Tuesday, 8 September 2015

4.6.8 Silicone Oil-Filled Transformers. Silicone oils became more common when PCBs were discontinued. They are mainly used in transformers inside buildings and that are smaller than generator step-up transformers. Silicone oils have a higher fire point than mineral oils and, therefore, are used where fire concerns are more critical. As of this writing, there are no definitive published standards. IEEE has a guide and Doble has some service limits, but there are no standards. Information below is taken from the IEEE publication, from Doble, from articles, from IEC 60599 concepts, and from Delta X Research’s/Transformer Oil Analyst rules. Silicone oil dissolved gas analysis is in the beginning stages, and the suggested methods and limits below are subject to change as we gain more experience. However, in the absence of any other methods and limits, use the ones below as a beginning. Silicone oils used in transformers are polydimethylsiloxane fluids, which are different than mineral oils. Many of the gases generated by thermal and electrical faults are the same. The gases are generated in different proportions than with transformer mineral oils. Also, some fault gases have different solubilities in silicone oils than in mineral oils. Therefore, the same faults would produce different concentrations and different generation rates in silicone oils than mineral oils. As with mineral oil-filled transformers, three principal causes of gas generation are aging, thermal faults, and/or electrical faults resulting in deterioration of solid insulation and deterioration of silicone fluid. These faults have been discussed at length in prior sections and will not be discussed in great detail here. Overheating of silicone oils causes degradation of fluid and generation of gases. Gases generated depend on the amount of dissolved oxygen in the fluid, temperature, and how close bare copper conductors are to the heating. When a transformer is new, silicone oil will typically contain a lot of oxygen. Silicone transformers are typically sealed and pressurized with nitrogen. New silicone oil is not degassed; and, as a rule, oxygen concentration will be equivalent to oxygen solubility (maximum) in silicone. The silicone has been exposed to atmosphere for some time during manufacture of the transformer and manufacturer and storage of silicone oil itself. Therefore, carbon monoxide and carbon dioxide are easily formed and dissolved in the silicone due to the abundance of oxygen in the oil resulting from this atmospheric exposure. In normal new silicone transformers (no faults), both carbon monoxide and carbon dioxide will be generated in the initial years of operation. As the transformer ages and oxygen is depleted, generation of these gases slows and concentrations level off [25]. See figure 29 below for the relationship of decreasing oxygen and increasing carbon monoxide and carbon dioxide as a transformer ages. This curve is for general information only and should not be taken to represent any particular transformer. A real transformer with changes in loading, ambient temperatures, and various duty cycles would make these curves look totally different. After the transformer is older (assuming no faults have occurred), oxygen concentration will reach equilibrium (figure 29). Reaching equilibrium may take a few years depending on the size of the transformer, loading, ambient temperatures, etc. After this time, oxygen, carbon monoxide, and Figure 29.—Relationship of Oxygen to Carboncarbon dioxide Dioxide and Carbon Monoxide as Transformer Ages. level off and the rate of production of these gases from normal aging should be relatively constant. If generation rates of these gases change greatly (seen from the DGA), a fault has occurred, either thermal or electrical. Rate of generation of these gases and amounts can be used to roughly determine what the fault is. Once you notice an significant increase in rate of generation of any gas, it is a good idea to subtract the amount of gas that was already in the transformer before this increase. This ensures that gases used in the diagnosis are only gases that were generated after the fault began. Carbon monoxide will be a lot higher in a silicone transformer than a mineral oil-filled one. The difficulty is in trying to determine what is producing the CO; is it coming from normal aging of oil or from deterioration of paper from a fault condition. The only solution is a furan analysis. If the CO content is greater than the IEEE limit of 3,000 ppm [26], and the generation rate G1 is met or exceeded, a furan analysis is recommended with the annual DGA. If a thermal fault is occurring and is producing CO and small amounts of methane and hydrogen, the fault may be masked by the normal production of CO from the silicone oil itself. If the CO generation rate has greatly increased, along with other gases, it becomes obvious that a fault has occurred. The furan analysis can only tell you if the paper is involved (being heated) in the fault. Some general conclusions can be drawn by comparing silicone oil and mineral oil transformers. 