NEUTRAL GROUNDING CHAPTER - 8
INTRODUCTION
The term earthing means
connecting the non-current carrying parts of the electrical equipment or the
neutral point of the supply system to the general mass of the earth in such a
manner that at all times an immediate discharge of electrical energy takes
place without danger.
Earthing means making a
connection to the general mass of earth. The use of earthing is so widespread
in the electric system that at practically every point in the system, from the
generators to the consumer’s equipments, earth connections are made.
Earthing is achieved by
electrically connecting the respective pats in the installations to some system
of electrical conductors or electrodes placed in the intimate contact with the
soil some distance below the ground level. The contacting assembly is called
the Earthing.
The
subject of earhing is divided into:
a)
Neutral
Earthing and
b)
General
Earthing
a)
Neutral Eathing is also known as “System Earhing” has the following
objectives:
1.
To
reduce the voltage stresses due to switching and lightening surges and
2.
To
control the fault currents to satisfactory values.
b)
General Earthing is also known as “Protective Earhing” and is provided
for protection against the dangers to plant and personnel associated with the
use of electrical energy.
Thus, the objectives of the
earthing are:
1. For the safety of personnel
from electric shock insuring that non-current carrying parts, such as equipment
frames are always safely at ground potential even though insulation fails.
2. For the safety of the
equipment and personnel against lightening and voltage surges providing the
discharge path for surge arrestors, gaps and other, similar devices.
3. For providing the ground
connections for the grounded neutral system.
4.
For
providing a means of positively discharging and de-energizing feeders or
equipment before proceeding with maintenance on them.
Power
system earthing is highly important. A substantial and adequate ground that
will not burn-off or permit dangerous rise in voltage under abnormal conditions
is essential. Extensive damage and dangerous conditions have arisen when
inadequate grounds have been provided. Multiple grounds and multiple
connections to them area usually desirable to ensure ground protection, even
though one connection opens due to burn off or other condition such as high
resistance. The station earthing system should have low resistance.
1)
Earth Electrode: Any wire, rod, pipe,
plate or an array of conductors, embedded in ground horizontally or vertically
is known as the Earth electrode. In
distribution system, earth electrode consists of a rod or pipe 1 metre in
length and driven vertically into the ground. In generating stations and
substations grounding mats are used rather than individual rods.
2)
Earth Resistance or
Resistance to Earth:
The resistance offered by the earth electrode to the flow of current into the
ground is known as resistance to earth. The term resistance to Earth or Earth
Resistance does not imply the contact resistance between the earthing electrode
and soil (which is insignificant) but mainly the ‘resistance of soil’ between
he electrode and the point of zero potential. Numerically, it is equal to the
ratio of the potential of earth electrode w.r.t. the remote point to the
current dissipated by it.
Mathematically, earth
resistance is given as V/I where, V is the measured voltage between the
electrode and the voltage spike and I is the injected current during the earth
resistance measurement through the electrode.
As in general rule, the
lower the value of earth resistance better it is but even then the following
values of earth resistance [Max. permissible] values will give satisfactory
results.
Large power station : 0.5 ohms
Major power station : 1.0 ohms
Small substations : 2.0 ohms
In all other cases : 8.0 ohms
3)
Earthing Lead: The wire which connects
earth wire or any other apparatus to be earthed to the earth electrode is known
as the earthing lead.
4)
Earth Current: The current dissipated by
the earth electrode into the ground is called the earthing current.
Soil Resistivity: Before starting the
design of earthing system, it is essential to understand the nature of the
resistance of ground and the various factors which govern it.
When
an electrode is driven into ground, the region around the electrode is known as
“resistance area” or the “potential gradient area” and the fault current tries
to flow away from the electrode in all directions as shown in figure. It
follows that the rise of grounding potential or the flow of current in the
ground depends upon the “resistivity of soil” in which the earthing conductor
is driven. The soil conductivity is purely electrolytic
phenomenon and its resistivity is governed by nature and may vary from ”1 ohm to 10,000 ohm. Some typical values
are:
1.
Sea
water : 2.5 Ω-m
2.
Tap
water : 20 Ω-m
3.
Clay : 50 Ω-m
4.
Sand-clay
mixture : 100 Ω-m
5.
Sand
: 2000 Ω-m
6.
Wet
concrete : 100 Ω-m
7.
Dry
concrete : 10,000 Ω-m
8.
Rock : 10,000 Ω-m
9.
Chalk : 250 Ω-m
It
may be a matter of interest to note that water has very poor conductivity. But
its presence in the soil helps in dissolving the salts thereby improving soil
conductivity. Soil conductivity increases with the increase in moisture content as shown in figure.
However, when moisture exceeds 20% the change in resistivity is negligible. The
amount of water which a soil can absorb depends on the soil type, grain size
and compactness.
