CLASSIFICATION OF POWER SUPPLY
1. Class IV - Normal PS
415V 3 ph – 2500 KVA
2. Class III – Diesel Generator set, 415V, 3 ph, 1010KVA – Self exited.
3. Class II - UPS – 230V, 50 KVA
4. Class I - Battery pS – 110VDC,
550AH & 425 AH-ROP S/stn, 300 AH – PREFRE S/stn.
Class I – Control ckt VCB, Exit lighting
Class II – Control room all area monitors, SCADA, trx scanners.
Class III – E2 fans & lighting
Class IV – All are normal supply.
FRLS: Flame Retardant Low Smoke Cable: Used in
High block
TRANSFORMER
A
Transformer is a static piece of apparatus which transforms electrical energy
from one circuit to another circuit without changing the frequency either
stepping up or stepping down the voltage.
Principle: The principle of operation of a transformer is based
upon the theory of mutual induction between two electrical circuits linked by a
common magnetic flux.
The
rating of a transformer is the maximum power which can be drawn from it without
the temperature rise in the winding exceeding the safe limits for she
particular class of insulation employed.
The
rated capacity of a transformer is expressed in kVA not in kW. Generally the
rating of a transformer is determined by its temperature rise. The temperature
rise is caused by the losses in the machine. Copper loss depends upon the value
of the load current and iron loss on voltage. Therefore, total loss of a
transformer depends on volt ampere (VA) and is independent of load power
factor. A certain amount of current will produce the same I2R loss
at any value of power factor. This loss limits the output of the machine. The
output in kilowatts is proportional to the power factor. For a given kW load,
if the power factor decreases, the load current increases proportionately
causing more losses and temperature rise in the machine. For the above reason
transformers are generally rated in kVA not in kW.
Power factor of transformer: The power factor of a transformer is very
low and lagging on no load. But the power factor on load is nearly equal to the
power factor of the load which it is carrying.
Normal phase difference between the voltage: The no load current in a transformer
normally lags behind the voltage by about 750.
Material used for the cores of a
transformer: Laminations
of specially alloyed silicon steel (silicon content 4 to5%) are used due to its
high electrical resistance, high permeability, non-ageing characteristics and
minimum iron loss.
The
iron core is used in a transformer to provide continuous easy magnetic path of
low reluctance. The magnetic leakage is reduced to a minimum by sectionalizing
& interleaving the primary and secondary windings. Iron cores are made
laminated to reduce the eddy current loss. The laminations are insulated from
each other by insulating varnish or thin paper to break the path of eddy
currents thus to reduce the eddy current loss.
Grain oriented laminations: The grain oriented laminations are such
cold rolled laminations specially annealed to orient crystals i.e. the grains
in a uniform direction in the direction of rolling which produce very high
permeability and low hysteresis loss. These laminations are punched and
assembled in such a way that the grains of different lamina lie in the same
direction as the magnetic field and not across it. A special care is taken
during tightening of iron cores to make it free from vibration and humming
sound. The max. flux density in transformer core is 1.6 to 1.8 Weber per metre2.
The
phase relationship between the primary and secondary voltages of a transformer
is 1800 out of phase.
CRGO Steel: It means Cold Rolled Grain Oriented silicon steel
manufactured by coiled rolling to give easy direction to all its crystals.
To
magnetize itself less magnetizing force is required. Accordingly requirement of
magnetizing current is reduced. Therefore it is widely used for making
transformer cores.
Special
attention is given to assemble a transformer core in such a manner that the
crystal direction is parallel to the flux path, otherwise the core will offer
high reluctance thereby lowering magnetic permeability.
Permolloy: It consists of iron and nickel alloyed with copper
and molybdenum having initial permeability of 2500 and maximum permeability up
to 100000.
It
is heat treated up to 11000C and curie temperature varies between
420-5800C depending on the composition. It is used in the
manufacture of sensitive relays.
