4.5 Moisture Problems
Moisture, especially in the presence of oxygen, is extremely hazardous to transformer insulation. Each DGA and Doble test result should be examined carefully to see if water is increasing and to determine the moisture by dry weight (M/DW) or percent saturation that is in the paper insulation. When 2% M/DW is reached, plans should be made for a dry out. Never allow the M/DW to go above 2.5% in the paper or 30% oil saturation without drying out the transformer. Each time the moisture is doubled in a transformer, the life of the insulation is cut by one-half. Keep in mind that the life of the transformer is the life of the paper, and the purpose of the paper is to keep out moisture and oxygen. For service-aged transformers rated less than 69 kV, results of up to 35 ppm are considered acceptable. For 69 kV through 288 kV, the DGA test result of 25 ppm is considered acceptable. For greater than 288 kV, moisture should not exceed 20 ppm. However, the use of absolute values for water does not always guarantee safe conditions, and the percent by dry weight should be determined. See table 12, “Doble Limits for In-Service Oils,” in section 4.6.5. If values are higher, the oil should be processed. If the transformer is kept as dry and free of oxygen as possible, transformer life will be extended.
Reclamation specifies that manufacturers dry new transformers to no more than 0.5% M/DW during commissioning. In a transformer having 10,000 pounds of paper insulation, this means that 10,000 x 0.005 = 50 pounds of water (about 6 gallons) is in the paper. This is not enough moisture to be detrimental to electrical integrity. When the transformer is new, this water is distributed equally through the transformer. It is extremely important to remove as much water as possible.
Fault Examples
Partial discharges Discharges in gas-filled cavities in insulation, resulting from incomplete impregnation, high moisture in paper, gas in oil supersaturation or cavitation, (gas bubbles in oil) leading to X wax formation on paper.
Discharges of low energy
Sparking or arcing between bad connections of different floating potential, from shielding rings, toroids, adjacent discs or conductors of different windings, broken brazing, closed loops in the core. Additional core grounds. Discharges between clamping parts, bushing and tank, high voltage and ground, within windings. Tracking in wood blocks, glue of insulating beam, winding spacers. Dielectric breakdown of oil, load tap changer breaking contact.
Discharges of high energy
Flashover, tracking or arcing of high local energy or with power follow-through. Short circuits between low voltage and ground, connectors, windings, bushings, and tank, windings and core, copper bus and tank, in oil duct. Closed loops between two adjacent conductors around the main magnetic flux, insulated bolts of core, metal rings holding core legs.
Overheating less than 300 °C
Overloading the transformer in emergency situations. Blocked or restricted oil flow in windings. Other cooling problem, pumps valves, etc. See the “Cooling” section in this document. Stray flux in damping beams of yoke. Overheating 300 to 700 °C
Defective contacts at bolted connections (especially busbar), contacts within tap changer, connections between cable and draw-rod of bushings. Circulating currents between yoke clamps and bolts, clamps and laminations, in ground wiring, bad welds or clamps in magnetic shields. Abraded insulation between adjacent parallel conductors in windings.
Overheating over 700 °C
Large circulating currents in tank and core. Minor currents in tank walls created by high uncompensated magnetic field. Shorted core laminations.
Notes: 1. X wax formation comes from Paraffinic oils (paraffin based). These are not used in transformers at present in the United States but are predominate in Europe. 2. The last overheating problem in the table says �over 700 °C.” Recent laboratory discoveries have found that acetylene can be produced in trace amounts at 500 °C, which is not reflected in this table. We have several transformers that show trace amounts of acetylene that are probably not active arcing but are the result of high- temperature thermal faults as in the example. It may also be the result of one arc, due to a nearby lightning strike or voltage surge. 3. A bad connection at the bottom of a bushing can be confirmed by comparing infrared scans of the top of the bushing with a sister bushing. When loaded, heat from a poor connection at the bottom will migrate to the top of the bushing, which will display a markedly higher temperature. If the top connection is checked and found tight, the problem is probably a bad connection at the bottom of the bushing.
When the transformer is energized, water begins to migrate to the coolest part of the transformer and the site of the greatest electrical stress. This location is normally the insulation in the lower one-third of the winding [5]. Paper insulation has a much greater affinity for water than does the oil. The water will distribute itself unequally, with much more water being in the paper than in the oil. The paper will partially dry the oil by absorbing water out of the oil. Temperature is also a big factor in how the water distributes itself between the oil and paper. See table 11 below for comparison.
