VFD
(VARIABLE FREQUENCY DRIVE)
Component No. 1:Six pulse
rectifier: Converts the 3 ph AC voltage into DC voltage
Component No. 2: Capacitor
bank : Energy storage which stabilizes the intermediate ckt DC voltage
Component No. 3: Six pulse
IGMT inverter: Converts the DC V to ACV & vice versa. Motor operation is controlled by switching the IGMTS.
Component No. 4: Motor
control: The motor control is based on direct torque control (DTC) method. Two
phase currents & DC link voltage are measured and used for the control; the
third phase current is measured for earth fault protection.
Ø How VFD is used as a
Energy saving?
Because
of it reduces the motor speed as per demand. When the speed is reduced he power
consumption will also reduces. Eg. Power = (Speed)3.
Ø What happens when DC
supply is given to AC motor?
No
rotating magnetic field will be generated & hence the motor will not
rotate.. No back emf will be generated. Reactance will not com as frequency is
zero. Rotor impedance will remain isolated from equivalent circuit of stator.
Only resistance of stator circuit (which is very low) will be there. Hence
stator current will be very high so motor will burn.
Ø What will happen if AC
power supply is given to the rotor of an alternator?
Excitation
AC current is constant. The rotor will be rotated by a motor or turbine. It
will cause emf induced in the rotor. If we give AC supply to the rotor, the
flux will be variable & cause emf induced in the stator & it will act
as a motor.
Ø What is the effect of PF
on the size of alternator?
If
PF is less, KVA rating on the generator will be more. Because KW= KVA/PF. If PF
reduces, KVA rating goes up for the same KW rating. So generator size will be
more than the normal. For low PF, current will also high and increase in losses
at all stages.
Ø What is the major
difference between PT & CVT?
PT
is inductive step down transformer used for measurement of voltage &
protection. Where a CVT is capacitive voltage transformer, consisting a stock
of series connecting capacitor. The voltage across the capacitor is used to
measure the voltage. It also serves the purpose of power line carrier
communication.
Ø Why ACB is not used in
place VCB at high transmission system?
VCB
means vacuum at higher potential. There is a change of ionization of air
molecules but if it is vacuum. Without a vacuum there will not be any change of
ionization of air molecules. Vacuum has a high arc quenching property compared
to air. Its dielectric strength is equal to 8 times of air. VCB works on zero natural current principal.
Ø Why layers of charcoal
& salt are used in Earth pits?
The
layers of charcoal & salt helps to maintain low resistance for earth fault
current because of ionic behavior of salt & charcoal. They will maintain
moisture around the earth pit.
Ø How % impedance affect on
the size of the power transformer?
%
impedance is used to determine the max. fault current. The Transformer is
capable of delivering to a down stream short circuit current.
Fault
current = FLC x 100/% Imp. Fault current is also named as MVA.
Fault
MVA = 1.73 x Fault current x V
Ø What is our max demand/
3500KVA
Ø Total connected Load?
4250
KW
Ø What will happen if MD
exceeds & what will you do?
I f
MD exceeds, we have to pay penalty. To avoid this we will cut our unwanted
load,
Ø In how much time MD is
changed in meter?
Max.
in 6 minutes
Ø In substation, what are
the merits for human safety?
1.
Remote control panel
2.
Insulation mat in front of panel
3.
Insulated tools & meters
4.
Electrical safety shoe, HT gloves, face screen etc
5.
Fire extinguishers.
Ø When we are using 433V
supply, why 33Kv supply is taken from MSEB?
By
increasing voltage, we have minimized the current due to following advantages:
1.
Due to minimized current, cable size & area is decreased.
2.
Range of switching capacity is also decreased.
3.
Saving money.
Ø Types of CT?
1.
Metering CT, 2. Protection CT.
Ø Difference between
Metering CT & Protection CT?
Metering CT is connected on Load
current and protection CT is connected on Fault Current. Fault current is
always more. So metering CT will not work on Protection CT but protection CT
will work on Metering CT but accuracy will not be there. Saturation current of
Metering CT is low & that of Protection CT is high. Saturation current is
depend upon the material of core.
Ø How Earthing is checked?
By
earth tester or by test lamp, keeping between phase & earth.
Ø How much the earth
resistance?
It
should be between 0.5 ohm to 1 ohm
Ø What will do if earth
resistance is 3 ohm? And what will you do?
Solution of salt is to be
added in earth pit. Still it is not decreasing we will provide parallel
earthing.