STAR-DELTA
STARTER
It is simple mechanical switch
connects the stator to the supply in star on ‘start’ position. When he motor
reaches near synchronous speed, the handle is taken to ‘run’ position. The
stator connections area then changed to delta. Thus at start 1/√3 times live
voltage is applied per phase and the currents area correspondingly reduced. In
‘run’ position, the rated line voltage is restored per phase. The starter also
has mechanical locking arrangement, no volt, and over load releases. When the
motor is over loaded the over load relay operates and NC contact is opened and
contactors are opened and motor stops and hence protected from over loading.
STARTER
FOR SLIP RING MOTOR
Rotor
Resistance Starter:
Three equal resistances in the form of a circular arrangement are connected in
the rotor circuit. ?These are cut out progressively as three variable contacts
move over the studs as the handle is moved from ‘start’ to ‘run’ position. The
rotor resistance is maximum (the current minimum) at ‘start’ and progressively
reduced till ‘run’ position. A switch is
provided which disconnects the motor phase from supply if the stator handle is
not brought back to ‘start’ position. This prevents starting the motor on ‘Run’
position. Usual protections are provided against no voltage and over load on
stator side switch by over load relay.
STARTER FOR BOTH TYPES OF
MOTORS
Push
button/Direct On-line Starter: The starter has a magnetic coil ‘A’ wound on the
attracted armature type of relay. When a ‘ON’ button is pressed it gets energized
and the armature ‘B’ is attracted. The set of contacts ‘C’ in the contactor are
made ‘ON’. The auxiliary contact at the bottom enables the coil to remain in
the circuit even if the button ‘ON’ is released. The motor is thus started
through the bimetallic strips ‘D’. If the supply fails the coil releases the
armature due to lack of excitation and gravitational pull and the motor is
disconnected from supply. If the motor is over loaded the strip ‘D’ bend
downwards to release ‘NO’ contact is made open and in both cases the motor
stops as the armature is released due to incomplete circuit of the coil ‘A’.
The contact E can be ‘reset’ through ‘OFF’ button before restoring the motor.
SINGLE PHASING PREVENTER
Main parts of circuit: (i) Control
coil, (ii) Negative sequence filter, (iii) Contactors, (iv) Normally closed NC
contacts, (v) Normally open NO contact, (vi) C.T.S., (vii) Thermal relay.
The preventive circuit is connected in
secondary’s of C.T. and R.Y.B. lines act as primaries of the CT. The negative
sequence filter is shown connected. The output of this filter is fed to a leel detector.
This sends the tripping command to the starter and NC contact gets opened and
contactors get opened, stopping the motor as it is disconnected from the supply
R.Y.B. This type of preventer is generally used for small/medium capacity
motors.
EXERCISE
1.
State
the probable faults in case of a 3-phase induction motor.
2.
Explain
how 3-phase induction motor shows abnormal behaviors in case of the following
faults:
a) Change in supply
frequencies, b) Single phasing, c) Over loading
d) Crawling/Cogging, e) Unbalanced voltage.
3.
suggest
the proper protective scheme for the motor protection under the following
faults:
a) Single phasing, b) Over
loading, c) Reverse phasing, d) Faults in stator,
e) faults in rotor, f) Unbalanced supply voltage.
4.
Explain
D.O.L. starter and state how it trips in over load conditions?
5.
Explain
by drawing a schematic diagram the working of single phase preventer.
6.
Which
protections are suggested for:
a) Small motors, b) Medium
HP motors and c) High Hp motors for short circuit faults.
**********************************
PROTECTION OF BUSBARS AND
TRANSMISSION LINE CHAPTER - 7
INTRODUCTION
Bus bars are important
parts in power system and industrial switchgear. Bus bars form important link
between incoming and outgoing circuits. The fault level at bus bars is very
high, since it is connected to a larger part of a power system. The fault on
bus bar may cause disconnection of supply to major portion of power system.
