Friday, 12 December 2014

Types of Faults:
Sn
Types of Faults
Symbols
Causes
1
Single line to ground fault
           
On line any how touches to ground or support.
2
Line to line fault.
        
Two lines connected together due to insufficient distance or wind pressure.
3
Double line to ground fault.
       
Two conductors touches together and touches to ground or pole/tower.
4
Three phase short circuitl
       
All the three lines make contract in abnormal situation such as storm, falling of trees.
5
Open circuit fault.
       
Conductor may be broken.
6
Simultaneous faults.
       
Two conductors touches and 3rd conductor touches to support/tower.
Fault Statistic: Due to various causes as explained above following is the collected statistical data for faults on various elements.
Sn
Element
%Total Faults.
1
O.H. Lines
50%
2
Under Ground Lines (cables)
  9%
3
Generators
  7%
4
Transformers
10%
5
Switchgears
12%
6
Protective devices like CT, PT, relay etc.
12%

Sn
Types of Fault
%Total faults.
1
Line to ground
85%
2
Line to line
  8%
3
Line to line to ground
  5%
4
3-phase
2% very rare

SHORT CIRCUIT CALCULATIONS (SYMMETRICAL FAULTS ONLY)
Most of the faults in power systems are due to short circuits which lead to a very heavy short circuiting current which may damage the equipments. Hence, it becomes necessary to determine the SC currents which enable us to determine the capacity of CB relays, CTs, etc.
The faults may be (1) Symmetrical, (2) Unsymmetrical.
1. Symmetrical Fault: In the system, if the short circuit currents are equal in different conductors, if the short circuit occurs in bothe the conductors of a single phase line or across three wires sin a 3-phase system, then the fault is a symmetrical fault. Current in all conductors are equal in magneitude and displaced by 1200.

2. Unsymmetrical fault: The fault in a 3-phase system which occurs across the two of the three-phases or between one or two-phases and earth causing unequal currnts in the conductors is called as an unsymmetrial fault. Our study is limited to calculations of SC currents in symmetrical faults only. The calculations become less laborious because of the balanced nature of fault. Only one phase need to be considered in calculations. The results of the other two will be same.
Note that most of the faults are unsymmetrical whereas the symmetrical faults are rare. Symmetrical faults are most severe and hence CB shall be of bulk capacity.
Take the case of a following fault.
                                                    

Say short circuit occurs at point ‘P’ in the power system. Current is inversely proportional to the impedance. So SC current is limited by impedance of the system up to the point of fault (at P). In this , the current limiting impedance is the impedance of generator plus impedance of transformer and the impedance of the line from G to P of the line. For calculating the SC current, we should know these impedances. The equipment like transformer, generator, reactors have the impedance mostly reactive whereas the lines, cables are resistive. When the total reactance in calculations exceeds 3-times the resistance, the resistance is usually negleced (as error in neglecting resistance is hardly 5%, if resistance is not considered.

Symbols Used in Representing a System.
Sn
Components
Symbols
1
Star connected generator with neutral solidly grounded.
         
2
Star connected generator with neutral grounded through resistance (R)
 
3
Star connected generator with neutral grounded through reactance coil (R)
         
4
Transformer
         
5
Current Transformer (CT)
Potential Transformer (PT)
         
6
Circuit breaker
         
7
Air-circuit breaker
         
8
Bus Bar
                         
9
Isolator
         
10
Earthing switch
         
11
Lightning arrestor
         
12
Fuse.






Single Line Diagram
A balanced 3-phase system is always solved as a single phase circuit consissting of one of the three lines and neutral return. Such simplified diagram of the system drawn to represent different components of a power system by standard symbols is called as a single line diagram. On the  diagram the information about loads, rating of the generator transformer and reactance of different components of the circuit is written. Braking capacity of CB is also written on the diagram.
See the following single line figure and its electric circuit of reactance figure below it.
                     
n the reactance diagram the compontne and their reactances are shown

Percentage Reactance:
For saving of time in calculations the reactance is expressed in percentage. This is defined as the percentage of the total phse dropped in the circuit when full load current is flowing.
%X = IX / V x 100
I = F.L. current in amphere
X = Reactance in Ω per phase
V = Phase voltage

& reactance can also be expressed in t4erms of kVA and kV as given below from the above
          (%X)V
X = -------------
         100 – 1
Simplifying i.e. multiplying numerator and denominator by V.

         % X. V. V             %X.(V/100) (V/100) x 100       %X.(Kv)2 X 10
X = ----------------   =    -------------------------------------  = ---------------------
100 I.V.             100 I (V/1000) X I                              Kva

             Kva.x
%X = -------------       Where, X is reactance in Ω.
                       10(kV)2
If only reactance is in the circuit (omitting resistance, capacitance etc). Then shor circuiting current,

           V                                               %X.V x 100
Isc  = -----  = I(100/%X) by putting x = ----------------   from eqn. (i), where I is full load current.
           X                                                       I
i.e. short circuiting is obtained by multiplying full load current with 100/%X.
It is seen that for calculations, use of %X rather than ohmic value as reactance makes calculation more quick and simple.
Base kVA: kVA ratings of different elements in the system are different. Percentage reactance depends on kVA rating of the equipment. It becomes necessary to find percentage reactance of all the elements on a common kVA rating. This kVA rating is known as Base kVa.
1.    Generally, base kVa is selected by sum of all kVAs of the system components .OR
2.    Highest kVa rating amongst the elements is taken as base kVa ratings. OR
3.    Any arbitrary value can be taken as base kVa. Generally, (ii) is taken as base kVa rating.
Therefore, % reactance at base k”Va = % reactance at rated kVA x Base kVA/Rated kVA.
Illustration 500 kVA transformer has %X = 5%, highest kVa equipment in the system is 1000 kVA. The
                                       100
% X at base kVa = 5 x -------  = 10%
                                       500
                                               

1.    Taking 2000 kVa as base kVA, Therefore, % reactance of Generateor same as 8%.

                                                            2000
So % reactance of transformer = 4 x -------- = 8% , Total %X on the common base = 8 + 8 = 16%.
                                                            1000
Full load current corresponding to 2000 kVA base.

KVa = 3. V.I./1000

     kVA X 1000     2000 x 1000
I = --------------- = ------------------- = 17.5 Amp
          √3.V            3 x 66 x 1000

              100       17.5 x 100
Isc = I x ------- = ---------------  = 109.36 Amp
              %X               16
2. Taking base kVa as 4000. Then,

                                     4000                                    4000
% X of generator = 8 x ------- = 16%, so % X = 4 x --------- = 16%
                                     2000                                     1000

Total of X = 16 + 16 = 32%
                                                                    4000 x 1000
F.L. current corresponding to 4000 kVa. = ----------------- = 35 Amp
                                                                                      √3 x 66 x 1000
             100            100
Isc = I x ----- = 35 x ------ = 109.36 same as in case (i)
             %X              32

Short Circuit kVA
The product of normal system voltage and the short circuiting current at the point of fault expressed in kVA is known as sshort circuit kVA.
Let         V = System normal voltage
              I = F.L. current in Amp. at base kVA
         %X = % reactance of the system on the base kVA up to the point of fault.
             100
Isc = I x -----
            % X

Now short circuit kVA for 3-phase circuit,

    3.V.Isc      3V            100       3 VI     100                         100
= ---------- = ------- x I x  ------  = ------- x ------ = Base kVA x -------
    1000        1000         % X       1000    % X                        % X


So  S.C. kVa = Base kVa x 100/%X

No comments:

Post a Comment