The
“Temperature” of he soil also plays
the vital role in varying its conductivity. The effect of the temperature on
the soil resistivity as investigated by the US Bureau of Standards is given in
Table:
|
Temperature
in 0C
|
Resistivity in Ω-m
|
|
200C
|
75
|
|
100C
|
99
|
|
00C Water in
soil
|
138
|
|
00C Ice
formation
|
300
|
|
-50C
|
790
|
|
-10C
|
3300
|
When
the temperature is more than 00C its effect on soil resistivity is
negligible. At 00C water in the soil starts freezing and resistivity
increases.
The
resistivity of soil is also considerably affected by the composition and amount
of soluble salts as shown in figure.
Magnitude of the current also affects the
resistivity of the soil as in case the value of current being dissipated by the
soil is high, it may cause significant drying of soil and increase its
resistivity.
The
soil resistivity at a particular location also varies with depth. Generally, the lower layers of have greater moisture content
and lower resistivity. However, if the lower layer contains hard and rocky
soil, resistivity may increase with depth.
Since,
the soil, resistivity depends on a number of factors, it is always preferable
to make proper resistivity measurements at the proposed site of grounding
system.
What Can Happen if the Neutral is not
Grounded
If
the neutral is not grounded (i.e. kept un-grounded) then:
1)
If
in any of the lines a fault develops (line to earth) the voltage to earth of
the remaining two phases is increases from their “phase to neutral” value (VP)
to full line voltage (VL). Due to this, it results in burning of
insulation (break-down) Natural grounding can avoid this.
2)
The
capacitive currents in the remaining
healthy phase increase to √3 times the normal value. This is avoided by neutral
grounding.
3)
The
capacitive current in the faulty phase is 3-times the normal value which is
very harmful and can be avoided by providing neutral earthing.
4)
The
capacitive fault current “IF” flows into earth which produce “Arcing
Ground” which is dangerous. Due to “IF” high frequency oscillations
are produced which are super imposed on the whole system and builds up very
high voltages about 5 to 6 times the normal voltage which results in insulation
break-down.
For
overhead lines the value of “IF” is found as:
kV x km kV x km x 25
IF = --------------- Amps , For underground cables, IF = --------------- Amps
260
260
Earth Fault
To
support the above discussion, let us compare ungrounded system with neutral
grounded.
C=
capacitances between lines forming delta connection, its influence is very
minor and hence neglected.
CR
= CY = CB for the transpose lines
So
line to neutral current
ICB
= ICR = ICY
The
vector diagram of voltages and currents are for the balanced condition. The
currents lead by 900 with the respective voltages as shown in figure. The
current Vphase/Xc for a balanced currents, the net
current is zero. So no current flows to ground.
Now
take the case of fault developed between a phase and ground (earth fault).
The
current in the faulty line has two components. IBR and IB
as shown through fault and capacitances. The voltage responsible to force these
currents is namely VBR and VBY. The phase difference
between the current and respective voltage is 900 being passing
through Xc.
VBR
√3 VPh
Now, current
IBR = ----- = -------
XC XC
VBY √3 VPh
Now, current
IBY = ----- = -------
XC XC
As seen in the vector diagram he fault
current ‘If’ is the vector sum of IBR and IBY.
√3Vph 3Vph
Trigonometrically, If = √3IBR = √3 X
--------- = --------
Xc Xc
Thus
he capacitive current in the faulty phase is 3 times the normal value.
Capacitive
current in the healthy phases = √3times the normal value.
Advantages of Grounding
i)
Persistent
arcing is eliminated.
ii)
Faulty
part can be disconnected by protective relaying.
iii)
Over
voltages due to arcing can be eliminated.
iv)
Magnitude
of transient voltage is reduced.
v)
System
provides greater safety to the panels and equipments.
vi)
Maintenance
and operational expenses can be reduced.
vii)
Improved
lightening protection.
viii)
A
better system fault protection system is obtained.
METHOD OF NEUTRAL GROUNDING
The
drawbacks discussed above of un-grounded neutral in a situation of earth fault
are eliminated by grounding the neutral by various methods discussed below.
Solid Grounding :
In
this type of grounding, a direct metallic connection is made as shown in
Figure, a) from the system neutral to one or more earth electrodes consisting
of rods, plat or pipes, buried in the ground.
The
path for fault current ‘IF’ is mainly inductive so it lays the
faulted phase voltage (VBN) by 900 as shown in Fig.
The
current in “B phase” has 3 components:
1. “INR” through
phase B, the fault, capacitance CR and to R phase
conductor
2.
“INY”
through B phase, the fault, capacitance CY and Y phase conductor.
3. “IF” through
phase ‘B and fault and ground.