The bus bar area for he
protection purpose includes the bus bar, circuit breakers and isolating
switches. When fault occurs within the bus bar area, the faulty section must be
immediately isolated in shortest possible time (50 msec.).
Lack of proper protection
scheme may cause a major shut down which is not desired.
ABNORMALITIES
AND FAULTS
As said earlier, the fault
level at bus bars is very high. The bus bar protection is designed to operate
for two types of fault:
a)
Earth
fault or line to ground fault.
b)
Phase
to phase fault.
The reasons for occurrence
of fault are as follows:
1.
Failure
of support insulators.
2.
Flash
over due to damaged insulator.
3.
Flash
over across insulators due to over voltage.
4.
Mechanical
damage, earthquake.
Following
are the methods of bus bar protection.
1.
Bus
bar protection by over current relays.
2.
Bus
bar protection by differential protection.
3.
Fault
bus protection.
4.
Frame
leakage protection.
The
earth fault or line to ground fault is common fault and phase to phase fault
occurs very rarely.
BUSBAR
PROTECTION
Bus
bar Protection by Over Current Relays
The CTs are connected in
two lines and CT secondary is connected to trip coil of over current relay R1
and R2.
Under normal working
conditions, all CB’s contacts are closed. When, fault occurs on any line say
line 2. The CT secondary current increases to a sufficient value that
sufficiently energizes the relay coil and R2 operates. The CB of
that line operates.
Bus
bar Protection by Differential Protection
The incoming line is
connected to bus bar which is supplying load to line 1 and 2. Two CTs are
connected in line 1 and 2. The secondary’s of these CTs are connected in parallel.
The incoming CT secondary is also in parallel with them. All CTs are identical
i.e. rating, ration is same. A protective relay is connected across the CT secondary’s
as shown.
Under normal working
conditions no current flows through relay coil. This is because sum of incoming
current entering the bus is equal to sum of currents leaving the bus.
But on occurrence of fault,
differential current flows through relay coil. The relay operates the incoming
circuit breaker and then the circuit breaker in line 1 and 2. Thus, faulty
section is isolated.
Fault
Bus Protection
It is generally preferred
for indoor installations. An earthed bus is provided which is made to run along
the conductor. This earthed bus is also known as fault bus.
With this type of
arrangement, the fault current is made to flow through the fault bus. This
fault current and location of fault is detected by suitable arrangement.
The bus bars are supported
on insulators, are installed on the earthed bus or fault bus. The fault bus is
earthed properly and a CT is inserted in the eathing connection. The trip coil
is connected across CT secondary.
Under normal working
conditions no current flows through the trip coil when earth fault develops,
the current flows through the earthed connection and CT secondary current is
circulated which energizes the trip coil and trip circuit contacts are closed.
The circuit breaker receives the trip signal and faulty part is isolated.
Frame
Leakage Protection
This protection scheme is
preferred for indoor substation. Figure shows the arrangement.
The bus bar and circuit
breaker are installed inside metallic casing. The metallic casing is earthed
properly.
When earth fault occurs,
leakage current is produced, it passes to the earth connection. CT secondary
current increases, causing trip coil to close the contacts and trip signal is
given to CB. The respective CB then operates and isolates the faulty part.
TRANSMISSION
LINE PROTECTION
The transmission lines have
large length, and it is exposed to different atmospheric conditions. So chances
of occurrence of fault are more.
The requirements of
transmission line protection scheme are:
1.
In
the event of short circuit in any sections, the CB closest to that fault should
open and other CBs should be in closed position.
2.
If
CB nearest to fault fails to open, the back up protection CB should operate.
3.
The
relay operating time should as short as possible.
The differential protection
scheme can satisfy above conditions. The transmission line can be divided into
number of sections. Each section can be protected by differential protection
scheme. But since length of transmission line is large, such scheme becomes
uneconomical so following methods are used.
Distance protection is
applied where time lag cannot be permitted.
1.
Time
graded over current protection.
2.
