VACUUME
CIRCUIT BREAKER (VCB)
MAKE
|
Jyoti Ltd. Vadodara
|
Type
|
UY – 30M25
|
Rated frequency
|
50Hz
|
Rated Voltage
|
36000 Volts(36KV)
|
Rated Current
|
1250 Amps
|
Ms Level Imp
|
170KV P, PF-75 kv
|
Rated Breaking current
|
25 KA
|
Rated Making Current
|
63 KA peak
|
Sr. No.
|
B-242, Year- 2001
|
Supply Voltage Closing
|
110 VDC
|
Supply Voltage Tripping
|
110 VDC
|
Rated short time current
|
25 KA
|
Wt of Beaker
|
375 Kg
|
Standard
|
IS:13118/IEC-56
|
Making Capacity
|
2.55 x symmetrical ÷ Breaking capacity
|
Breaking Capacity
|
1000 x 106/√3 x 33000
|
ADVANTAGE
OF VCB
1.
They
are compact, reliable and have longer life
2.
There
are no fire hazards
3.
There
is no generation of gas during and after operation
4.
They
can interrupt any fault current. The outstanding feature of a VCB is that it
can break any heavy fault current perfectly just before the contacts reach the
definite open position
5.
They
require little maintenance and are quiet in operation
6.
They
can successfully withstand lightening surge.
7.
They
have low arc energy
8.
They
have low inertia and hence require smaller power for control mechanism.
9.
DISADVANTAGE OF VCB
1.
Air
chopping/current chopping
2.
Vacuum
leakage cannot be indentified
3.
Costly
MAKING CAPACITY: Breaker closes on fault condition, contacts does not
damage. Current on which a ckt breaker is capable of breaking under specified
condition.
BREAKING CAPACITY: Breaking current capacity of circuit-breaker, is the
highest value of short circuit current which a circuit breaker is capable of
breaking under specified condition.
In the circuit
breaker, breaking capacity is less than making capacity: When short circuit
occurs, there will be voltage drop. Thus voltage is less, current is also less.
So Coil temperature in the circuit breaker = 800.
We are having
OCB.VCB with low resistance zero common method. For zero method, contact,
material is used.
When breaker is
switching on & off, spark takes place & due to hydrogen gas heat
produced. To cool this heat and quenching of arc, vacuum is used.
High Vacuum: 10-5
to 10-8 Tor
PRINCIPLE
OF VACUUM CIRCUIT BREAKER
The production of
arc in vacuum circuit breaker and its extinction can be explains as follows:
When the contacts
of the Breaker are opened in vacuum (10-7 – 10-5 torr)
and arc is produced between the contacts by ionization of metal vapor of
contacts. However, the arc is quickly extinguished because the metallic vapors,
electrons and ions produced during arc
rapidly condenses on the surfaces of the circuit breaker contacts resulting in
quick recovery of dielectric strength. The reader May note that the salient
feature of vacuum as an arc quenching media. As soon as the arc is produced in
vacuum, it is quickly extinguished due to the fast rate of recovery of dielectric
strength in vacuum.
MCB ( MINIATURE CIRCUIT BREAKERS)
Ø “L” – SERIES : GREEN
KNOB MCB – FOR LIGHTING
Ø “G” – SERIES: BLUE KNOB
MCB - FOR MOTOR
Ø DC – SERIES : BLACK KNOB - FOR DC CIRCUIT
Ø ISOLATOR : RED KNOB -
Features:
1. At the short ckt, it does
not allow to flow fault current fully
2. Contacts get opened within
1 m/sec.
3. Operating time is less
that 5 m/sec.
ELCB
TYPES OF
BREAKERS
LOW VOLTAGE:
1. Miniature circuit breaker
2. Molded case circuit
breaker
3. Residual case circuit
breaker
4. Power breakers
HIGH VOLTAGE:
1. Air blast circuit breaker
2. SF6 – (sulfur) breaker
3. Vacuum circuit breaker
4. Oil circuit breaker
5. Minimum oil circuit
breakers.
NPCC
MAIN INCOMER BREAKER – USED RELAY
NPCC – LV
1. Inverse type Under voltage
relay : Type: VAGM – 2 Nos, Range: 44 to 88 Volts
2. Over Current
Relay(Inverse): Type CDG – 2 Nos., Range: 2.5 to 10 Amps
3. Earth Fault
Relay(Inverse): Type CDG – 2 Nos., 0.5 to 2 Amps.
4. Instantaneous Earth Fault
Relay: Type CAG, Range: 0.5 to 2 Amps
5. Tripping Relay : Type:
VAJ, Range 110 to 125 Volts,
6. Trip Circuit Supervision
Relay: Type – VAX MK11
SIEMENS BREAKERS
BASIC PROTECTIVE FUNCTIONS
v The basic protective
functions of the over current release are ensured without additional auxiliary
voltage. The required power is supplied by internal transformer of the circuit
breaker.
v To evaluate arc current,
the electronic system of the over current release calculates the RMS value.