1. All silicone oil filled transformers will have a great deal more CO than normal mineral oil filled transformers. CO can come from two sources, the oil itself and from degradation of paper insulation. If the DGA shows little other fault in gas generation besides CO, the only way to tell for certain if CO is coming from paper degradation (a fault) is to run a furan analysis with the DGA. If other fault gases are also being generated in significant amounts, in addition to CO, obviously there is a fault, and CO is coming from paper degradation. 2. There will generally be more hydrogen present than in a mineral oil-filled transformer. 3. Due to “fault masking,” mentioned above, it is almost impossible to diagnose what is going on inside a silicone filled transformer based solely on DGA. One exception is if acetylene is being generated, there is an active arc. You must also look at gas generation rates and operating history. Look at loading history, through faults, and other incidents. It is imperative that detailed records of silicone oil filled transformers be carefully kept up-to-date. These are invaluable when a problem is encountered. 4. If acetylene is being generated in any amount, there is a definitely an active electrical arc. The transformer should be removed from service. 5. In general, oxygen in a silicone-filled transformer comes from atmospheric leaks or was present in the transformer oil when it was new. This oxygen is consumed as CO and CO2 are formed from the normal heating from operation of the transformer. 6. Once the transformer has matured and the oxygen has leveled off and remained relatively constant for two or more DGA samples, if you see a sudden increase in oxygen, and perhaps carbon dioxide and nitrogen, the transformer has developed a leak. In table 14 below are IEEE limits [26], compared with Doble [25] in a study of 299 operating transformers. The table of gases from the Doble study seems more realistic. They show gas level average of 95% of transformers in the study. Note, with the last four gases, limits given by the IEEE (trial use guide) run over 70% higher than the Doble 95% norms. But with the first three gases, hydrogen, methane, and ethane, the IEEE limits are well below the amount of gas found in 95% norms in the Doble study. We obviously cannot have limits that are below the amount of gas found in normal operating transformers. Therefore, it is suggested that we use the Doble (95% norm) limits. The 95% norm limit means that 95% of the silicone oil transformers studied had gas levels below these limits. Obviously, 5% had gases higher than these limits. These are problem transformers that we should pay more attention to. Table 14.—Comparison of Gas Limits Gas Doble 95% Norm IEEE Limits Hydrogen 511 200 Methane 134 100 Ethane 26 30 Ethylene 17 30 Acetylene 0.6 1 CO 1,749 3,000 CO2 15,485 30,000 Total Combustibles 2,024 3,360 In table 15, the IEEE limits for L1 were chosen. For L2 limits, a statistical analysis was applied, and two standard deviations were added to L1 to obtain L2. For L3 limits, the L1 limits were doubled. Gas generation rate limits G1 are 10% of L1 limits per month. G2 generation rate limits are 50% of L1 limits per month. These basic concepts were taken from IEC 60599 [12], for mineral oil transformers and applied to silicone oil transformers due to absence of any other criteria. As our experience grows in silicone DGA, these may have to be changed, but they will be used in the beginning. Limits L1, L2, and L3 represent the concentration in individual gases in ppm. G1 and G2 represents generation rates of individual gases in ppm per month. To obtain G1 and G2 in ppm per day divide the per month numbers by 30. Except for acetylene, G1 is 10% of L1 and G2 is 50% of L1. The generation rates (G1, G2), are points where our level of concern should increase, especially when considered with the L1, L2, and L3 limits. At G2 generation rate, we should be extremely concerned and reduce the DGA sampling interval accordingly, and perhaps plan an outage, etc. Except for acetylene, generation rate levels G1 and G2 were taken from IEC 60599 reference [12] which is used with mineral oil transformers. Any amount of ongoing acetylene generation means active arcing inside the transformer. In this case, the transformer should be removed from service. These criteria were chosen because of an absence of any other criteria. As