1. CONDENSED INSTRUCTIONS: LEAD-ACID BATTERIES
E1.1 PURPOSE
The
purpose of this section is to outline the duties and responsibilities for
routine operation and care of vented lead-acid batteries. Section 2 contains
detailed information on lead-acid battery principles.
11..22
BATTERY CHARGING AND SPECIFIC GRAVITY TEMPERATURE CORRECTION BATTERY CHARGING
AND SPECIFIC GRAVITY TEMPERATURE CORRECTION
AA..
Initial Freshening Charge Initial Freshening Charge
To
establish a reference, give each new battery, or reinstalled battery stored for
more than 3 months, an initial freshening charge. Use the equalizing voltage
given by the manufacturer for the type cell, but do not exceed the maximum
voltage of other loads connected to the charger. Apply this charge until each
cell gasses freely and equally and specific gravity (sp.gr.) stops rising. Just
before the end of the initial charge, record the voltage of each cell. About 20
minutes after the end of the charge, record the specific gravity of each cell,
corrected to 77 EF. For every 3 EF above 77EF, add one point (0.001) to the
reading. For every 3 EF below 77EF, subtract one point (0.001) from the
reading. Use form POM-133A for these records and keep them for the life of the
battery.
—ell.C.1
PilotA A.1 Pilot Cell.—After the initial charge or to begin a yearly cycle,
choose a pilot cell from one of the lowest specific gravity and lowest voltage
cells. This cell is used as a representative for readings, for one year. Each
year a new pilot cell is chosen.
eB.
Float Charg. B Float Charge
Charge
batteries continuously at the float voltage recommended by the manufacturer.
Monthly y take the voltage across the overall battery terminals with an
accurate digital meter and compare this reading with the charger and bus
voltmeters. If needed, adjust the charger float voltage based on the digital
meter. Adjust the charger and/or bus voltmeters to agree with the digital meter
if needed.
A
battery is said to float when charging voltage is slightly greater than the
open circuit voltage of the battery. Floating current required to keep lead-
calcium cells at full charge is about one-fourth to one-third that of lead-
antimony cells, but lead-calcium cells usually must be floated at a slightly
higher voltage. Lead-selenium cells require float voltages slightly above those
of lead-calcium.
The operation
of a battery by float method is based on overall voltage applied to the battery
terminals. The voltmeter used must be very accurate. An inaccurate meter can
result in either over or undercharge and resulting problems, which reduce life
and service of the battery. See section 1.3.
DD.. Unattended Stations
The
equalizing charge may be terminated automatically by a timer. Use the
manufacturer’s recommended charge time for the cell type. Set the timer to
switch off the equalizing charge and to reconnect the float charge. In the
event that the manufacturer does not provide a recommended charge time, 3 days
(72 hours) may be used as the charge time.
A
"check charge" for batteries at unattended locations may be used to
determine if equalization is necessary. With a "check charge,” the battery
is placed on charge at the equalizing rate. After allowing 15 or 20 minutes for
the rate to stabilize, the voltages of individual cells are measured. If the
highest and lowest cell voltages (while on charge at the equalizing rate)
differ by no more than 0.04 volt, the battery does not require equalizing. The
battery should be equalized if the voltage differences exceed 0.04 volt. Use a
digital meter accurate to 0.01 volt. The test described above is effective in
determining equality of cell charge. However, the test cannot be substituted
for a hydrometer in determining state of charge. All cells must be within 5°F,
the reason is described in paragraph 2.6, and the temperature must not be below
55 °F.
1.3.
VOLTAGE READINGSVOLTAGE READINGS
Voltage
readings should be taken in accordance with the following instructions. NNote:
Accurate voltmeters are critical for extending battery life. Provide a digital
voltmeter accurate to 0.01 volt reserved only for station battery duty and
calibrate it or send it out for calibration at least once a year. This
voltmeter must be treated with extra care; do not use a shop meter or
electrician’s general-use meter for battery voltages.
A. Each shift(Attendend Stations) or During routine inspections(Unattended Stations)
Check
the voltmeter on the control panel to determine if the battery is being charged
at the proper voltage. Adjust the battery charging voltage if necessary.
B.
Whe Tapps are changed
Check
the voltage on the control panel when taps are changed on power or
station-service transformers. Adjust the battery charging voltage if necessary.
C. During equilizing charge
Just
before terminating the equalizing charge, measure the voltages of the highest
voltage cell and the lowest voltage cell of the battery to the nearest 0.01
volt with an accurate digital voltmeter. The equalizing charge should be
continued if the voltage difference between the two cells is more than that
recorded for the initial charge.
Rev.12/31/97
5
D.