OVERLOAD
PROTECTION
v The current setting Ir defines the maximum continuous
current. The circuit breaker can carry without tripping. The time lag class to
determines the maximum duration of an over load without tripping
ETU – 45B –
IR (0.4/0.45/0.5/0.55/0.6/0.65/0.7/0.8/1.0) X In.
BASIC
PROTECTIVE FUNCTIONS OF ACB
v Over Load Protection – L Tripping
v Short Time Delay – Short
circuit protection – S Tripping
v Instantaneous short
circuit protection – I Tripping
v Neutral conductor
protection – N Tripping
v Earth fault tripping 1.
Alarm setting.
SHORT TIME DELAY:SHORT CIRCUIT
TRIPPING
– S TRIPPING
v Over current release ETU 25-B-76B tripping due to the short
circuit current Isd can be delayed
by the time tsd.
This provides selectivity for the
short circuit protection in switch gear with several grading levels.
ETU – 25B,
45B – Isd (1.25/1.5/2/2.5/3/4/6/8/10/12) X In.
SETTING FOR tsd
ETU – 45B –
tsd=0.02(M)/0.1/0.2/0.3/0.4 Si off
v The time delay 0.02s is not
a grading time. In this protection, the motor protection function is activated.
v For setting tsd >0.4s the maximum possible
setting Isd is reduced automatically
according to frame size.
Frame size : 1.5 KA, 20 KA, 30KA. with the setting “off”. For the over current
release ETU 45B – 76B is provided to
de-activate the short time delay short circuit protection.
If zone selective inter locking ZSI -> is used however, the setting
for the time delay tsd is
deactivated. If the circuit breaker does not receive any blocking, signal from
a down streak circuit breaker, it will trip after 50 ms regardless of the setting for tsd.
MOTOR
PROTECTION FUNCTIONS
v In the circuit breaker
position tsd = (M) (0.02), a special
protection function for electromotive drive is activated. It prevents the short
time delay short circuit tripping. From being activated during the peak inrush
current of electric motors. At the same time phase failure protection is
activated and time constant for the internally calculated reproductive of the
temperature rise and cooling process is switched over from switch gear
protection to motor protection.
33KV PANEL RELAY
PROTECTION
TYPE OF RELAYS
v TRIV-VECTOR METER ELT
v OVER VOLTAGE RELAY TYPE VIC
Definite time
– ALStom – 50A (z)
v INSTENSTENEUS UNDER
VOLTAGE RELAY
Setting ->
Type VAGM, 44 to 88 Volts
Specified
ratings of an AC circuit breaker:
1. Symmetrical
Breaker capacity: The breaking capacity in symmetrical condition is known as symmetrical
breaking capacity which is generally expressed in terms of MVA and is equal to
the product of rated symmetrical breaking current (kA), rated service voltage
(kV) and a factor depending upon the
number of phases (1 for single phase and √3 for three phase).
2.
Asymmetrical breaking capacity: The breaking capacity in asymmetrical condition is
known as asymmetrical breaking capacity which is also expressed in terms of MVA
and is equal to the product of rated asymmetrical breaking current (kA), rated
service voltage (kV) and a factor depending upon the number of phases(1 for
single phase and √3 for three phase).
3. Making
capacity:
The making capacity is term used in connection with the rating of a switchgear
to denote the capability or a switch, circuit breaker or similar apparatus to
make a circuit by closing under short circuit condition. Making capacity is
approximately equal to 2.55 times of symmetrical breaking capacity.
4. Short
time rating: The short time rating of a circuit breaker is that highest permissible
value of the current which the fully closed circuit breaker can carry for a
specified time of about 1 to 3 seconds without excessive temperature rise and
electro-dynamic effect capable of causing injury.
5. Rated
normal current: The rated normal current of a circuit breaker is the r.m.s. value of
the current which the circuit breaker shall be able to carry at normal
frequency and at the rated voltage continuously under specified conditions.
6. Rated
service voltage: The rated service voltage of a circuit breaker is the r.m.s. value of
the operating voltage at which the circuit breaker shall be able to carry the
normal current continuously at normal frequency.
Rated operating sequence: O(open)-t-CO(close open)-T-CO (t=0.3 or 0.5 sec., T=3minutes)
Circuit
breaker designed to have a short time rating: In the power system sometimes a very
temporary nature of fault persists for a short period of 2 or 3 seconds and
after which the fault is automatically cleared. To maintain continuity of
supply the breaker should not trip in such condition. Therefore, breaker should
be able to carry high current safely for some specified period during running
i.e. the circuit breakers should have a short time rating.
