DIESEL GENERATOR
Connected Devices
1. Cooling Tower Pump : Raw
water tank Checking
2. Cooling Tower Fan
3. Air Compressor : 0 to 10
Kg/cm2.
4. Lub oil Priming pump :
5. Fuel transfer pump
RELAYS USED
FOR D.G. PANEL
1. Restricted Earth Fault :
Instantaneous Earth Fault – Type : CAG, Range : 1.5 to 4 Amps
2. Negative phase sequence
Relay: Negative sequence relay, Type: CTNM, Range:
3. Earth fault relay: E/F
relay(Inverse type) Type: CDG – Range: 0.5 to 2 Amps.
4. Over Current Relay:
(Inverse) Type: CDG- 3 NOS, Range: 2.5 to 10 Amps.
DG INCOMER PANEL (EPCC)
1.
Instantaneous Earth fault Relay: Type CAG, Range: 0.5 to 2
Amps,
setting: 1A (320 x 1=320)A
2.
Trip Circuit Supervision Relay: Type – VAX MK11, 110 – 125
Volts
3.
Definite Time Relay: Type VTT – 110V, setting: 0.5 sec delay
on pick up
4.
Over current Relay(Inverse)Type CDG, Range :2.5 to 10 A,
setting: 3.75A (320 x 3.75 = 1200)A
5.
Earth fault relay(Inverse) Type CDG, Range: 0.5 to 2 A,
Setting: 0.75A(320 x 0.75=240)A
6.
Over current relay(Inverse) Type DCG, Range: 2.5 to 10Amps
7.
Tripping relay: Type VAG
8.
Instantaneous over voltage relay: VAGM-ALSTOM. Normal
voltage: 110 VAC, setting:132V, range 121 to 154V
9.
Instantaneous under voltage relay: VAGM:ALSTOM. Normal
Voltage:110VAC,
Range 44 to 88 V, setting: 88 volts
DG INCOMER PANEL (Control Panel)
1. Instantaneous Earth fault Relay:
Type CAG, Range: 1 to 4 Amps, Setting: 1(269.4 x 1)
3. Over current Relay(Inverse)Type
CDG, Range :2.5 to 10Amps, Setting: 3.75 A, Full load
current: 1347 Amps. ( 269.4 x 3.75 = 1010 Amps)
4. Earth fault relay(Inverse) Type CDG, Range:
0.5 to 2 Amps, Setting: 0.5 (269.4 x 0.5 = 134.7 Amps.
DG
panel meters: Ammeter, Voltmeter, PF meter, Energy meter, Frequency meter,
DG- KVAR meter, KW meter, Excitation voltmeter & ammeter, enunciator 1 to
5, Double voltmeter, synchroscope meter, Double frequency meter.
DG GCU: Generator controller unit.
1. Digital governing, voltage
regulation, synchronizing, load sharing, paralleling with main bus(Grid).
2. Protection of
Alternator against over current protection.
3. Analogue and digital AC
output metering.
4. Battery monitoring
system to check for weak condition.
5. Digital alarm and
status massage display.
6. Generator set – Engine
monitoring system
7. Smart stealing control
feature
8. Network capability.
9. Ip-54 protection.
10. PC Compatibility.
* Battery supply – 24.5
VDC 200 Ah.
Ø Min. time of operation
without cooling water availability during start up
Ø Max time require to start
the diesel from preheated (cold) condition to bring up to rated speed and load
up to its capacity without exceeding voltage and frequency limit
Ø Ip-23: Ingress protection.
Where
2 stands for-12 mm gap, eg: figure
3 stands for direct spray of water up to 600
C from vertical.
Ø S – Motor stop condition
tested
Ø M – Motor running
condition tested.
PROTECTION FOR DG SET
SN
|
Alternator side
|
Setting
|
|
SN
|
Panel side
|
Setting
|
1
|
High Lub oil temperature
|
1050C
|
1
|
Over Voltage
|
480 V
|
|
2
|
High cooling water temperature
|
70-950c
|
2
|
Over Current
|
1010A
|
|
3
|
Low lub oil pressure
|
2-7 kg/cm2
|
3
|
Restricted Earth fault
|
269.4A
|
|
4
|
Engine over speed
|
1650 rpm
|
4
|
Under Voltage
|
88%:345.8A
|
|
5
|
Generator Bearing temperature
|
720C
|
5
|
Frequency
adjustment
|
+
5%
|
|
6
|
Engine Bearing temperature
|
700C
|
6
|
Raw water inlet temp.
|
33.30C
|
|
7
|
Generator winding temperature
|
93- 960C
|
|
7
|
Raw water temp. raise
|
43.30C
|
8
|
Air pressure
|
7– 10.5 kg/cm2
|
|
8
|
Designed Amb.temp.
|
450C
|
9.
|
|
3 minutes.
|
|
|
|
|
10
|
|
15 Sec.
|
|
|
|
|
Back-up protection for alternator: The I.D.M.T.L relay is used for
back up over current and earth fault protection of alternators.