Mumetal: It consists of iron and nickel alloyed with copper
and chromium having initial permeability of 20000 and maximum permeability up
to 110000. It is heat treated up to 11000C and curie temperature is
4300C. It is used for manufacturing instrument transformers and
miniature transformers.
Turn ratio of a transformer: The ration of number of turns in the primary
to the number of turns in the secondary winding is called the turn ratio or the
ratio of transformation of the transformer which is indicated by a constant
’K’. Then N1/N2 = E1/E2= K
Voltage ratio of a transformer: Voltage ratio is the ratio of the voltage
between the line terminals of one winding to that between the line terminals of
another winding at no load.
Counter e.m.f. in primary winding of a
transformer: When an alternating
voltage is applied to the primary winding it causes a flow of alternating
current which creates alternating flux. This alternating flux is linked with
both the primary and secondary windings and hence induces self induced emf on
the primary winding and a mutually induced emf on the secondary winding. Since
the primary self induced emf is in the opposite direction to the applied
voltage, it is known as counter emf or back emf of the transformer.
e.m.f. equation: Erms = 4.44φm.f.T. volts
The different types of coils used in the
transformer winding and their uses:
(a) Spiral type coil: Spiral type coil: This consists of layers
wound in continuous length from top of bottom of the coils, the conductors of
which consist of a number of square or rectangular strips in parallel. These
coils are only used for low voltage winding carrying a heavy current of more
than 100 amps.
(b) Cross over type coil: This type of coil consists of a number of
layers having a number of turns per layer, the conductor being round wire or a
strip insulated with a paper covering. Cross over coils are wound on formers.
These coils are used for high voltage windings of distribution transformers and
current up to about 20Amps.
(c) Helical type coil: This type of coil is wound in the form of
a helix and consists of a number of rectangular strips wound in parallel
radically so that each separate turn occupies the total radial depth of the
winding. These coils area used for lower voltage winding of larger transformer
at voltages 11kV to 33 kV. Multilayer helix can be used for higher voltage
winding up to 500 kV.
(d) Continuous disc type coil: This coil consists of a number of discs
wound continuously from a single wire or a number of strips in parallel. In
each disc a number of turns are wound radially over one another and the
conductor passes from disc to disc uninterruptedly. These coils are used for
both higher voltage winding from 33kV to 500kV and lower voltage winding from
11kV to 66kV above the rating of 1MVA.
Ideal transformer: The transformer having an overall
efficiency of 100% is called ideal transformer. For an ideal transformer,
Output = Input.
Losses in Transformer: (i) Core losses or iron losses or
constant losses consisting of hysteresis and eddy current losses in the core
and (ii) Copper losses in the primary and secondary windings.
Since
hysteresis is a kind of loss and affect the efficiency of transformer, so it is
always objectionable.. The hysteresis loss depends on (i) the quality and
constituents of iron core, (ii) the frequency and (iii) the flux density.
Hysteresis loss is more than eddy current loss in a transformer. The main
purpose of using silicon steel in the laminations of transformer core is to
reduce the hysteresis loss. The core flux is always constant on every load i.e
no load to full load. No load current produces core flux and supplies iron
losses and copper loss on no load.
Load current of a transformer: When a load is connected to the secondary
side of a transformer the transformer is said to be on load and the current
circulating through the secondary winding via load is called the load
current.
Primary current on load: When the load current(I2) flows
through the secondary winding a counterbalancing current (I1) is
induced on the primary winding varying inversely to their respective turns. The
total primary current on load (I1) is equal to the vector sum of the
primary counter balancing, current (I1) and the no load current (I0)
which will be approximately equal to (I1) as I0 is
practically very small.
If
the load current increases with the increase in load current corresponding
transformer circuit modeling the behavior of a real transformer which represents
the primary circuit as well as secondary circuit in one circuit with suitable
parameters for easy calculation with the addition of a shunt circuit to account for no load current.
Approximate equivalent circuit of the
transformer: The
approximate equivalent circuit to the transformer means a slight modification
of the equivalent circuit by transferring the shunt circuit to the primary
terminal with close approximation effecting very little change in the result.
