EARTHING SUB-STATION
The object of earthing
system is to provide as nearly as possible a surface, under and around a
station, which shall be at uniform potential and as nearly zero or absolute
earth potential as possible with a view to ensure that:
1.
All
parts of the equipment (other than live parts) connected to the earthing system
(through earthing conductors) shall be at ground potential.
2.
Operators
and attendants shall be at ground potential at all times.
Also by providing such a
ground surface of uniform potential under and surrounding the station, there
can exist no difference of potential in a short distance great enough to shock
or injure at attendant when short circuits or abnormal occurrences take place.
Under fault conditions the
non-current carrying metal parts of an electrical installation such as frames,
enclosures, supports, fencing etc. may attain high potentials with respect to
he ground so that any person or animal touching these or approaching these will
be subjected to potential difference which results in the flow of a current
through the body of the person or animal of such a value as may prove fatal.
For a human body, it has
been found experimentally that the safe value of current in amperes (rms) which
human body can tolerate is:
I = 0.165/√t to 0.157 for t <3 sec.
And I = 9 mA for t>3 sec.
Where, t is the time
duration in seconds of the flow of current.
The objective of earthing
is to ensure safety of the operating personnel and other human or animal bodies
by discharging the electrical energy to the earth. This is done by connecting
the non current carrying metallic parts to the general mass of earth by means
of an earthing system which consists of:
·
Electrical
conductors to conduct fault currents and
·
Connecting
leads
The conductors are in the
form of:
·
Single
electrode in the form of rod, pipe or plate.
·
Multiple
electrodes – rods, pipes or plates.
·
Grid
or Mat.
Consider a transformer
whose tank is earthed by a pipe electrode driven into earth. Let there be a
damage to the terminal bushing which has resulted into faulting of one phase
conductor to the tank. The earth fault current in this case will flow from the
phase conductor into the transformer tank and through the earthing pipe to
earth. If the soil is homogeneous in resistivity, the current will flow
uniformly outwards in all directions.
The flow of ground fault
current results in voltage gradient on the surface of the earth in the vicinity
of earthing system.
As the current flows
through a constantly increasing volume of earth, its density drops as the
distance from the pipe increases. As the current density is highest at the
surface of the pipe, the potential at the
surface of the earth will be higher round the pipe. As the distance from
the pipe increases, the less is the difference in earth surface potential
between two points per unit length.
If we take a series of
measurements with a voltmeter to determine the earth surface potential at
different places from the pipe, we will obtain, potential curves as shown in
figure. The curves show that the highest potential is possessed by the pipe
indicated by Ve (the potential of the electrode). Neglecting the
voltage drop in the connecting lead the tank of the transformer can be
considered atd the same potential.
Near the pipe, the rate of
decrease in potential is very marked, but as the distance further increases it
decreases more slowly. As a distance of 20m from the earthing pipe, the
potential is so small that it can be neglected, that is considered equal to
zero.
Now if an operator touches
the tank of the transformer (as shown in figure), the potential difference
between his hand end feet will be:
Etouch = Ve –V
Where Etouch is
termed as touch potential. It is the voltage that exists between the hand and
both feet of the operator.
On the left hand side of
the figure, the operator is shown walking towards the transformer. At any time,
the earth surface potential difference between his feet will amount to,
Estep = V1 – V2
Where Estep is
termed as step potential and is the voltage that exists between the two feet of
a person standing on a ground through which fault current is flowing.
IfRk = the
resistance of the body in ohms.
= 1000 Ω and
Rt is the
grounding resistance of one foot in ohms = taken to be equal to 3Ps
where Ps is the resistivity of the soil near the ground in
ohm-metre.
Then Estep =m(Rk + 2Rf)Ik
volts
And Etouch = (Rk + Rf/2)Ik
Volts
Where, IK is the current in
amps rms flowing through the body.
Substituting the tolerable
limits of current:
(1000 + 6Ps) (0.157)
Estep
= --------------------------- [for
t<3 sec.]
√t
And = (1000 + 6Ps) 0.009 [for
t>3sec.]
Similarly (1000 +
1.5Ps) (0.15t)
Etouch
= --------------------------- [for
t<3 sec.]
√t
and = (1000 + 1.5Ps) 0.009
[for t>3sec.]
Simplifying (157 +
0.942Ps)
Estep = ----------------------------- [for t<3 sec.]
√t
and = (9 + 0.054Ps) 0.009 [for
t>3sec.sustained fault]
and (157 + 0.2355Ps)
Etouch = ----------------------------- [for t<3 sec.]
√t
and = (9 + 0.0135Ps) 0.009
[for t>3sec.]