Symmetrical fault: In a three phase power
system when all the three conductors are brought together simultaneously into a
short circuit condition giving rise to equal fault currents with 1200 displacement
symmetrical currents to flow through the lines then this fault is called as
symmetrical fault.
Short
circuit kVA: The product of normal system voltage and short circuit current at the
point of fault expressed in kVA is called as short circuit kVA.
Unsymmetrical
fault In
a three phase power system when single line to ground or line to line or double
line to ground fault occurs giving rise to unequal fault current with unequal
displacement i.e. unsymmetrical currents to flow through the lines then this
fault is called as unsymmetrical fault.
Reactor: A reactor is generally an air cored coil of
large number of turns having high value of constant inductive reactance as
compared to its ohmic resistance in which magnetic saturation at high current
does not reduce the coil reactance.
Making
current & Breaking current:
a) Making current of a circuit
breaker is the total maximum current peak which occurs during the first cycle
immediately after the circuit is closed
on a short circuit.
b) The Breaking current of a circuit
breaker is the total maximum current peak that can be safely broken by the
circuit breaker at the time of separation of the contacts at its rated voltage.
Is a 50 Hz
circuit breaker suitable for 60 Hz supply? Can 12 kV C.B. be used for 6/6 kV
application?
a. It is possible only when the
breaker is type tested at 60 Hz frequency, otherwise not.
b. A 12 kV circuit breaker can be
used for any voltage up to its rated voltage under the condition that the
breaking current is within its breaking capacity.
The difference between low voltage circuit-breaker
and high voltage circuit-breaker.
Low voltage circuit breakers are used
in indoor control gears for controlling power consuming devices of circuits
below rated voltage 1000 volts AC or
1200 volts DC whereas high voltage circuit breakers are used in both indoor and
outdoor control-gears in high voltage supply system. Low voltage circuit
breakers operate frequently than high voltage circuit breaker.
Low voltage circuit breakers are more
compact than high voltage circuit breakers because of less phase to phase and
phase to ground clearances. Testing requirements of high voltage circuit
breaker are quite different from those of low voltage circuit breakers.
CLASSIFICATION
OF HIGH VOLTAGE CIRCUIT BREAKERS
a) Oil circuit breaker: i)
Bulk oil circuit breaker, ii) Minimum oil circuit breaker
b) Oil-less circuit breaker:
i) Air blast circuit breaker, ii) SF6 circuit breaker, iii)
Vacuum ckt. Breaker, iv) Air break ckt breaker
A) For low & medium
voltage installation the following types of circuit breakers are used:
a) Air break with magnetic blow out
circuit breaker
b) Bulk oil circuit breaker
B) For high voltage
installation the following types of circuit breakers are used:
a) Bulk oil circuit breaker, b)
Minimum oil circuit breaker,
c) Air break with magnetic blow out
circuit breaker, d) Air blast circuit breaker,
e), Sulphur hexafluoride circuit
breaker, f) Vacuum circuit breaker
C) For extra high voltage
installation the following types of circuit breakers are used:
66kV: Minimum oil, SF6 and
Vacuum circuit breakers
132kV &
220 kV:
SF6 and Vacuum circuit breakers.
AIR BREAK
CIRCUIT BREAKER: The circuit breakers in which the air at atmospheric pressure is used as
an arc quenching medium, is called air break circuit breaker. These are
generally indoor type and installed on vertical panels or indoor draw out type
switchgears. These are used in DC circuits and AC circuits up to 12 kV. AC air
break circuit breakers are widely used in indoor type medium & low voltage
switchgears.
BULK OIL
CIRCUIT BREAKERS: The bulk oil circuit breakers are large volume oil circuit
breakers consisting of contacts and arc control systems arranged inside the
earthed metal tank filled with a considerable quantity of insulating oil and
operating mechanism mounted outside the tank. These are widely used for the both,
indoor & outdoor transformer substation, arc furnace, railway stations,
large motors of AC power system.
MINIMUM OIL
CIRCUIT BREAKERS: The minimum oil circuit breakers are small volume oil
circuit breakers in which the contacts are separated in tube shaped tank of
insulating material like porcelain filled with a relatively small quantity of
oil and held between the metal end terminal caps for the external circuits. It
has having less volume of oil because solid insulation is provided in a minimum
oil circuit breaker for insulating the contacts from earth. These are used in
high and extra high voltage outdoor substation. Closing and opening operation
can be done by manual operation and by remote control operation either by motor
drive or pneumatic drive. c
AIR BLAST
CIRCUIT BREAKER: The air blast circuit breaker is nothing but a compressed air circuit
breaker in which high pressure air is forced on the arc through a nozzle at the
instant of contact separation to blow away the ionized medium between the
contacts and thereby extinguishing the arc by the blast of compressed air
supplied from an air reservoir. Air Blast circuit breaker is operated at the
pressure of 20 to 30 kg/cm2. These breakers are generally used in
outdoor substations of high voltage system specially for railways and inter
connected lines where frequent switching operation is the principal
requirements.