Core losses can be determined by short circuit test. In this test
the low voltage secondary of the transformer is short circuited through an ammeter.
At first a small voltage is applied to the high voltage primary side and the
voltage is gradually raised in steps till full load current flows through the
secondary. Since the test voltage is very small in comparison to the normal
voltage the core losses are negligible and the wattmeter connected on the
primary side records the full load copper losses.
Since
no load current is very small and no load copper loss is very small in
comparison with the iron losses so the copper losses are neglected in open
circuit test.
Copper
losses can be determined by short circuit test. In this test the low voltage
secondary of the transformer is short circuited through an ammeter. At first a
small voltage is applied to the high voltage primary side and the voltage is
gradually raised in steps till full load current flows through the secondary.
Since the test voltage is very small in comparison to the normal voltage the
core losses are negligible and the wattmeter connected on the primary side
records the full load copper losses.
Copper
loss varies inversely with the power factor.
Impedance voltage: The impedance voltage of a transformer is
the voltage required to circulate rated current through a winding of the
transformer when another winding is short circuited with the respective
windings connected as for rated voltage operation. It is usually expressed in
percent of the rated voltage of the winding in which the voltage is measured.
Efficiency of the transformer: The ordinary or commercial efficiency of
a transformer is defined as the ratio of the output in watts to the input in
watts. Since the efficiency is based on the power output in watts and not on
volt-amperes, the power factor plays an important role in determining the
efficiency.
The
condition for the maximum efficiency of a transformer is (Iron losses = Copper
losses).
The
efficiency of a power transformer depends on the power factor of the load and
the percentage of the load.
Since
the transformer is a static apparatus without any rotating parts there is no
frictional loss. The only losses are iron losses and copper losses in the
primary & secondary. Therefore, the efficiency of a transformer becomes so
high about 95% to 98%.
All day efficiency of a transformer: It is defined as the ratio of energy
output in 24 hours to energy input in 24 hours.
Regulation of a transformer: The regulation of a transformer is the
difference between the no load and full load secondary voltages expressed in
terms of the no load voltage with constant primary voltage.
No load voltage – Full load voltage
Percentage
regulation = ----------------------------------------------- x 100%
No load voltage
E – V IR cosφ + IX sinφ
= --------------- x 100%
= ------------------------- x 100%
E E
Where R =
Equivalent resistance in terms of secondary.
X = Equivalent reactance in terms of secondary.
E = Induced e.m.f. of secondary
φ = Phase difference between
voltage and current
I
= Full load current.
Effect of power factor and load on the regulation of a
transformer: For lagging
power factor of load current the regulation will be positive i.e. the secondary
voltage will be reduced with the increase in the load current.
For leading power factor of load current the
regulation will be negative i.e.
the secondary voltage will be negative i.e. the secondary voltage will be
increased with the increase in the load current.
Percentage impedance of the transformer: The impedance voltage is the vector sum
of resistance voltage and reactance voltage. The percentage impedance is the
value of impedance voltage expressed as a percentage of rated voltage. Thus %
impedance = % Impedance voltage.
I1Z’1
= ---------
x 100
V1
Where I1
= Rated primary current
Z1 = Impedance with reference to primary.
V1 = Rated primary voltage.
Tap changing: Tap changing is a process of changing the ratio of
transformation by increasing or decreasing the number of active turns in one
winding with respect to another winding for maintaining a constant voltage on a
power system.
There are two
types of tap changing arrangements:
1. OFF load tap changing: Off load tap changing gears can be operated only
when all the loads on the transformer are cut off. The voltage ratio of a
transformer can be varied by about + 10% by means of OFF load tap
changing gears.
2. ON load tap changing gears can be operated even when the load is on. The
voltage ratio of a transformer can be varied by about + 16% by means of
ON load tap changing gears. The tapings are
generally provided on the high voltage side since the current loading is
comparatively small on the high voltage side.
Bushing: Bushing is a type of porcelain or ebonite post insulator put on the
top or side of the transformer tank though which connection are made to the
external circuits.