Current
graded over current protection.
3.
Distance
protection.
Time graded over current
protection is used as main protection for distribution lines and back up for
main lines where main protection is of distance type.
Current graded protection
is used where a time lag can be permitted and instantaneous operation is not
necessary.
Distance protection is
applied where time lag cannot be permitted.
Time
Graded Over Current Protection
The line or feeder is
divided into number of sections. Over current relays are provided for each
section. On occurrence of fault in any section, the respective relay operates
and gives trip signal to CB. The CB then
opens and isolates the faulty part.
The figure shows time
graded over current protection scheme.
The entire feeder is
sectionalized (i.e. AB, BC, CD). Definite time relays are used for individual
section which gives trip signal to respective CB.
Relay R1 has
operating time of 0.5 second, for R2 it is 1 sec and so on. If fault
occurs in section CD, that section will be isolated in 0.5 sec by R1
and CB1. Remaining relays will not operate because their operating
time is higher.
If R1 and CB1
fails to operate even after 0.5 seconds, R2 operates after 1 second causing CB2
to open. Thus acts as back up protection. In the similar way if R2
and CB2 fails to operate in 1 second, R3 and CB3
will operate.
Drawbacks:
1.
If
feeder is having large length or more number of sections, the operating time
near supply side point is more. For our case it will be 2 second which is
appreciable.
2.
If
a fault say line to ground fault occurs in the section near the transformer, or
source, in that cause amount of fault current will be more because line
impedance is less.
Ideally, the operating time
should be less for more amount of fault current. If feeder is having large
length and number of sections are more, this condition can not be satisfied.
So time graded principle is
applicable where impedance between substation is low i.e. feeder length is
less.
Note: In addition to relay
operating time, the CB operating time should also be considered. In most of the
cases it is necessary to limit the maximum tripping time to 2 seconds.
Current
Graded Over Current Protection
The drawback of time graded
system is that relay near the source operates at last and the fault current
level is high near the source.
The relays used for this scheme
are high speed instantaneous over current relays. The operating time for every
relay is same.
Consider a feeder which is
divided into sections A,B,C.
The current setting for a
relay corresponds to the fault current level for the respective section. Relay
R2 should operate for faults between B and C. But it should not
operate for faults beyond C. Similarly, relay R1 should operate for
faults between A and B. The relay R3 should operate for faults
beyond C.
But above operation is
difficult to obtain because of following reasons:
1. Relay R1 is not
able to differentiate between faults very close to B i.e. neither side of B. If
fault in section BC is very close to B, the relay R1 considers that
the fault is in section AB and it operates, which is not desired.
This happens because there
is a very little difference in fault currents if a fault occurs at the end of
section AB or in the beginning of section BC.
2. It is difficult to evaluate
value of fault current because the conditions may be different for respective
faults.
3.
During
fault, transients are produced and relay performance is affected.
The current graded system
is used where impedance between substations or sections is sufficiently large
to create a marginal difference in fault current.
Combination
of current and time grading:
This is a popular scheme for protection of distribution lines. IDMT relays are
used for such scheme. These have combined features of current and time grading.
IDMT relays have current as well as time setting arrangements. The current setting of relay is made according
to fault current level of a particular section to be protected. The relays are
set to pick up progressively at higher current levels, towards the source. Time
setting is also done in a progressively increasing order towards the source.
Pilot
Wire Protection
It uses differential
protection principle i.e. under normal working conditions the current entering
one end of line is equal to that leaving the other end. If fault develops, the
balance is disturbed and the difference of incoming and outgoing current flows
through the relay coil and trip signal is produced that operates the CB and
thus faulty part is isolated.
Pilot
wire protection methods:
Following methods are used:
1.
Mertz - Price voltage balance system
2.
Translay
scheme.
1. Mertz
– Price voltage balance system: Figure shows arrangement for this scheme.