Protection against unbalanced load: Alternators area
protected against unbalanced load by negative sequence relay along with a
filter unit.;
Negative sequence filter: The negative sequence filter being
a sensor element segregates the negative sequence component and allows the same
to pass through the relay coil.
Reverse power protection for parallel operation of alternator: During parallel
operation if the input to the prime mover of an alternator is stopped or
reduced then its E.M.F. will obviously become less than the bus bar voltage and
then it will act as a synchronous motor drawing power from the bus bar instead
of delivering power to the bus bar. So to avoid this abnormal situation reverse
power protection is absolutely necessary for alternators running in parallel.
Protection from stator winding fault: As the stator winding
fault may lead to burning of stator coils automatic protection is absolutely
necessary to clear such fault in the quickest possible time in order to
minimize the extend of damage to the expensive machinery.
For protection of
alternators against stator winding faults differential protection (also known
as Merz-price system) is commonly used due to its greater sensitivity and
reliability.
Protection against abnormal vibration of alternator: Vibration detector is
used for this purpose. When an abnormal vibration the radial deflection exceeds
a preselected value it operates to trip the breaker of the machine.
HOW DG GETS ON
1. In field exciter residual
magnetism is available. When normal supply fails, command gets DG and
24VDC Starter gets on, it rotates DG
wheel & starter gets off. Due to this in the armature of exciter, EMF is
produced.
2. Produced is 3 ph AC which
converts in DC due to rotating diode assembly on the shaft and feed to rotating
field.
3. Main Rotating Field: This
rotating field cuts stationary conductor of stator then EMF in is borne in
stator coil.
4. Stator Of Generator: Here
exactly armature is given. But for brushless generator, it is constructed over
stator, This is why no need of brush. Due to brushless, efficiency will be
more.
When
generator starts, it is on no-load, its field voltage is 32V & field
current is 1.2 A & line voltage is 425V. When generator is loaded, its
voltage should be decrease. But it do not take place because of Automatic
Voltage regulator. When load increases, voltage getting to AVR, then exciter field
winding voltage increases. There is no difference in voltage during loading, un
loading. Speed is maintained by governor which increases diesel flow when speed
decreases.
AVR(Automatic
Voltage Regulator) : The electronic controller is the heart of system which
maintains stable output DC voltage of the charger in spite of supply voltage
fluctuations and load variations.
Starting
procedure of DG set in detail
The main stator is provided power for
excitation of the exciter field via the SX 440 or SX 421 AVR which is the
controlling device governing the level of excitation provided to the exciter
field. The AVR responds to voltage sensing signal derived from the main stator
winding by controlling the low power of the exciter field control of the high
power requirement of the main field is achieved through the rectifier our put
of the exciter.
The SX 421 AVR in addition to the SX440 features
has three phase rms sensing and also provides for over voltage protection when
used in conjunction with an external circuit breaker.
Permanent magnet Generator PMG
excited AVR controlled generator.
The permanent magnet generator provides power
for excitation of the exciter field via the AVR (MX341 or MX321) which is the
controlling device governing the level of excitation provided to the exciter
field. The AVR responds to a voltage sensing signal derived via an isolating
transformer in the case of MX321 AVR from the main stator winding. By
controlling a low power of the exciter field. Main field is achieved through
the rectified out put of the exciter armature.
The PMG system provides a constant
source of excitation power irrespective of main stator loading and provides
high motor starting capability as well as immunity to wave form distortion on
the main stator out put created by non linear load 2.9 thyristor controlled DC
motor.
The MX341 AVR senses average voltage
on two phases ensuring close regulation in addition it defects engine speed and
provides an adjustable voltage fall off with speed below a pre-selected speed
(Hz) setting preventing over-excitation at low engine speed and softening the
effect of load switching to relieve the burden on the engine. It also provides
over-excitation delay, to de-excite the generator in the event of excessive
exciter field voltage.
The MX321 provides the protection and
engine relief features of the MX341 and additionally incorporates 3 phase rms
sensing and over voltage protection.
The detailed function of all the AVR
circuits is covered in the load testing section.
The SX440 and MX321 AVRs incorporate
circuits which, when used in conjunction with accessories can provide for
parallel operation either with drop or a static control AVR/PF control and in
the case of the MX321 AVR, short circuit current limiting.
Function and adjustment of the
accessories which can be fitted inside the generator terminal box are covered
in the accessories section of the box.
No comments:
Post a Comment