Merits of these breakers:
i) Air blast circuit breaker operates
at high speed maintaining better stability.
ii) Arcing time is very short.
iii) The life of the breaker is
increased due to lesser damage to the contact points.
iv) This can be given rapid auto re-closure
feature.
v) The possibility of fire hazards is
very less.
vi) Due to absence of oil less
maintenance is required.
vii) It has very high breaking
capacity and service voltage in extra high range can be obtained by connecting
more number of units in series.
viii) Frequent operation creates no
problems.
Demerits:
i) High capacity compressor plant is
required.
ii) The complex design of arc
quenching chamber and operating mechanism creates problems of switch over
voltages.
iii) Special attention is required
for proper operation and maintenance of compressors and its accessories.
iv) Resistance switching is required
for reducing switch over voltages and current chopping.
SF6
CIRCUIT BREAKER:
The circuit breakers in which an
inert electronegative gas sulphur hexafluoride(SF6) is used as
dielectric and arc quenching medium, is known as SF6 circuit
breaker. They are similar is design to the air blast circuit breakers with the
difference that the blast of air is replaced by that of sulphur hexafluoride
gas. These breakers are used mainly in EHV outdoor substation. SF6
gas used in circuit breaker is transported in liquid form at higher pressure
and lower temperature in a sealed cylinder to site. SF6 gas becomes
liquid at lower temperature and higher pressure. At ambient temperature the SF6
can not be used above 8 kg/cm2.
Merits:
i) The dielectric strength is higher
than air and oil.
ii) The arc extinction is very rapid.
iii) The contact corrosion is very
little due to inertness of SF6 gas. Hence contacts do not suffer oxidation.
iv) The maintenance & replacement
of contacts required are minimum.
v) It has ample over load margin.
vi)Since SF6 is non inflammable and chemically
stable the decomposition products become non explosive thus eliminating the
risk of fire or explosion.
vii) It has noiseless operation.
viii) It has no over voltage problem
ix) The contamination by moisture,
dust, sand etc is avoided due to its sealed construction.
x) The requirement of SF6 gas is very
small as the same gas is re-circulated in the circuit.
xi) It has ability to interrupt low
and high fault current, magnetizing and capacitive current.
xii) It is simple, non toxic, less
costly, maintenance free and compact with high interrupting capacity.
Demerits:
i) It has low breaking capacity,
ii) Imperfect joint may cause a
leakage at gas.
iii) The presence of moisture in the
gas may cause severe failure.
iv) Arced gas is very poisonous to
human breathing.
v) It needs special materials for
sealing to avoid gas leakage and moisture contamination.
Classification
of circuit breaker contact according to their arrangement:
i) Stationary contacts which
constitute a permanent electrical connection and do not move in relation to
each other during operation.
ii) Switching contacts which make,
break or change the connections of circuits carrying an electric current.
iii) Sliding contacts, where one of
the contact members slides over the other one without interrupting their
electrical contact.
Classification
of circuit breaker contact according to their shape of the contact faces:
i) Point contacts in which the
current carrying members come into contact only at a single point.
ii) Line contacts in which the
current carrying members nominally come into the contact along a line.
iii) Plane contacts in which the
current carrying members nominally touch each other over a plane of some
configuration.
Reasons of
formation of arcs in a circuit breaker.
When the contacts of the circuit
breaker are separated during operation high local temperatures are created on
the contact surface, which constitute electrons emission from contact surface
by thermal emission. The gas or air molecules between contact space become
extremely hot and get ionized by thermal ionization and ionization by
collision. The normal insulation property of the medium is destroyed and the
hot molecules of the medium become conductors of electricity. Thereby due to
high speed electron movement arc discharge takes place between the contacts.
Advantages
of having oil in the circuit breaker:
i) The transformer oil used in a
circuit breaker is a very good insulator and thus reduces the clearance between
the live parts and earth.
ii) It absorbs the heat energy of the
arc by decomposition of the oil.
iii) The gases so formed by the
decomposition of oil(chiefly hydrogen) have good cooling properties.
iv) The oil has a high dielectric
strength.
v) The cold oil has the ability to
flow into the arc space after the arc current goes to zero.
Disadvantages
of having oil in the circuit breaker:
i) Oil is inflammable.
ii) The oil absorbs moisture rapidly.
The dielectric strength is reduced by the absorption of moisture and also by
carbonization occurred during arcing.
iii) In case of frequent operation of
the breaker oil is most unsuitable.
iv) For leakage, losses, replacement
and purification of oil it needs regular maintenance.
No comments:
Post a Comment