PROTECTION OF TRANSFORMER CHAPTER - 5
Introduction
The transformer is heart of
power system. Power transformer is a major equipment in power system. It
requires highly reliable protection devices. The protective scheme depends on
size of transformer. The ratings of transformers used in transmission and
distribution systems range from few kVA to several hundred MVA. For medium
capacity transformers over current relays are used. For large transformers
differential protection scheme is used.
Abnormalities
and faults
The faults occurring in
power transformer are earth fault, phase to phase faults, inter turn faults,
over heating because of overloading, core heating. The most common type of
faults are, earth faults, inter turn faults.
Through
fault: It
is a fault which lies outside the protective zone of the transformer but fed
through the transformer.
Following Table shows,
abnormal conditions; the protection necessary for power transformer.
Abnormal
Condition/Fault
|
Protection
Employed
|
Over load
|
I)
Thermal overload relays
II)
Temperature relays.
|
Earth faults
|
i)
Differential protection.
ii)
Earth fault relay
|
Through faults
|
i)
Graded time lag over current relay
ii)
HRC fuses
|
Incipient faults
below oil level resulting into
decomposition of oil.
|
i)
Buchholz relay i.e. gas actuated relay
ii)
Pressure relief valve
|
Large internal
faults: Phase to phase, phase to ground, below oil level.
|
Buchholz relay and
circuit breaker.
|
Faults in tap
changer.
|
i)
Percentage differential protection
ii)
High speed over current relay.
|
High voltage surges
due to lightning & switching
|
I)
Horn gaps.
II)
Lightning arrestor.
|
For other transformers the
protections provided are as per following table:
Abnormal
Condition/Fault
|
Protection
Employed
|
Small distribution
transformer
|
HV fuses for earth
fault protection and phase fault protection
|
Transformers in
important location rating 500 kVA above.
|
i)
Restricted earth fault protection.
ii)
Over current protection.
iii)
Buchholz relay.
|
While selecting protection
scheme for transformer the following information is necessary.
i)
kVA
rating.
ii)
Whether
it is indoor or outdoor.
iii)
Voltage
ratio.
iv)
Connections
of winding.
v)
Percentage
reactance.
vi)
Neutral
point earthing, value of resistance.
vii)
Conservator
is provided or not.
viii)
Value
of system earthing resistance.
ix)
Details
of connection of CTs and relays.
x)
Fault
level at transformer terminals.
xi)
Network
diagram showing position of transformer.
Differential
protection for transformer
The
differential protection is based on current circulation principle. It is also
known as Merz-Price protection. CTs will be used with pilot wire and relay
coils. The CTs will be connected in primary side and secondary side of the
transformer to be protected. The system is fundamentally same as that for
alternator. However, the scheme used for alternator can not be directly used
for transformer protection. This is because of following reasons:
1.
One
group of CTs is to be connected in primary side of transformer and second group
of CTs is to be connected in secondary side. The currents of primary side and
secondary of transformer are different. But for differential protection, under
normal working condition, the CTs should send same amount of current in the
pilot wire so the CT ratio of respective side is selected such that they send
same current in pilot wire so the CT ratio of respective side Ct ratios are
different but pilot wire currents are the same under normal working condition.
2.
The
primary side and secondary side currents of transformer have phase difference.
This is because the transformer may be delta-star or star-delta connected. So
CTs used for protection have to be connected is a particular way.
Following
table shows the connection to be made for the CTs used in differential
protection of power transformer.
Power
Transformer Connections
|
CT
Connections
|
||
Primary
|
Secondary
|
Primary
|
Secondary
|
Star with neutral earthed
|
Delta
|
Delta
|
Star
|
Delta
|
Delta
|
Star
|
Star
|
Star
|
Star with neutral earthed
|
Delta
|
Delta
|
Delta
|
Star with neutral earthed
|
Star
|
Delta
|
This, we can conclude that
CTs on star side of transformer should be connected in delta and CTs on delta
side should be connected in star.
