PROTECTION OF ALTERNATOR CHAPTER - 4
INDRODUCTION
Alternator
is the most important and costly equipment in power system. The cost is high
because the alternator unit is accompanied by prime mover, excitation system,
voltage regulator, cooling system etc. The protection system provided should be
therefore becomes elaborate and complex.
As
soon as the fault develops on alternator, it should be immediately disconnected
from he other generating plant to avoid the faulty machine from being fed by
other sources.
ABNORMALITIES AND FAULTS
Following
Table shows abnormal conditions (Faults) and protection schemes employed for
the alternator.
SN
|
Abnormal Condition
|
Effect
|
Protection
|
1
|
Thermal
overloading:
i) Continuous
overloading
ii) Failure
of cooling system
|
Overheating
of stator winding and insulation failure.
|
Thermocouples
of resistance thermometer impeded in stator slots and cooling system. Stator
overloading protection with over current relays.
|
2
|
External
fault fed by generator
|
Unbalanced
loading stresses on winding and shaft, excessive heating for prolonged short
circuit.
|
Negative
phase sequence protection for large machines.
Overload
protection for small generators.
|
3
|
Stator
faults:
i)
Phase to phase
ii) Phase to
earth
iii) Inter-turn
|
Winding
burn-out, welding of core laminations down
|
Biased
differential protection, sensitive earth fault protection, inter-turn fault
protection.
|
4
|
Rotor
earth faults
|
Single
fault does not harm second fault causes unbalanced magnetic forces causing
damage to shaft, bearings
|
Rotor
earth fault protection
|
5
|
Loss of
field:
Tripping
of field circuit breaker.
|
Generator
runs as induction generator deriving excitation currents from bus-bar. Speed
increases slightly.
|
‘Loss of
field’ or ‘Field failure’ protection.
|
6
|
Motoring
of generator. When input to prime mover stops, the generator draws power from
bus-bars and runs a synchronous motor in the same direction.
|
Effect
depends upon type of prime mover and the power drawn from he bus during motoring.
|
Reverse
power protection by directional power relays direct the reversal of power.
|
7
|
Over-voltages
|
Insulation
failure
|
Lightning
arresters connected near generator terminals.
|
8
|
Over-fluxing
of generator transformer and auxiliary transformer.
|
Heating
of core relay.
|
Connected
in voltage regulator circuit generator.
|
9
|
Under-frequency
|
Failure
of blades of steam turbines.
|
Frequency
Relays.
|
Something about diagrams: The differential
protection scheme is applied for 3-phase alternator. For simplicity of
understanding the star and delta connections are drawn in some different way .
DIFFERENTIAL PROTECTION
This
is the most common scheme used for alternator protection differential
protection scheme for a star connected alternator.
Six
identical CTs are used for this scheme. The secondary’s of CT area connected in
star through pilot wires. The relay operating coils (R1, R2, R3) are connected
across neutral pilot wire end. The relays are connected between equi-potential
points respective line pilot wires of CT secondary side. The relays used are
electromagnetic type. Operation under normal working conditions, the current
entering altering the alternator winding is equal to current leaving the
alternator winding.
There
is induced current in secondary’s of CT these currents are also same in
magnitude. These currents circulate in pilot wires but not through the relay
coils.
When
a fault develops, say earth fault or phase to phase fault, the current entering
the alternator winding is not equal to current leaving the alternator winding.
So CT secondary currents are no longer equal and difference current flows
through operating coil. Thus, relay is energized, and trip signal operates the
respective CB to isolate the faulty part.
Percentage Differential Protection of
Alternator/Biased Differential Protection of Alternator
Fig.
(a) and (b) shows percentage differential protection scheme for star and delta
connected alternators.
For
star connected alternator the neutral is earthed through a resistance. The CTs
are connected in star. One more coil called restraining coil is added in the
circuit as shown. The restraining coil is connected centrally in the pilot
wires. The respective operating coils are connected at centre of respective
restraining coils. Under normal operating conditions the secondary currents of
CTs are equal. Thus, there is balanced circulating current in the pilot wires
and the restraining coil and current does not flow in the operating coil.