An
analysis of fault by symmetrical components gives.
3Vph
If = -----------------
Z1 +Z2 +Z0
Since
Z1 + Z2 + Z0 is inductive, the current If lags
behind by 900 to phase to neutral voltage or the fault phase VBN.
The
voltages driving the current INR and INY are VNR
and VNY respectively and
since the impedance of the circuits transverse y these current is predominantly
capacitive, they lead their respective voltages by 900 as shown by
phases INR, INY, ICF, the resultant of INR
and INY.
Advantages:
1. The phase to earth voltage
of the faulty phase becomes zero. The other phase remains at their normal phase
values.
2.
The
flow of heavy fault current IF will be completely nullify the effect
of the capacitive current ICF so no arcing ground phenomenon can
occur.
3.
Low
voltage lightning arrestors are sufficient.
4.
There
is saving is cost of equipment.
5. It permits the use of
discriminative protective gear.
Disadvantages:
1. If fault current is heavy,
it causes disturbance in neighboring communication objects.
2.
Higher
capacity C.B.S. is required as there is a possibility of burning contact
material due to heavy current of fault.
3. System has to bear large
number of shocks.
Application:
Suitably used for systems up to 33kV with
total power capacity of 5000 kVA.
Resistance
Grounding
A resistance ‘R’ may be of
metal or may be liquid resistance (used 66 kV or above). Metal resistance is
easy for maintenance but being slightly inductive the effect may create
breakdown of insulation due to lightening. This drawback is absent in liquid
resistance. In case of fault in the line say line B the three currents in it at
the fault F are IF, IBR and IBY. Fault current
IF lags VBN by certain angle (Not 900 due to
resistance) IBR lead VBR by 900 so also IBY
lead VBY by 900, ICF is the resultant of these
two. IF may be resolved into two mutually perpendicular components
(Reactive and Resistive) (as shown by IReac and IRes).
The value of resistance R shall be such that it will limit the fault current to
the full rating of the largest generator or transformer.
Merits
and Demerits of Resistance Grounding:
1.
Minimizes
arcing grounds so hazards are minimized.
2.
It
permits the use of discriminative protective gear.
3.
Cost
of equipment is more than solid type.
4.
Grounding
fault current is less than first method and communication circuits are not
affected much.
5.
Lightning
arrestors are necessary.
6.
The
equipment has to be selected for higher voltages.
7.
Extra
cost due to providing resistance.
Application:
For the system of 33 kV but
power capacity is more than 5000 kVA, this system is suitable.
Reactance
Grounding:
This system is not used.
Grounding through impedance is a reactance grounding.
In this type of grounding,
over voltage or transients may occur due to arcing and higher surge voltage due
to lightening and switching. But it is very good for relaying. It reduces
interference with communication circuits and cost is intermediate. The circuit
arrangement is similar as shown in the next type.
Arc
Suppression Coil Grounding (Peterson Coil Grounding)
L is a iron-cored coil
inserted in the earthing. The function of this coil is to make arcing earth
faults self extinguishing and in
case of sustained faults it reduces the earth current to a low value. The
grounding is also known as resonant grounding, B phase has an earth fault.
ICF = √3IBR
= √3
V/XC
= √3 Vph/XC – 3 Vph/Xc
= 3 times the line to neutral charging
current.
Under the fault condition
the voltage of faulty phase is impressed on the arc suppression coil and a
fault current IF lags approximately by 900 and it is in
phase opposition to ICF. The coil has adjustable tapping and hence
adjusting suitable. It is possible to make ICF =IF and
hence resultant current = 0. Hence, no “arc-ground”, no power current or
capacitive current can flow at fault.
Advantages:
The reactive current at the
fault is neutralized to some extend in the case of cable network by the
capacitance current that finds a return path to the supply point through the
faulty phase byway of the fault.
Drawback: Fault current required to
operate protective devices is ¼ or fault current.
Application: This method is suggested
for medium voltage over-head transmission lines which suffer from lightening, borage
etc.
Voltage
Transformer Earthing
In this system, a voltage transformer
VT is connected to neutral point N and grounded. If acts as a very
high reactance earthing device. It serves as a voltage measuring device to
indicate a fault to earth on the system. The surge diverter is also connected
as shown in figure.
The application of VT
in this circuit is confined to generator equipment which is directly connected
to step up power transformer. The generator circuits are isolated from the main
‘arcing ground’. The extend of the fault can be detected by measuring voltage on
the secondary winding of the transformer.
The earth neutral acts as a
reflection point for the travelling waves through the machine windings. It is
prevented by surge diverter.
Advantages
1.
Transient
voltages due to switching and arcing grounds are reduced due to the reactance
of transformer.
2.
It
acts as a insulated neutral system due to transformer.
No comments:
Post a Comment