            A window type annunciator panel shall be supplied & mounted on each diesel control panel to give visual and audible indication on occurrence of any one or more of the following troubles:

i) High ambient temperature in Diesel Room when the DG set is operating.  

ii) High jacket water temperature.

iv) Standby lube oil pump inoperative.

v) Lube oil pressure failure and trip of engine.

vi) Pre-lube oil pump inoperative.

vii) Lube oil tank level low.

ix) Starting air pressure low.

x) Air pressure very low (only two starts possible).

xi) Diesel Generator Auxiliary trouble (combined annunciation for tripping of auxiliary motors).

xii) Fuel oil day tank level low.

xiii) Fuel oil day tank level high.

xiv) Generator winding temperature high.

xv) 110 V DC failure.

  xvi) Restricted earth fault protection.

 xvii) Reverse power protection.

 xviii) Negative phase sequence protection.

 xix) Over-current protection.

 xx) Earth fault protection.

 xxi) Under voltage protection.

 xxii) Over-voltage protection.

xxiii) Emergency stop.

 xxiv) Starting failure.

xxv) DG set Overspeed.

xxvi) Generator excitation failure.

xxvii) Fire detector device actuated.

xxviii) Generator bearing temperature high.

xxix) Engine bearing temperature high.

xxxi)  Two spare windows for use of purchaser.

 Each annunciator panel shall be provided with:

  1. A push button for clearing the available alarm.(The visual annunciation will persist).

  1. A push button for clearing the visual annunciation after the   fault has been cleared.

  1. A push button for testing the illuminated transparencies.

After acknowledgement of one trouble by clearing the audible alarm the alarm circuit shall be ready to operate for another fault.

All alarm devices shall be suitable for operation on 110 V/24 V DC.

Table-VIII


POWER CONTROL CENTRE (PCC) PANELS


Sr. No.
Description
Specification
1.0
Standards applicable
IS 13947, IS-8623
3.0
General features of ACB, MCCB

3.1
Rated voltage
415V
3.2
Maximum voltage at which breaker can operate continuously
690V
3.3
Rated frequency
50 Hz
3.4
Current rating
As per latest single line diagrams (A2/RP.05.01.01/01/Rev-1 & A2/RP.05.02.01.2/01/Rev-1)
3.5
De-rating factor for site conditions
Upto 500C, no de-ration
3.6
ACB & MCCB of PCC (NPCC & EPCC) panels with microprocessor based release
Confirmed
3.7
ACB & MCCB of PCC (NPCC & EPCC)     communication capable type.
Confirmed
3.8
Make (model) and protections available in I/C ACB of PCC panels
Siemens (ETU-45B); O/L, S/C, E/F, U/V, O/V, U/F, O/F, reverse power, current unbalance, temp. monitoring , uP trip error, I-discrimination, all metering & text display
3.9
Make (model) and protections available in O/G ACB of PCC panels
Siemens (ETU-45B); O/L, S/C, E/F, U/V, O/V, U/F, O/F, reverse power, current unbalance, temp. monitoring , uP trip error, I-discrimination, all metering & text display
3.10
ACB with continuous duty trip coil
Confirmed
3.11
Make (model) and protections available in MCCB of PCC panels
Siemens (ETU-42);  O/L, S/C (delayed & instantaneous), E/F and current metering (In,Ir,Iy,Ie & Ig)
3.12
For ACB & MCCB, Icu=Ics=65 kA
Confirmed
3.13
Insulation level of the breaker (one minute dry withstand voltage, rms)
3 kV
3.14
Life of circuit breaker


Electrical
20,000 operations for Size 1 frame (with maintenance)
15,000 operations for size 2 frame (with maintenance)
10,000 operations for size 3 frame (with maintenance)

Mechanical
20,000 operations for Size 1 frame (with maintenance)
15,000 operations for size 2 frame (with maintenance)
10,000 operations for size 3 frame (with maintenance)
3.15
MCCB/ SFU in non-drawout module
≥ 630A
3.16
ACB provided in all incomers and Bus-couplers of 4-pole type
Confirmed
3.17
Positive isolation feature of MCCB
Confirmed for < 630A MCCB.
3.18
MCCB with door driving mechanism, shunt release, inter-phase barriers, pad-locking and defeat facility