Differential protection
scheme Merz-Price protection scheme for delta-delta power transformer.
The scheme for protection
of delta/delta power transformer is an shown in Fig. This protection scheme
gives protection against phase to ground and phase to phase fault. The CTs on
primary and secondary side are connected in star. All the CTs are identical.
During normal working
conditions the CT secondary currents are equal and no current flows through the
relay coil.
When line to ground fault
or phase to phase fault occurs, the currents through the CT secondary’s are no
longer the same. A difference current is produced which flows through pilot
wires and relay coils. The respective relay coil is thus energized, it sends
trip signal to circuit breakers on primary and secondary side. The CBs then
operate and transformer is disconnected.
Differential
protection scheme/Merz-price protection scheme for delta-star power transformer:
The CTs on delta side of
power transformer are connected in star and CTs on star side of transformer are
connected in delta as shown in figure.
The working of this scheme
is exactly the same as explained for delta-delta power transformer. In the
similar way diagram can be drawn for Star-delta transformer. The working of
that scheme will be similar.
SOLVED
EXAMPLES
Example: A 3-phase, 33/6.6
kV, star delta transformer is protected by Merz-Price circulating current
system. If the CTs on the low voltage side have a ratio of 300/5. Determine the
ratio of CTs on the high voltage side.
Solution: Suppose current
flowing in secondary side of transformer is 300 Amp. This current is primary
current for the CTs connected to delta side of transformer. The secondary
current of the CT will be 5 Amp. Since ratio is 300/5.
(Note: For both side CTs
the primary side is single turn i.e. bar type or line conductor itself acting
as primary winding.)
For differential protection
scheme, when operating conditions are normal, the CT secondary currents flowing
through pilot wire from both group have to be equal. Refer Figure we have drawn
it for the CTs only. The CT1, CT2, CT3 are in primary side of transformer and
these are connected in delta and CT1, CT2, CT3 are in secondary side of
transformer and these are connected in star.
The pilot wire current = CT
secondary current (connected a delta side of transformer)
= 5 Amp.
The CTs connected in delta
should also send 5 Amp. In the pilot wire i.e.
same current.
So current induced in the
CTs secondary should be 5/√3 Amp.(For delta circuit, line current is √3 times
phase current.
Thus the CTs connected in
delta have a current of 5/√3 Amp in their secondary.
(Note: For both side CTs
the primary is bar type i.e. single turn or the line conductor)
Primary apparent power = Secondary apparent power
√3V1I1 =
√3V2I2
√3 x (33 x 1000) x I1 = √3 x (6.6 x 1000) x 300
We have already assumed
that secondary carries 300 Amp.
I1 = 60 Amp
This is primary current of
main transformer and it is primary current of CT on HV side.
So Primary current of HV
side CT = 60 Amp
Secondary current of HV
side CT = 5/√3 Amp.
Ratio = 60: 5/√3 or
60/(5/√3)
Example 2: A 3-phase Transformer
of 220/10000 line voltage is connected in star/delta. The protective
transformers on 220 V side have a current ratio 600/5. What should be the CT
ration on 11000 V side?
Solution: The connection
diagram will be similar to example A.
Suppose the line current on
220 V side is 600 Amp. i.e. CT primary current (I1) is 600 Amp. The
CT secondary i.e. phase current in delta connected CTs current will be = 5
Amp…. (Therefore the ratio is 600/5). The current coming out in pilot wires
(i.e. line current) from delta connected CTs is 5√3 … (for delta connection IL
- √3Iph).
Under normal condition,
same current is supposed to flow in pilot wires from 11000 V side CTs. Therefore,
secondary current of star connected CTs is 5/√3 Amp.
Primary apparent power =
Secondary apparent power
√3V1I1 = √3V2I2
√3 x 220 x 600 = √3
x 11000 x I2
I2 = 12
Amp.