Types of bushing:
(a) Porcelain insulator bushing used up to
33 kV
(b) Oil filled bushings consisting of a
hollow porcelain cylinder of special shape with a hollow tube shaped conductor
through its centre used for the voltage above 33 kV
(c) Capacitor type bushing made of thick
layers of bakelized paper alternating with thin graded layers of tin foil being
covered by a porcelain rain shed and filled up with bitumen in the annular
space between the rain shed and the bushing used in outdoor substation for the
voltage above 33kV.
Auto transformer: An auto transformer is a single winding transformer
provided with a number of taps in which the single winding performs the
functions of both the primary and the secondary.
Basic difference between distribution transformer and
auto transformer: The
basic difference is that the distribution transformer has two separate windings
and there is no electrical connection between the primary and the secondary
while an auto transformer has a single winding in which the primary and
secondary are electrically connected.
Advantage of Auto transformer: (i) Being single winding transformer it
requires less copper and becomes lighter in weight. (ii) The cost is less than
a two winding transformer, (iii) As it is provided with large number of taps
desired voltages can be obtained by adjusting suitable taps.
The Auto transformers is used in high voltage line a fault in the primary
may affect the secondary side in which case the secondary load equipments may
be damaged. So it is not used for high voltages.
Auto transformers
are used in case of low voltage and low transformation ration e.g. starting
equipments of there phase induction motor, control equipments of single phase
and three phase electr5ic locomotives, voltage control of power and lighting
circuits, regulating transformers, boosters to raise the voltages in a.c.
circuits etc.
Variable transformer: A variable transformer (named as Variac, Dimmer-stat
etc) is nothing but an auto transformer having continuously variable tap so
that any output voltage desired could be obtained.
Difference forms of connections used in primary and
secondary windings in three phase transformers:
Star/Star connection is best suited for small high voltage
transformers with balanced load.
Star/Delta connection is applied to the transformers at sending
end of the transmission line where the voltage is to be stepped up.
Delta/Delta connection may be used in large low voltage
transformers where the insulation problem is not so urgent.
Delta/Star connection is generally applied in step-down
distribution transformers to provide a 3-phase, 4 wire supply for three phase
loads as well as single phase loads which may be balanced or unbalance.
Symbolic vector groups for identification of 3-phase
transformer:
(i) Group -1
(Yyo, Dd0, Dzo, Zd0)
(ii) Group-2
(Yy6, Dd6, Dz6, Zd6)
(iii)Group-3
(Dy1, Yd1, Yz1, Zy1)
(iv) Group -4
(Dy11, Yd11, Yz11, Zy11)
Transformer vector group Dy11 and impedance voltage 5%: A transformer with vector group symbol
(Dy11) means a transformer having primary winding delta connected and secondary
winding star connected and belonging to group-4 with + 300 or -3300
phase displacement between primary and secondary winding as referred to the
standard counterclockwise vector rotation.
Impedance voltage
5% means when 5% of normal voltage is applied across one winding it produces
normal full load current to flow through the secondary winding when its
terminals are short circuited.
Parallel operation: To connect two or more transformers in parallel is
called parallel operation of transformers.
The necessity: (i) To share the increasing demand of the load, (ii)
to continue the supply in case of any fault and periodical maintenance, (iii)
To get maximum operational efficiency.
Condition for parallel operation:
(i) The voltage transformation must be same
(ii) The polarity must be same
(iii) The percentage impedance should be same
(iv) The phase
sequence must be same
(v) The vector diagram and the phase displacement
must be same.
If the voltage
ratios of the transformers running in parallel are not identical, the secondary
voltage will be different for which a circulating current will flow through the
two secondary’s if the transformers area connected in parallel. The circulating
current will act as extra load without any useful work being done and cause
heating of transformers even on no load.
It is not necessary that the ratings of two
transformers to be the same for parallel operation but they should share the
load in proportion to their ratings.
Incorrect
polarity results a dead short circuit and due to unequal percentage impedance
the load sharing of two transformers will not be in proportion to their kVA
ratings.