4.0
PCC (NPCC & EPCC) Panels

4.1
Short time withstand rating of the assembly (r.m.s.) for 1 sec.
65 kAmp

4.2
Mechanical (momentary) withstand rating of assembly (peak)
136 kA
4.3
EPCC panel is physically two separate panels connected together by cable
Confirmed
4.4
NPCC panel is a physically single panel
Confirmed
4.5
Clearances
a)      Between phases (live parts)
b)      Between live parts and earth
c)      Creepage path to earth

25 mm
19 mm
25 mm
4.6
Power frequency withstand voltage of cubicle
a)      power wiring
b)      control wiring

3.0 kV rms for 1 sec
1.5 kV rms for 1 sec
4.7
MCC panels designed for structural integrity based on NNS, IS-1893
Yes, confirmed
4.8
Material and thickness of
(a)    Main frame work
(b)   Doors
(c)    Side cover
(d)   Partitioning sheet
(e)    Gland plate
CRCA Sheet
2.5/2.0 mm  
1.6 mm
1.6 mm                               
1.6 mm
3 mm
4.8

4.8.1







4.8.2
Internal wiring

Cross section & material of Conductor for

-power wiring

-control wiring
-C.T. wires


Type & voltage of insulation


Copper Wires

70 sq.mm (maxm)
4.0 sq.mm.(min.)
1.5 sq.mm.
2.5 sq.mm.

HRPVC wires, 1.1KV grade
4.9
Powder coating after 7-tank treatment
Confirmed
4.10
Paint thickness (epoxy based) in micron
50-60
4.11
Degree of protection for NPCC panel
IP42 for feeders having current rating> 2500A and IP52 for feeders having current rating ≤ 2500A
4.12
Degree of protection for EPCC panels
IP52
4.13
Provision of Panel space heater with thermostat switch
Confirmed
4.14
Panel indoor illumination with switch
Confirmed
4.15
One marshalling box for each bus section provided
Confirmed
4.16
Operating height of panels
350-1900 mm
4.17
Maximum length of shipping section
2000 mm
4.18
Conformity to SLDs
Yes
4.19
Earthing of panel doors
By 4.0 sq.mm.braided copper wire
4.20
Shrouding as required
Confirmed
4.21
Remote/ local selector switch provided for ACB feeders
Confirmed
4.22
Auto/ Manual selector switch provided for ACB feeders
Confirmed
4.23
Mechanical & electrical interlocks provided between both incomers of NPCC panel
Confirmed/ Mechanical not possible as either Electrical or Mechanical interlock will work.
4.24
Mechanical & electrical interlocks provided between 2-class-IV incomers of EPCC panel
Confirmed/ Mechanical not possible as either Electrical or Mechanical interlock will work.
4.25
Make of components
As per specification
5.0
Communication ports for SCADA connectivity
Communication ports of ACB, shall be brought to the marshalling compartment of the panel
6.0
HRC Fuse

6.1
Make
Siemens
6.2
Type
3NA-3
6.3
Current rating
As per SLD
6.4
Interrupting capacity
120 kA
6.5
Fusing factor
1.5
7.0
Rotary Switch/ SFU/ Disconnecting switches

7.1
Make
Siemens
7.2
Type
3KM/3KL
7.3
Rated voltage
550 V at 50Hz.
7.4
Rated current
As per SLD
7.5  
Rated making current
80 kA
8.0
Miniature Circuit Breaker (MCB)

8.1
Make
Siemens/MDS
8.2
Voltage rating
230V AC
8.3
Breaking capacity
10 kA
9.0
Control/ Selector switch

9.1
Make
Kaycee
9.2
Type
3R
10.0
Push Buttons

10.1
Make
Siemens
10.2
Type
3SB
10.3
No. of NO, NC contacts
2NO + 2NC
10.4
Off push button type
Mushroom/ Normal-Luminous
11.0
Bus bars