To identical CTs are placed at both ends of the line. The
CT secondary’s are connected in phase opposition i.e. their secondary voltages
oppose each other. Relay coils are connected in CT secondary’s as shown.
Under normal conditions, current
entering from A is equal to current leaving from B. The CT secondary voltages
are equal in magnitude and opposite in phase, so no current flows through the
relay coils.
When fault occurs between A and B,
this causes CT1 secondary current to increase compared to CT2,
so voltages of CT secondary’s are no longer equal. Circulating current flows in
CT secondary circuit through pilot wires and relay coils. The relays R1
and R2 operate causing operation of CB1 and CB2.
This faulty part is isolated.
Advantages:
1.
This
schemed can be used for ring system and parallel feeder system
2.
Provides
instantaneous protection for ground faults.
Disadvantages
1.
CTs
should be identical
2.
If
pilot wire breaks, malfunctioning occurs.
3.
It
is expensive.
4.
Not
suitable for very long lines.
5. It can not be used beyond
33 kV.
This scheme can be used for
3 phase system also. In that case total 6b CTs and 6 relays will be connected
in the three phase line.
2.
Tran-slay
Scheme: It uses over current induction relays. The CT secondary’s are connected to the windings which are placed on
central limb of the induction relay.
Each induction relay has
two electromagnets E-shaped and C-shaped.
E-shaped electromagnet
central limb carries winding A or A’ which are connected in CT secondary’s. The
connections are made such that there is submission transformer action. All the
CTs are identical.
The central limb also
carries another winding BB’ just below AA’. This BB’ windings and CC’ windings
are connected in series through pilot wires and in phase opposition i.e. their voltages
act in opposite direction.
Operation: Under normal working
conditions CT secondary currents are equal. These currents produce flux that
links with B, B’ and e.m.f. is induced in these coils. Since B and B’ are in
phase opposition, there is no current flowing in the circuit of these windings
i.e. no current flows through C and C’. So there is no torque produced on the
disc.
When fault occurs, the
voltages induced in B and B’ are no
longer the same, corresponding difference current flows through C and C’. And
due to induction action a torque is produced on the disc, the disc rotates and
trip circuit contacts are closed. The respective CBs operate such that faulty
section is isolated.
Advantages:
1.
It
is economical because only two pilot wires are used.
2.
Normal
CTs can be used.
Distance
Protection
The time graded system,
pilot wire system are not suitable for protection of high voltage transmission
lines having a large length.
The time graded system has
a drawback of long operating time and pilot wire sysstem is expensive.
Distance protection scheme
uses impedance relay. The relay operation is based on the impedance (for
distance) between the relay and point of fault. This scheme of protection does
not require any pilot wire. Figure shows arrangement for distance protection
scheme.
The voltage element of
impedance receives supply from PT secondary and current element receives supply
from CT secondary.
The protection zone of line
is between A and b. under normal working conditions, the impedance of line is
ZL. The impedence relay is so designed that, it operates only when line impedance
becomes less than ZL.
When fault occurs between A
and B (say F1), the impedance of line becomes less than ZL and impedance relay
operates, trip signal is produced that operates CB and line is disconnected.
If fault occurs beyond C
(say F2), the impedance in that case is greater than ZL, hence relay does not
operate. The sectiojn beyond C will be protected by another protection scheme
in that section.
Advantages:
1.
No
need of pilot wires.
2.
Less
expensive.
3.
Operation
is simple.
4.
Three
zone protection scheme can be employed to increase reliability.
EXERCISE
1.
What
are abnormalities and fault in bus-bars?
2.
What
are the reasons for occurrence of fault in bus-bar?
3.
Explain
frame leakage protection with a neat sketch.
4.
What
are the requirements of transmission line protection?
5.
What
are the drawbacks of time graded over current protection?
6.
What
accurate operation is not possible in current graded over current protection
scheme?
7.
Explain
translay scheme for protection of transmission line.
8.
What
are the advantages and disadvantages of Mertz price voltage balance system?
No comments:
Post a Comment