Effect of percentage impedance on load sharing: Since the percentage impedance determines
the voltage drop between no load to full load, with equal percentage impedances
the transformers running in parallel will share the load in proportion to their
capacities. The transformer with a lower percentage impedance will have a
lesser voltage drop and therefore it will take greater share of the load. On the
contrary the transformer with a higher percentage impedance will have a higher
voltage drop and it will not take its due share of the load.
In parallel
operations of two transformers, both will share equally load if their
impedances are equal. If the ratings of
the two transformers are equal but percentage impedances are different the
loads will be shared inversely as the impedances of the transformers expresssed
in percent of normal voltage. In case of
different percentage impedances for different ratings of transformers the
percentage impedances have to be converted to the same basic kVA. Then the
loads will be shared inversely as the converted impedance of the transformers.
In parallel
operation of transformers of different capacities. The rated output of the
smallest transformer in the group should not be less the 33x 1/3 percent of the
rated output of the largest transformer in the group.
Protection requires to transformer: A
transformer requires protection for the following hazards:
(i) Overloading and short circuit fault.
(ii) Internal fault: (a) Loose contact,
(b)
Short circuit between adjacent turns &
(c)
Earth fault in the winding or leads.
(iii) External hazards:
(a)
Lightning surges &
(b) System overvoltage.
Protective equipments required for a large transformer: (i) Over current relay, (ii) Differential
relay, (iii) Earth leakage relay & (iv) lightning arrestor.
Instrument transformer: Ana instrument transformer is a transformer designed
to represent the condition of current or voltage and of phase position in the
primary circuit with acceptable accuracy in the secondary circuit. It changes
the voltage or current in a power circuit to values which render them
convenient for measurement.
The instrument
transformers differ from the power transformers mainly by their volt ampere
rating. The instrument transformers have very low rating of only a few tens of
VA e.g. 10VA, 50 VA, 100 VA etc. Whereas the power transformers have high kVA
rating e.g. 25kVA, 200kVA, 500kVA, 1000kVA even up to 1000 MVA.
Two types of
instruments transformers: 1. Current transformer, 2. Potential transformers.
Current transformer: (i) Air-cooled current transformers and (ii) Oil
immersed current transformers.
Types of current
transformers according to the magnetic circuit: (i) Ring type, (ii) Core type,
(iii) Shell type.
Error in CT’s: There are two types of errors, e.g. ratio error and
phase difference error. The ratio error is the amount by which the secondary
current differs from exact proportionality to the primary current and is
expressed as a percentage of the rated secondary current.
The phase
difference error is the angle by which the secondary current differs in phase
from the primary current and is expressed in minutes of arc.
Categories of current transformers: There are two categories of CTs, e.g.
(i) Measuring
current transformers are used with ammeters, watt meters, kVA meters, kWh
meters, power factor meters etc.
(ii) Protective
current transformers are used with over current relays, earth fault relays,
differential protection, impedance protection etc. Current
transformer is used in a Tong tester.
Only one turn of very thick conductor is used in the
primary of a current transformer: In the primary of a current transformer only one turn of very thick
conductor having negligible resistance is used not only for reducing the
induced voltage but also for reducing the voltage drop to nearly zero. As large
current flows through the primary and small current as per current ratio flows
through the secondary, if one turn is selected for primary the secondary turns
will be smaller.
Material used for the core of CT : In order to reduce the ampere turns
required the core of a CT must have high permeability, small iron loss, a low
flux density and low phase difference error. Two suitable materials are (i)
Silicon steel having maximum permeability of 4500 at flux densities in the neighborhood
of 5000 lines/cm2 with phase difference error of 1.5 to 20,
(ii) Mumetal, a nickel iron alloy containing a small amount of copper having
maximum permeability of about 80000 at flux densities of about 3500 lines/cm2
with phase difference error of below 0.50.
As the
nickel-iron alloy reduces the magnetizing current and core loss to about 10% of
that of the corresponding silicon steel values, Mumetal is best suited for the
core of CT where a high degree of accuracy is desired.