Temperature Water Water (degrees C) in Oil in Paper
20° 1 3,000 times what is in the oil
40° 1 1,000 times what is in the oil
60° 1 300 times what is in the oil
The table above shows the tremendous attraction that paper insulation has for water. The ppm of water in oil shown in the DGA is only a small part of the water in the transformer. It is important that, when an oil sample is taken, you record the oil temperature from the top oil temperature gage.
Some laboratories give percent M/DW of the insulation in the DGA. Others give percent oil saturation, and some give only the ppm of water in the oil. If you have an accurate temperature of the oil and the ppm of water, the Nomograph (figure 23, section 4.5.2) will give percent M/DW of the insulation and the percent oil saturation.
Where does the water come from? Moisture can be in the insulation when it is delivered from the factory. If the transformer is opened for inspection, the insulation can absorb moisture from the atmosphere. If there is a leak, moisture can enter in the form of water or humidity in air. Moisture is also formed by the degradation of insulation as the transformer ages. Most water penetration is flow of wet air or rain water through poor gasket seals due to pressure difference caused by transformer cooling. During rain or snow, if a transformer is removed from service, some transformer designs cool rapidly and the pressure inside drops. The most common moisture ingress points are gaskets between bushing bottoms and the transformer top and the pressure relief device gasket. Small oil leaks, especially in the oil cooling piping, will also allow moisture ingress. With rapid cooling and the resultant pressure drop, relatively large amounts of water and water vapor can be pumped into the transformer in a short time. It is important to repair small oil leaks; the small amount of visible oil is not important in itself, but it also indicates a point where moisture will enter [22].
It is critical for life extension to keep transformers as dry and as free of oxygen as possible. Moisture and oxygen cause the paper insulation to decay much faster than normal and form acids, sludge, and more moisture. Sludge settles on windings and inside the structure, causing transformer cooling to be less efficient, and slowly over time temperature rises. (This was discussed earlier in “3. Transformer Cooling Methods.”) Acids cause an increase in the rate of decay, which forms more acid, sludge, and moisture at a faster rate [20]. This is a vicious cycle of increasing speed forming more acid and causing more decay. The answer is to keep the transformer as dry as possible and as free of oxygen as possible. In addition, oxygen inhibitor should be watched in the DGA testing. The transformer oil should be dried when moisture reaches the values according to table 12. Inhibitor should be added (0.3% by weight ASTM D-3787) when the oil is processed.
Water can exist in a transformer in five forms.
1. Free water, at the bottom of the tank.
2. Ice at the tank bottom (if the oil specific gravity is greater than 0.9, ice can float).
3. Water can be in the form of a water/oil emulsion.
4. Water can be dissolved in the oil and is given in ppm in the DGA.
5. Water can be in the form of humidity if transformers have an inert gas blanket.
Free water causes few problems with dielectric strength of oil; however, it should be drained as soon as possible. Having a water- oil interface allows oil to dissolve water and transport it to the insulation. Problems with moisture in insulation were discussed above. If the transformer is out of service in winter, water can freeze. If oil specific gravity is greater than 0.9 (ice specific gravity), ice will float. This can cause transformer failure if the transformer is energized with floating ice inside. This is one reason that DGA laboratories test specific gravity of transformer oil.
The amount of moisture that can be dissolved in oil increases with temperature. (See figure 19.) This is why hot oil is used to dryout a transformer. A water/oil emulsion can be formed by purifying oil at Figure 19.—Maximum Amount of Water too high temperature. When the oil Dissolved in Mineral Oil Versus Temperature. cools, dissolved moisture forms an emulsion [20]. A water/oil emulsion causes drastic reduction in dielectric strength.
How much moisture in insulation is too much? When the insulation gets to 2.5% M/DW or 30% oil saturation (given on some DGAs), the transformer should have a dry out with vacuum if the tank is rated for vacuum. If the transformer is old, pulling a vacuum can do more harm than good. In this case, it is better to do round-the-clock re circulation with a Bowser drying the oil as much as possible, which will pull water out of the paper. At 2.5% M/DW, the paper insulation is degrading much faster than normal [5]. As the paper is degraded, more water is produced from the decay products, and the transformer becomes even wetter and decays even faster. When a transformer gets above 4% M/DW, it is in danger of flashover if the temperature rises to 90 °C.