Monthly
With
the charger in service, check the overall float voltage across the battery
terminals with an accurate digital meter and record on form POM-133A.
E.
Monthly
Check
the pilot cell float voltage with an accurate digital voltmeter and record on
form POM-133A.
F.
Quaterly
Check
the float voltage on all individual cells to the nearest 0.01 volt with an
accurate digital voltmeter. Take these readings as rapidly as possible and
record them on form POM-133A. At the end of the yearly cycle, use these
readings to determine the pilot cells for the next year.
1.4 SPECIFIC GRAVITY READINGS
Specific
gravity readings of vented lead-acid batteries must be taken in accordance with
the following instructions. Note: All specific gravity readings must be corrected
to 77EF before recording (see 2.18). Do not attempt to take any specific
gravity reading after adding water to a cell. The electrolyte takes several
hours to mix after water is added.
A.
Monthly
Take
the specific gravity reading of the pilot cell and record it on form POM 133A.
B.
Quarterly
Take
specific gravity readings of 10 percent of the total number of cells and record
them on form POM-133A. Rotate these cells so that readings are taken on
different cells each quarter.
C.
Annualy
Take
specific gravity readings of every cell and record them on form POM 133A.
D.
After equilizing charge
About
15 minutes after heavy gassing stops, take the specific gravity readings of
every cell and record them on form POM-133A. If two cells with the lowest
specific gravity (checked over the last one-eighth of the charging period) have
not stopped rising, continue the equalizing charge.
Rev.12/31/97
6
1.5 TEMPERATURE READINGS
All
cells of a battery should be at the same ambient temperature. Heat sources such
as sunlight, portable heaters, etc. must be blocked so they do not raise the
temperature of individual cells. Record the room ambient temperature before
cell temperatures are taken.
Note:
An accurate infrared (IR) camera may be used for temperatures; however, the
camera calibration must be checked at least once each year. If possible, take
the annual temperature readings of the cells just after camera calibration. If
the temperature spread of the cells exceeds 5 °F (i.e., upper rows are warmer)
the room ventilation may be inadequate.
A.
Monthly
Record
the pilot cell temperatures on form POM-133A.
B.
Quarterly
Record
temperature readings of 10 percent of all the cells; rotate the subject cells
each quarter.
CC..
Annually
If
an accurate IR camera is available, take the temperature of the battery
connections during a load or discharge test, i.e., while current is flowing. If
one or more of the connections are loose or dirty, their temperatures will be
higher than the other connections.
1.6 CONNECTION RESISTANCE READINGS
A..
After Installation
Using
an accurate micro-ohm meter, record the resistance of each connection on form
POM-134A. The readings should be on the order of a few micro-ohms (less than
100). Record the readings as a baseline on form POM-134A. For additional
information see IEEE 450-1995—Maintenance, Testing , and Replacement of Vented
Lead-acid Batteries, Annex D and F. See below for detailed instructions.
B..
Annually
Repeat
resistance checks of the connections checked in step A above and compare
values. If any connection resistance has increased more than 20 percent, clean,
apply no-ox grease, retorque the connections, and retest. Fill out both “as
found” and “as left” columns on form POM-134A.
Rev.12/31/97
7
Figure
2. - Placement of meter probes for connection resistance measurements.
Caution:
Never place probes across a cell or cells (between positive and negative
posts), with the meter set on ohms. The meter may be destroyed and arcing may
occur at the battery.
1. Make sure the battery is on float
charge before beginning the readings. Obtain an accurate digital
micro-ohmmeter, and set it to the lowest scale.
2. On cell No. 1 take the first reading
between the connector lug and the first post (see fig. 2). This reading will be
the resistance between the post and connector lug and will be about one-half
the middle readings. Record all readings on form POM-134A.
3. Take the second reading between
opposite polarity posts (not connectors) of cells No. 1 and No. 2. Following
readings will be between positive and
negative
posts of adjacent cells. These middle readings will include the
resistance
of two connections (one on each post) and the intercell
lead(see
fig. 2). These readings will be about double the first and last.
4. Take the remaining middle readings
as in step 4, proceeding from cell to cell.
5. Take the last reading between the
last post on the last cell and the connector lug as shown.
6. If high resistance is found, take
readings from each post to its connector to determine which of the two
connections is bad. Mark this and all high-resistance connections for later
repair.
7. After readings are complete,
disconnect the charger and loads from the battery. Caution: do not remove or
make connections while current is flowing. Clean problem connections, retorque
to manufacturer’s specifications, and apply no-ox grease. Retest the repaired
connections and record the resistance in the “as-left” column on form POM-134A.
No comments:
Post a Comment