Effect of saturation on the performance of CT: On reaching saturation the transformer
ratio is affected resulting in an increase of exciting current due to reduction
in magnetizing inductance and introducing a phase error in the CT deviating
primary and secondary currents from their desired phase opposition i.e. 1800
.
The increase in
exciting current causes the reduced secondary output and hence reduced speed of
over current relays. The saturation of CT disturbs the balance in differential
relays thus affecting the stability of protection.
Therefore the
effect of saturation makes the operation of the CT unsatisfactory.
Basic difference between current transformers and
potential transformers:
(i) A CT is connected in series with the line whereas a PT is connected across
the supply lines. (ii) In a CT the number of turns is inversely proportional to
the current but in a PT the number of turns is directly proportional to the
voltage. (iii) In a CT the primary has one or more turns of heavy conductor and
the secondary has large number of turns of thin wires whereas in a PT the
primary has a large number of turns of thin wires and the secondary has a few
number of turns of comparatively thick wires.
Types of potential transformer and application:
There are two
types of potential transformers:
(i)
Electromagnetic type potential transformer, in which primary and secondary
windings are used on magnetic core like usual transformers.
(ii) Capacitor
type potential transformer, in which a series capacitor group is used with an
auxiliary voltage transformer. The primary voltage is applied to the series
capacitor group and the voltage across one of the capacitor is taken to the
primary of the auxiliary voltage transformer. Then the secondary of the
auxiliary voltage transformer is finally taken to the metering and/or control
panel.
Potential
transformers are used with voltmeter, kWh meter, power factor meter, frequency
meter, protective relays for the purpose o measurement and protection.
Electromagnetic type potential transformers are used up to 66kV lines while
capacitor type potential transformers are used for the voltages 66kV and above.
Effect of open circuiting the secondary of a CT: If the secondary of a CT is open
circuited the whole current in the primary becomes magnetizing current & a
dangerously high voltage will appear across the secondary which may cause
insulation breakdown, damage to the magnetic property of its iron core,
overheating and also death to life. For these reasons open circuiting of a CT
should never be permitted.
Current limit of
CT is 50 amps and voltage limit of PT is 750 volts.
Standard
secondary rating of PT is 110 volts and that of CT is 5 amps.
Basic difference between a power transformer and a
potential transformer according to the operating condition: Though the primary windings in both power
transformer and potential transformer are energized continuously at a
substantially constant voltage, the secondary of a power transformer is
connected to a a load which may vary between zero and the maximum which he
transformer is capable of carrying whereas the load or burden connected to the
secondary of a potential transformer does not vary as a rule. The permissible
voltage drop in potential transformer between zero and maximum burden is much
smaller than the corresponding limit in a power transformer.
Earthing arrangement for:
(a) 132 kV or 220 kV generator transformers: The metallic frame is earthed by two
separate and distinct connections with earth. The neutral point is directly
earthed by not less than two separate and distinct connection with earth each
having its own electrode thus permitting the grading of insulation in the
transformer from the terminal end to the neutral point.
(b) 11kV or 33kV substation transformers: The frame is earthed by two separate
earth electrodes as above but for neutral earthing resistance earthing not less
than two numbers may be used to limit the fault current which is expected to be
too high in this case.
(c) 11lB/0.433 kV distribution transformers: The frame is earthed by two separate
earth electrodes and the neutral of the secondary star winding is earthed by
not less than two nos separate and distinct connections directly to earth each
having its own electrode.
(d) Transformer with delta winding: The frame is earthed by two separate
earth electrodes. An earthing transformer may be used to get the star neutral
point which may be earthed by two separate connections to the earth either
directly or through a resistance if desired.
(e) Instrument transformers: Cases or frames of instrument
transformers, the secondary windings of current transformers and one point of
the secondary winding of potential transformer shall be earthed which may be
done by connection to the earth bus.