EARTH FAULT PROTECTION OF ALTERNATOR
When
the fault current flows through earth return path, the fault is called earth
fault. The earth faults are frequent. So earth fault protection is important.
Residual earth fault relay: When earth fault does not
take place, the sum of three secondary currents of CT is zero. i.e. IR
+IY + IB =0.
The
sum of these currents is called residual current. When earth fault develops,
the sum of three currents is not zero, the residual current flows through earth
fault relay.
This
protection is also called unrestricted earth fault protection. In another
scheme, the relay is connected in neutral of the transformer.
The
neutral acts as CT, primary. When fault occur, the fault current flows through
this earth connection and secondary current increases causing earth fault relay
operation. The amount of neutral current flowing does depend on type of
earthing system provided.
This
is also called unrestricted earth fault protection.
Earth Fault Protection with Core
balance Current Transformer (CBCT)/zero Sequence CT.
A
core balance CT is used in this scheme. The core of CBCT has large
cross-sectional area so that it does not saturate when fault current produces
high flux density in it.
The
core embraces the three conductors R, Y, B. Under normal conditions, the components
of fluxes produced by three currents are balanced and CT secondary current is
negligible and relay does not operate.
When
earth fault develops the balance is disturbed and sufficient current is induced
in CT secondary, thus relay is operated.
RESTRICTED EARTH FAULT PROTECTION FOR
ALTERNATOR
The
CTs area connected in star as shown in Fig. The remaining connections are as
per percentage differential protection scheme. In addition, one restricted
earth fault relay is placed in the star connection of CT secondary’s as shown
in Fig.
When
earth fault occurs on the winding, the imbalance current flows through the
operating coils and restricted earth fault relay. Thus, the restricted earth
fault relay operates and trip signal is produced which operates the CB.
INTER-TURN FAULT PROTECTION OR STATOR
INTER-TURN FAULT PROTECTION
The
normal differential protection scheme can protect the alternator against phase
in ground or phase to phase faults. It cannot protect the alternator from
inter-turn faults. This is because current entering and leaving, the alternator
winding remains the same. Even though some turns of any phase are shorted. So
CT secondary currents do not change and operating coil does not carry any
current.
The
inter-turn faults later on develop earth fault, so inter-turn fault must be
detected at an early stage.
Fig.
shows arrangement for inter-turn fault protection scheme. We have shown it for
one phase only for simplicity of under standing. For three phases alternators
there will be such three groups.
This
scheme is used for multi-turn alternator, the winding of each phase is divided
into two equal sections (S1 and S2) as shown in figure.
Two identical CTs are connected in respective windings. The CT secondary’s are
connected in phase opposition and a relay R is connected in CT secondary loop.
The
functioning of this scheme is similar to differential protection principle.
Under
normal operating conditions, the currents through S1 and S2
are same, so CT secondaries carry same current. And no current flows through
relay R.
If
the adjacent turns of S1 are shorted, currents shared by S1 and S2 differs
hence there is difference in CT secondary currents. The difference current
flows through the loop and relay now carries current and produces trip signal
for CB.
OVERHEATING PROTECTION
Stator Overheating Protection: Overheating in stator may
be caused by the failure of the cooling system, over loading or core fault like
shorted laminations.
Modern
alternators 9above 2MW) employ two methods to detect overheating.
In
one method, the inlet and outlet temperatures of cooling medium are measured.
Cooling medium may be gas (hydrogen) or liquid (water). The inlet and outlet
temperatures of cooling medium are compared and if drastic difference is there,
it means over heating is occurring. Thus, overheating can be detected.
In
second method, temperature sensors are embedded in stator slots. The
temperature sensors may be a RTD (Resistance Temperature Detector), thermistor,
thermocouple.