11.1
Material for PCC panels
Copper
11.2
Type of insulation
Heat shrinkable Black PVC sleeve (Class-E) with colour coding at suitable location.
11.3
Temperature rise of the bus-bars over the specified ambient temperature
500C over 450C ambient
11.4
Current rating of bus-bars (in house rating)
As per latest SLD
12.0
Ground Bus

12.1
Material
Copper
12.2
Cross section
40x10 sqmm.
13.0

Control Bus (Separate AC & DC control bus)


13.1
Physically separate control bus provided
Yes, confirmed
13.2
Material
Copper
13.3
Cross-section
5x5 sq.mm.
13.4
Control bus supply through double pole MCB
Provided
14.0
Protective electromagnetic relays on both I/Cs of NPCC Panel

14.1
O/C, UEF, REF, UVR, OVR
Confirmed
14.2
C.T provided for REF relay
4000/2000/5A, Class-PS
14.3
C.T provided for OC, UEF relay
4000/2000/5A, Class-10P10, 15VA
14.4
PT provided for UVR, OVR
2 Nos.415/ 110V, 25VA, class-1
15.0
Protective electromagnetic relays on I/Cs of EPCC Panel

15.1
Protective electromagnetic relays (OC, UEF, REF, UVR, OVR & Reverse power relay) provided on DG I/Cs of EPCC panel
Confirmed
15.2
Protective electromagnetic relays (OC, UEF, UVR) provided on Class-IV I/Cs of EPCC panel
Confirmed
15.3
C.T provided for OC, UEF relay on class-IV incomers
2500/1000/5A, Class-10P10, 10VA
15.4
PT provided for UVR, OVR on class-IV & DG I/Cs
2 Nos.415/ 110V, 10VA, class-1
15.5
C.T provided for OC, UEF relay on DG incomers
1600/800/5A, Class-10P10, 10VA
15.6
C.T provided for REF relay on DG incomers
1600/800/1A, Class-PS
16.0

Metering, Indication & Terminal Blocks


16.1
Load manager with 12-parameter display (displays max.demand also) provided
Confirmed (Enercon make, EM3480)
16.2
Window annunciators provided on I/Cs of PCC panels
Confirmed
16.3
Meters provided on all incomer feeders of NPCC & EPCC panels
Analog type Voltmeter with selector switch, Ammeter with selector switch and Frequency meter
16.4
Meters provided on PCC (NPCC& EPCC) O/G feeders
As per SLD
16.5
Auto changeover switch provided between I/C and B/C feeder of PCC panels
Confirmed
16.6
For microprocessor based ACB, HMI with suitable softwares and hardwares shall be provided
Confirmed
16.7
Potential indicating lamps (LED based) for all incomers through control fuse
Confirmed
16.8
ON indicating lamps for all outgoing MCCB feeders
Confirmed
16.9
Class-1 CT (Class-E insulation) for metering purpose
Confirmed
16.9
Class-1 VT (Class-E insulation) for metering purpose
Confirmed
16.10
10A DC contactor with 415V coil connected in NPCC & EPCC panel
Confirmed
16.11
20% spare terminals in cable alley
Provided
16.12
20% spare terminals as contacts
Provided
17.0
Cable/ Bus-duct entry to PCC Panel

17.1
NPCC Panel

17.1.1
Top bus-duct (compact sandwich) entry for both incomers
Confirmed
17.1.2
Outgoing feeder Nos.F6 & F24 shall have bottom bus-duct (compact sandwich) entry
Confirmed
17.1.3
All other outgoing feeders with top cable entry
Confirmed
17.2
EPCC Panel

17.2.1
Top bus-duct (compact sandwich) entry for all 4-incomers
Confirmed
17.2.2
All outgoing feeders with bottom cable entry
Confirmed
18.0
Others

18.1
Auxiliary power supply (24V d.c.) shall be provided for PCC panels through a power pack . The 230V input to the power pack will be from the incomer feeder.
Confirmed.
18.2
Cranking handle is an integral part of ACB
Confirmed

1 comment:

  1. The blog provides information on Technical Specifications of Powerica Diesel Engine and Generators. To get Dealers of Powerica DG set on Rental Basis, visit https://vidyutbazar.com/bazardirectory/powerica-rentals-dg/

    ReplyDelete