This is line current of
secondary of main transformer which is primary current for star connected CTS.
Primary current 12
So
CT ratio = ---------------------- =
----- or 12: 5√3
Secondary Current 5√3
Difficulties in
differential protection scheme:
1.
CT
ratio error during short circuit : This is because of inherent characteristics
of individual CT.
2.
The
difference in pilot wire lengths causes current difference.
3.
During
short circuit condition, the CT core may saturate due to high flux density.
Percentage
differential protection:
To increase reliability of differential protection percentage differential
protection or biased differential protection is used.
Fig. Shows, arrangement of
biased differential protection for delta – Star power transformer.
The percentage differential
relay has an operating coil and restraining coil in each phase. The operating
coil is connected between mid-point to restraining coils and neutral pilot
wire.
Under normal working
conditions, the currents in pilot wires fed from CTs are equal and no
differential current flows through operating coil. When fault occurs in the
transformer winding, the balance is disturbed and differential current flows
through operating coil and parts of restraining coil. Trip signal is thus
produced and CB is operated.
OVER CURRENT PROTECTION
When cost of differential
relying is not justified, over current protection is provided. Following relays
are used for over current protection. Instantaneous over current relay, inverse
time relay, directional over current relay, static over current relay, thermal
relays.
HRC fuses, shows dropout
fuses are also used up to 11 kV.
The three over current
relays R1,R2, R3 are connected in CTs
secondary circuit.
When fault occurs in the
protected zone, the CT secondary current increases and it operates the circuit
breaker.
This scheme is used for
short circuit faults, phase faults, earth faults.
EARTH FAULT
PROTECTION
When the fault current
flows through earth return path, the fault is called earth fault. The earth
faults area frequent. So earth fault protection is important.
Residual
earth fault relay:
When earth fault does not take place, the sum of three secondary currents of CT
is zero. i.e. IR +IY
+ IB =0.
The sum of these currents
is called residual current. When earth fault develops, the sum of three
currents is not zero, the residual current flows through earth fault relay.
This protection is also
called unrestricted earth fault protection. In another scheme, the relay is
connected in neutral of the transformer.
The neutral acts as CT
primary. When fault occurs, the fault current flows through this earth
connection and secondary current inc4reases causing earth fault relay
operation. The amount of neutral current flowing does depend on type of
earthing system provided.
This is also called
unrestricted earth fault protection.
Earth
fault Protection with Core Balance Current Transformer (CBCT)/zero Sequence CT: A core balance CT is used
in this scheme. The core of CBCT has large cross-sectional area so that it does
not saturate when fault current produces high flux density in it.
The core embraces the three
conductors R, Y, B. Under normal condition, the components of fluxes produced
by three currents are balanced and CT secondary current is negligible and relay
does not operate.
When earth fault develops
the balance is disturbed and sufficient current is induced in CT secondary thus
relay is operated.
RESTRICTED
EARTH FAULT PROTECTION
The previous schemes for
earth fault come under unrestricted category i.e. the scheme may operate for a
fault beyond the transformer winding.
If a fault(F1) occurs,
which is beyond transformer it causes current I1 and I2 flow through CT
secondary’s and resultant current through R (relay) is negligible and it does
not operate.
If fault F2 occurs, current
I2 flows and I1 is negligible so I2 flows through R and relay is operated.Thus,
this scheme can distinguish between the faults that are away from transformer
winding and within transformer winding.
INTER TURN
FAULT PROTECTION
The normal differential
protection scheme can protect the alternator against phase to ground or phase
to phase faults. It cannot protect the alternator from inter-turn faults. This
is because current entering and leaving the alternator winding remains the same.
Even though some turns of any phase are shorted. So CT secondary currents do
not change and operating coil does not carry any current.
The inter-turn faults later
on develop earth fault, so inter-turn fault must be detected at an early stage.