Whetstone's
bridge principle is used to detect overheating. P, Q and S are the fixed value
resistances. The RTD is connected in one arm as shown. This RTD is kept in
stator slot of alternator. When temperature is within limits, point a and b are
he same potential and relay coil does not carry any current i.e. bridge is
balanced. When overheating occurs, RTD resistance changes causing imbalance and
some potential difference is created across a and b. The relay coil is thus
energized and relay operates the alarm circuit.
Negative Sequence Protection of
Alternator Against Unbalance Load
When
stator currents are unbalanced, they produce negative sequence component. This
component rotates at synchronous speed and in opposite direction to rotor. This
cause double frequency currents to be induced in the rotor. So, rotor iron
losses increase and heating of rotor occurs. The double frequency current also
produces vibrations and heating of stator.
Figure
shows a scheme for protection against unbalance loads.
Three
CTs are connected in star and the secondary’s are connected to negative
sequence filter, over current relay is connected to sequence filter.
The
negative sequence filters consists of number of inductors and resistors. This
negative sequence filter detects presence of negative sequence component due to
unbalance and operates.
REVERSE POWER PROTECTION
The
turbine drives the alternator. Alternator is connected to supply system through
transformers, bus bars etc. And at a time many alternators are connected to the
supply system. But when input to any one turbine is stopped, the alternator
continues to rotate as a motor i.e. it takes electrical power from supply and
supplies mechanical input to the turbine so it drives the turbine.
So
previously the power flow was from turbine à alternator à supply system and no it is
from supply system à motor (alternator acting
as a motor) à turbine i.e. power flow reverses. When
electrical power flows in reverse direction, it still maintains the balance in
three phases. So reverse power flow can be detected by using a single relay in
any one phases.
Directional
relay can be used to detect reverse flow. Figure shows induction type
directional relay to detect reverse power flow.
The
shunt magnet coil and series magnetic coil are excited from any one alternator
winding. When power flow direction is correct the disc rotates in normal
direction. But when power flow reverses, the disc rotation is in opposite
direction and opposite rotation causes trip circuit contacts to close. Thus,
trip signal is produced.
SOLVED EXAMPLE
A
20 MVA 11kV, 3-phase star connected alternator is protected by Mertz-Price
protection scheme. The star point is earthed through a resistance of 5Ω. If
CTs have a ratio of 1000/5 and the relay is set to operate when there is an out
of balance current of 1.5 Amp.
Calculate:
i)
The
percentage of each phase of the stator winding which is unprotected.
ii)
The
minimum value of earthing resistance to protect 90% of the winding.
Solution: i) Let X% of the winding is
unprotected, Earthing resistance re = 5Ω
11 x
103
Vph = Voltage
per phase = --------- = 6350.85 volts
√3
The minimum fault current to operate
the relay = 1000/5 x 1.5 = 300 Amp.
e.m.f.
induced is X% of stator winding, = Vph x (X/100) = 63.508 x Volt.
Earth
fault, current that will flow because of voltage induced in X% winding
= 63508X
63.508
------------- =
------------ = 12.7X amps.
re 5
This current should be equal to
minimum fault current required to operate the relay.
12.7X = 300 so X = 23.62%
ii)
Let re = minimum earthing resistance required to protect 90% of the stator
winding. The 10% winding will be unprotected.
63.508
x 10
i.e. X = 10% 300 =
63.508X/re 300 = ----------------
= 12.7X Amp, re = 2.12Ω.
re
EXERCISE
1.
State
the abnormalities and faults in alternator with necessary protection.
2.
Draw
a diagram of differential protection scheme for a star connected alternator and
explain its working.
3.
Draw
a diagram of percentage differential protection scheme for delta connected
alternator and explain its working.
4.
Explain
earth fault protection of alternator using CBCT.
5.
With
a neat sketch explain overheating protection using Wheatstone bridge.
6.
Draw
a protection scheme for double frequency current using negative sequence
filters.
***************************************************
I like your blog because you shared the content about Protection of Alternator. It is help to the employers as well as workers who are worked in the Electrical Protection system. If you have any queries about Relay Coordination system, Click on
ReplyDeleteRelay Coordination