Earthing transformer: An earthing transformer is a transformer which is
intended primarily for the purpose of providing a neutral point for grounding
purposes. It may be a two winding unit with a delta connected primary and a
star connected secondary or a single winding three phase auto-transformer with
windings in interconnected star or “Zigzag”.
When the
necessity arises for earthing the neutral of one part or another of an
interconnected transmission or distribution network at a place where no natural
neutral point is available, an earthing transformer is used for that purpose.
The neutral point of the earthing transformer is connected to earth directly or
through a current limiting impedance while the terminals are connected to the
three phase lines.
Arrangements
for proper ventilation of transformer installed indoor in an enclosed room: For proper ventilation the transformer
should be kept well away from the wall to make free movement of air round all
the four sides. To ensure proper air circulation for the efficient cooling of
the transformer a minimum are of 1 sq/ meter for inlet per 1000kVA should be
provided as near the floor as possible and a minimum area of 2 sq. meters for
outlet per 1000kVA should be provided in the opposite side of air inlet as high
as the building allows to enable the heated air to escape readily and be
replaced by cool air.
Name Plate: Indoor type Transformer
Make
|
Vijay Electrical Ltd (Hydrabad)
|
Type
|
Dry type Resin Cast
|
Capacity
|
2500 KVA, 2.5 MVA
|
No load Voltage
|
HV: 33000 volts, 33 KV
LV : 433 volts
|
Current:
|
HV: 43.738 Amps
LV : 3333.43 Amps
|
Type of cooling
|
AN ( Air
Natural)
|
Frequency
|
50Hz
|
Imp. Voltage
|
8.76%
|
Core, Coil Assy
|
9830 Kg
|
Enclosure & fitting
|
2320 Kg
|
Total Weight
|
12150 Kg
|
Off ckt Tap changing links
|
+
in steps of 2.5 variation in HV
|
Phase
|
3
|
Scanner
|
total 8 channels. Alarm – 130oC, Trip 140oC
|
Class of insulation
|
H (180o)
|
Vector gr.(Connection symbol)
|
Dyn11
|
Yr of manufacturing
|
2004
|
Insulation Level
|
HV-Kv : L1170/AC-70
LV55354-Kv: AC-3
|
Serial No
|
|
Guaranteed max. temperature rise in winding
|
over an ambient of 45oC-95oC
|
Neutral CT
|
4000/1
|
Dry type Resin cast: Advantage
1.
Improves
earth tracking resistance
2.
High
di-electric strength
3.
Moisture
repellent
4.
Flame
retardant
5.
High
insulation resistance
6.
Easy
for maintenance.
PROTECTION (AUXILIARY RELAY TYPE VAA-ALSTOM)
1.
Over
current
2.
Earth
Fault
3.
Restricted
Earth fault
4.
High
winding temperature protection. ALARM- 1000C, TRIP – 1100C
5.
Door
interlocking
6.
Neutral
displacement relay.
TYPES
OF TRANSFORMER
1.
CORE
type, 2. BERRY type, 3. SHELL type, 4. DISTRIBUTION, 5. Power, 6.
AUTO-TRANSFORMER, 7. SINGLE & THREE PHASE.
In Transformer/Alternator, star point is
earthed because to keep unbalance load & line voltage constant. So,
electrical equipment is safe.
PT PV SI
Transformer ratio: ----
= -------- = --------
ST SV PS
PT: Primary winding - high turns wire small/high voltage 33Kv
Secondary winding – low turns wire thick/low voltage 110 V
CT: Primary winding – low turns wire max
thick / high current 100 Amps
Secondary winding high turns wire thin/ low current 1 Amps
VECTOR GROUP Dyn11
Primary
is Delta connected and Secondary is Star connected. As per Watch minute pointer
indicates Primary Voltage & Hour pointer indicates Secondary voltage. When
there is 11 o’clock in the watch it means there is 300 angle between
two pointers. i.e Secondary voltage
leads by 300 to primary voltage. When primary voltage leads to
Secondary voltage, it is in anti-clockwise direction of the watch.