4.5.1 Dissolved Moisture in Transformer Oil. Moisture is given in the dissolved gas analysis in ppm, and some laboratories also give percent saturation. Percent saturation means percent saturation of water in the oil. This is a percentage of how much water is in the oil compared with the maximum amount of water the oil can hold. In figure 19, it can be seen that the amount of water the oil can dissolve is greatly dependent on temperature. The curves (figure 20) below are percent saturation curves. On the left line, find the ppm of water from your DGA. From this point, draw a horizontal with a straight edge. From the oil temperature, draw a vertical line. At the point where the lines intersect, read the percent saturation curve. If the point falls between two saturation curves, estimate the percent saturation based on where the point is located. For example, if the water is 30 ppm and the temperature is 40 °C, you can see on the curves that this point of intersection falls about halfway between the 20% curve and the 30% curve. This means that the oil is approximately 25% saturated.
Caution: Below 30 °C, the curves are not very accurate.
4.5.2 Moisture in Transformer Insulation. The illustration at right (figure 21) shows how moisture is distributed throughout transformer insulation. Notice that the moisture is distributed according to temperature, with most moisture at the bottom and less as temperature increases toward the top. In this example, there is almost twice the moisture near bottom as there is at the top. Most service-aged transformers fail in the lower one-third of the windings, which is the area of most moisture. It is also the area of most electrical stress. Moisture and oxygen are two of the transformer’s worst enemies. It is very important to keep the insulation and oil as dry as possible and as free of oxygen as possible.
Failures due to moisture are the most common cause of transformer failures [5]. Without an accurate oil temperature, it is impossible for laboratories to provide accurate information about the M/DW or percent saturation. It will also be impossible for you to calculate this information accurately.
Experts disagree on how to tell how much moisture is in the insulation based on how much moisture is in the oil (ppm). At best, methods to determine moisture in the insulation based solely on DGA are inaccurate. The methods discussed below to determine moisture in the insulation are approximations and no decision should be made based on one DGA. However, keep in mind that the life of the transformer is the life of the insulation. The insulation is quickly degraded by excess moisture and the presence of oxygen. Base any decisions on several DGAs over a period of time and establish a trend of increasing moisture.
If the lab does not provide the percent M/DW, IEEE 62-1995 [19] gives a method. From the curve (figure 22), find temperature of the bottom oil sample and add 5 °C. Do not use the top oil temperature. This approximates temperature of the bottom third (coolest part) of the winding, where most of the water is located. From this temperature, move up vertically to the curve. From this point on the curve, move horizontally to the left and find the Myers Multiplier number. Take this number and multiply the ppm of water shown on the DGA. The result is percent M/DW in the upper part of the insulation. This method gives less amount of water than the General Electric nomograph on the following page.
This nomograph, published by General Electric in 1974 (figure 23), gives the percent saturation of oil and percent M/DW of insulation. Use the nomograph to check yourself after you have completed the method illustrated in figure 22. The nomograph in figure 23 will show more moisture than the IEEE method.
The curves in figure 23 are useful to help understand relationships between temperature, percent saturation of the oil, and percent M/DW of the insulation. For example, pick a point on the ppm water line, say 10 ppm. Place a straight edge on that point and pick a point on the temperature line, say 45 °C. Read the percent saturation and percent M/DW on the center lines. In this example, percent saturation is about 6.5% and the % M/DW is about 1.5%. Now, hold the 10 ppm point and move the sample temperature upward (cooler), and notice how quickly the moisture numbers increase. For example, use 20 °C and read the % saturation of oil at about 18.5% and the % M/DW at about 3.75%. The cooler the oil, the higher the moisture percentage for the same ppm of water in the oil.
Do not make a decision on dryout based on only one DGA and one calculation; it should be based on trends over a period of time. Take additional samples and send them for analysis. Take extra care to make sure the oil temperature is correct. You can see by the nomograph that moisture content varies dramatically with temperature. Take extra care that the sample is not exposed to air. If after using the more conservative IEEE method and again subsequent samples show M/DW is 2.5% or more and the oil is 30% saturated or more, the transformer should be dried as soon as possible. Check the nomograph and curves above to determine the percent saturation of the oil. The insulation is degrading much faster than normal due to the high moisture content. Drying can be an expensive process; it is prudent to consult with others before making a final decision to do dryout. However, it is much less expensive to perform a dryout than to allow a transformer to degrade faster than normal, substantially shortening transformer life.
No comments:
Post a Comment