This scheme is used for
multi-turn alternators. For multi-turn alternator, the winding of each phase is
divided into two equal sections (S1 and S2). Two
identical CTs are connected in respective windings. The CT secondary's are
connected in phase opposition and a relay R is connected in CT secondary loop.
The functioning of this
scheme is similar to differential protection principle.
Under normal operating
conditions, the currents through S1 and S2 are same, so
CT secondary’s carry same current. And no current flows through relay R.
If the adjacent turns of S1
are shorted, currents shared by S1 and S2 differs hence
there is differ3ence in CT secondary currents. The difference current flows
through the loop and relay now carries current and produces trip signal for CB.
THERMAL
OVERHEATING PROTECTION OF LARGE TRANSFORMER
Temperature sensors are
kept in the vicinity of transformer winding. Thermocouples, resistance
temperature detectors can be used. These are arranged in the bridge circuit,
when temperature rises above safe value, the bridge balance is disturbed and
voltage is available across two points of that bridge. This voltage signal can
be used to operate the alarm or to operate the circuit breaker.
Some typical settings for
oil temperature are as follows:
Switch ON fans :600C
Alarm ON : 950C
CB trip : 1200C
Oil
Thermometer:
It is commonly used for oil filled transformer. It is equipped with alarm
contacts to give indication of excessive increase in temperature. Accordingly
signal can be processed to make the fans ON.
However, thermometer is not
a reliable fault detecting device because it does not detect winding
temperature correctly. This is because the transformer oil has much longer time
constant than windings themselves i.e. winding temperature heats up the oil,
oil temperature increases and this oil temperature is measured by thermometer.
So
by the time thermometer measures the oil temperature, actual winding
temperature is much higher.
BUCHHOLZ
RELAY
It
is gas actuated relay. It is connected in the pipe installed between
transformer tank and conservator.
Construction: It consists of a domed
vessel. There are two mercury switches. The upper mercury switch is attached to
a float. This float is hinged. The lower mercury switch is attached to the flap
and the mechanism in hinged.
Alarm
circuit contacts are brought to upper mercury switch and trip circuit contacts
are brought to lower mercury switch.
The
upper mercury switch operates during incipient faults and lower mercury switch
operates in case of severe faults.
Working: Under normal working
conditions, the position of mercury switches. It is seen that the alarm circuit
contacts and trip circuit contacts are not bridged by liquid mercury in the
switch. In case of incipient faults, the heating oil occurs, the oil decomposes
and gases are formed. The majority portion of gases is hydrogen (70%). This gas
is accumulated at the topside near domb. Due to gas pressure, the float comes
down and mercury level shifts closing the alarm circuit contacts. Thus alarm
circuit is complete and alarm sounds.
In case of severe faults,
gas formation is rapid and large amount of gas rushes from transformer to
Buchholz relay. During its travel, the gas produces sufficient pressure on the
flap, the flap turns in anticlockwise direction, the mercury switch also tilts
and mercury level inside the mercury switch shifts, closing the trip circuit
contact. Thus, trip signal is produced causing operation of circuit breaker.
The Buchholz relay is used
for transformer having rating greater than 750 kVA because of economy reasons.
Advantages:
1.
Simple.
2.
Fault
detection is faster.
3.
Operation
is reliable.
Disadvantages;
1.
Only
applicable for oil immersed transformer.
2.
Only
the faults below oil level can be detected.
EXERCISE
1.
Write
a short not on abnormalities and faults in transformer.
2.
What
are the difficulties in differential protection scheme used for transformer?
3.
How CTs used in differential protection of
3-phase transformer are to be connected?
4.
How
over current protection is provided in case of transformer? Explain any one
scheme.
5.
Explain
earth fault protection using CBCT.
6.
Explain
restricted earth fault protection scheme with a neat diagram.
7.
Write
a short note on thermal overheating protection for transformer.
8.
Explain
any one scheme for inter turn fault protection for transformer.
**********************************
No comments:
Post a Comment