Percentage impedance: 8.76
Ø If 33 Kv supply is give to HT side and
if 3333.33 amps full load current is
flowing then secondary voltage will be 400v in place of 433v ie 8.76% less.
Ø If secondary if short circuited , we are
giving 8.76 v in place of 33kv, then from secondary 3333.33 amp current will
flow.
Transformer: The transformer is of resin cast type with primary
winding connected in delta and secondary winding connected in star. HV & LV
winding are separately cast under vacuum with unfilled epoxy resin system and
with fiber glass reinforcement core is constructed out of cold rolled grain
oriented silicon steel and the exposed cut surfaces are given epoxy varnish
coating. Core clamping is done with mild steel channels. Tie rods and clamping
rods with FRP sheet insulation between core channels and lamination. HV &
LV coils are assembled concentrically with FRP and supporting blocks at top and
bottom winding. Temperature is monitored with the help of PT-100 sensors
connected to a Digital winding temperature scanner. WTS is provided with two
set points for Alarm and trip.
Periodic Inspection & Maintenance:
i) Ensure that
the transformer is kept free of dust and other obstructing material on the
enclosure.
ii) Check
protection circuit periodically.
iii) Check the
winding temperature scanner and limit switches of doors.
Iv) Ensure that the transformer is not
overloaded.
Ø In case of repair, it
should be de-energized and the enclosure case should be grounded. This ground
should be connected to all transformer coil terminals these connections must be
removed before the transformer is placed in service.
Ø Dry type resin cast
transformer, require very little maintenance from time to time. However,
inspection should be made at regular intervals and corrective measure shall be
taken when necessary to ensure the most satisfactory service from this
equipment evidence of rusting. Corrosion of enclosure and deterioration of
the insulation and point should be checked and corrective measures shall be
taken whenever necessary.
Ø Winding should be
inspected for dirt especially accumulation on insulating surface or where it
would tend to restrict air flow. For loose connections for the condition of tap
changing links or terminal boards and for the general condition of the
transformer. Accumulations of dirt on the coils, insulators, lead connections
of ventilated. Dry type transformers should be removed to permit free
circulation of air particular attention should be given to the cleaning of top
and bottom ends of coils assemblies and to the cleaning of ventilating ducts.
Ø The winding may be cleaned
with vacuum cleaner, air blower or with compressed air, care should be taken to
maintain adequate ventilation during cleaning, lead supports, tap changing
links and terminal boards, bushings and other major insulating surfaces should
be brushed or wiped with a dr4y link free cloth.
Connection
of CT for transformer: The CTs are delta connected on the star side and star
connected on the delta side in order to compensate for the phase difference in
the primary and secondary currents of power transformer.
The ratio of the CT on the
HV side of a 3 phase Star-Delta, 33/11 kV transformer if the protecting CT on
the LV side has a ration of 300:5. If 300 Amps is the line current on the LV
side the CT secondary current is 5 Amps. 11
The line current on
HV(Star side = 300 x ------ = 100 Amps
33
The CTs on the star side are delta connected and the current
required on the relay side of the CT is 5 amps. Therefore, the current in the
CT
Secondary (phase current) is 5/√3. Therefore the CT ratio on
the HT side will be 100: 5/√3.
Bus bar protection schemes: There are mainly two
classes of bus bar protection schemes:
(a) Differential protection, the most sensitive and reliable
method of protection.
(b) Fault bus protection also known as frame leakage
protection gives the earth fault protection.
Protection schemes for
feeder line: The feeder line protection schemes are as follows:
(a) Time graded over current and earth fault protection.
(b) Instantaneous over current protection.
(c) Differential pilot wire protection with wire pilot system
or carrier pilot system.
(d) Carrier current protection with phase comparison relaying
or directional comparison relaying mainly used for transmission lines of 132 kV
and above.
(e) Distance protection employing plain impedance relay,
reactance relay or MHO relay.
(f) Reverse power protection generally employed in
interconnected system of generating units or stations, ring and parallel
feeders.
No comments:
Post a Comment