dissolved gas analysis criteria for silicone oils becomes better known and quantified table 15 will change to reflect new information. As with mineral oil-filled transformers, gas generation rates are much more important that the amount of gas present. Total accumulated gas depends a lot on age (an older transformer has more gas). If the rate of generation of any combustible gas shows a sudden increase in the DGA, take another oil sample immediately to confirm the gas generation rate increase. If the second DGA confirms a generation rate increase, get some outside advice. Be careful; gas generation rates increase somewhat with temperature variations caused by increased loading and summer ambient temperatures. However, higher operating temperatures are also the most likely conditions for a fault to occur. The real question is has the increased gas generation rate been caused by a fault or increased temperature from greater loading or higher ambient temperature? If gas generation rates are fairly constant (no big increases and less than G1 limits above), what do we do if a transformer exceeds the L1 limits? We begin to pay more attention to that transformer, just as we do with a mineral oil transformer. We may shorten the DGA sampling interval, reduce loading, check transformer cooling, get some outside advice, etc. As with mineral oil transformers, age exerts a big influence in accumulated gas. We should be much more concerned if a 3-year old transformer which has exceeded the L1 limits than if a 30-year old transformer exceeds the limits. However, if G1 generation rates are exceeded in either an old or new transformer, we should step up our level of concern. If accumulated gas exceeds the L2 limit, we may plan to have the transformer degassed. Examine the physical tests in the DGAs and compare them to the Doble/IEEE table (table 16) (Reference Book on Insulating Liquids and Gasses) [23]. The oil should be treated in whatever manner is appropriate if these limits are exceeded. If both L1 limits and G1 limits are exceeded, we should become more concerned. Reduce sampling intervals, get outside advice, reduce loading, check transformer cooling and oil levels, etc. If G2 generation limits are exceeded, we should be extremely concerned. It will not be long before L3 limits are exceeded, and consideration must be given to removing the transformer from service, for testing, repair, or replacement. If acetylene is being generated, the transformer should be taken out of service. However as with mineral oil transformers, a one-time nearby lightning strike or through fault can cause a “one-time” generation of acetylene. If you notice acetylene in the DGA, immediately take another sample. If the amount of acetylene is increasing, an active electrical arc is present within the transformer. It should be taken out of service. If you have a critical silicone (or mineral oil-filled transformer), such as a single station service transformer, or excitation transformer, you should find out if a spare is available at another facility or from Western Area Power Administration or Bonneville Power. If there are no other possible spares consider beginning the budget process for getting a spare transformer. Table 16 lists test limits for service-aged silicone filled transformer oil. If any of these limits are exceeded, it is suggested that the oil be treated in whatever manner is appropriate to return the oil to serviceable condition. Table 16.—Doble and IEEE Physical Test Limits for Service-Aged Silicone Fluid Test Acceptable Limits Unacceptable Values Indicate ASTM Test Method Visual Clear free of particles Particulates, free water D 1524 D 2129 Dielectric breakdown voltage 30 kV Particulates, dissolved water D 877 Water content maximum 70 ppm (Doble) 100 ppm (IEEE) Dissolved water contamination D 1533 Power factor max. at 25 °C 0.2 Polar/ionic contamination D 924 Viscosity at 25 °C, cSt 47.5–52.5 Fluid degradation contamination D 44 Acid neutralization number max, mg KOH/gm 0.1 (Doble) 0.2 (IEEE) Degradation of cellulose or contamination D 974 Note: If only one number appears, both Doble and IEEE have the same limit. If the above limits are exceeded in the DGA, the silicone oil should be filtered, dried or treated to correct the specific problem.

1 comment:

  1. Getting to know that silicone oils are better than mineral oils, and since they have become popular over time after PCBs were discontinued, it is important to consider the limits and procedures are provided by the manufacture because they are already tested. I never knew the PCBs were discontinued because I don't engage much with transformers, but I guess the next time it's being serviced, I will be eyes open.

    Abraham Yates @ Apache Oil Company

    ReplyDelete