When the earthing system is designed
and installed, the objective is to obtain as low values of Estep and
Etouch as possible in order to ensure full safety for the operators
in the installation. These values should never exceed the values given by the
above expressions.
Spreading of gravel or crushed rock layer of
0.08 – 0.15m (3 to 6 inches) thickness on the earth surface is useful in
retarding the evaporation of moisture and thus in limiting the drying of top
soil layers during dry weather periods. It also increases the contact
resistance between the soil and the feet. This resistance, however, may be
considerably less than that of the crushed rock.
Transferred
Potential:
If, a person touches a
conductor grounded at a distance, much greater than the dimensions of the
earthing system, the shock voltage will be equal to the full voltage rise of the
earthing system under fault conditions. Such a touch contact is called
Transferred Potential contact as shown in figure.
Grounding
of Sub-Stations
For any particular value of
the fault current, the potential Ve and the potential gradient over the surface
out from the electrode in the case considered above will depend upon the ground
resistance. In EHV systems maximum ground fault current is very high, and it is
not possible to obtain a ground resistance so low as to ensure that the total
rise of the grounding system corrected only by control of local potentials.
A grid (or a mat) is the most practical way of
limiting the potentials at sub-station yards. A grid controls the voltage
gradient under ground fault conditions so as to keep the potential difference
between nearby points within safe limits and avoid danger to the persons
working in the area.
A grid (or a mat) consists
of a number of square or rectangular meshes of earthing conductor buried horizontally
and connected to several electrodes drive at intervals. The typical size of
mesh being 4 m x 5 m of earthing conductor or buried horizontally at a depth of
about 0.5 m varying to 1.5 m depending upon the soil resistivity and connected
to several earth electrodes of size 1.9cm x 3 m driven at intervals. All metal
structures and frames including fencing posts are securely connected to
the earthing grid by running multiple
connections as far as possible.
DESIGN OF
EARTHING GRID.
In designing the earthing
grid for a sub-station, it is necessary to obtain the following information
about the system:
a)
Maximum
earth fault current.
b)
Resistivity
of the soil at the sub-station site.
c)
Fault
clearing time.
d)
Area
covered by the sub-station.
1.
Earth Fault Current: The maximum earth fault
current constitutes a major factor in the earthing system design, this
determines the cross section of the grounding conductor and total rise of the
earthing system potential. The potential gradients are also a function of this
current .
It is common to consider
the symmetrical value of the maximum single line to ground fault.
When the fault duration is
less than 0.5 sec, the rms value of the earth fault current is increased by a
factor as given below to allow for DC offset and Ac and DC decrement.
Fault
Duration
|
Decrement
Factor
|
0.08
|
1.65
|
0.10
|
1.25
|
0.25
|
1.10
|
0.50 or more
|
1.0
|
To allow for the future growth of the
system and the consequent increase in fault current a multiplication factor of
1.2 to 1.5 depending on the site of growth of the system is also adopted.
The current diverted away from the
earthing system by the earthing wires connected to the station earthing is
neglected.
2.
Soil Resistivity: The resistivity of earth
varies within extremely wide limits; between 1 and 10,000 ohm-meters.
To design the most
economical earthing system for a sub-station it is necessary to obtain accurate
data on the soil resistivity and its variation at the station site. Even at the
same site the resistivity of the soil may vary considerably at different times
of the year. It is, therefore, necessary that the measurements are made a
number of times during different parts of the year. Where time does not permit
measurements should be made in dry season to set the maximum value of the soil
resistivity. A number of test locations should be chosen at each site to cover
a wide area of the soil. When 4 to 5 test sites are chosen and measurements
spread over a period of full one year, it may be quite realistic to adopt for
earth resistivity – the arithmetic average of various reading.
3.
Fault Clearing Time: There are many
considerations which influence the choice of fault clearing time such ass the
system stability, the type of switchgear and relaying used. The Russian
practice is to adopt 0.2 sec. as the time of adopting 4 sec. i.e. the same
duration as is used for short time rating of switchgear.
The short time rating of
switchgear as per Indian practice is based on 3 seconds. Therefore, 3 sec. time
may be adopted as the fault clearing time for Earthing Calculations.
However the system design
engineer has to use his judgment to adopt any lower value consistent with the
operating times of circuit breakers and relays used on the system (0.5 to 1.0
sec.).
4.
Area Covered by Sub-Station: The area covered by the
sub-station is governed by the number and type of equipment.
After the layout has been
decided and sub-station plan finalized it is a simple matter to calculate the
area covered by the sub-station.
The next steps in the design procedure
is the
a)
Selection
of earthing material.
b)
Determination
of size of earthing conductor.
c)
Preliminary
arrangement of earthing conductors.
d)
Determination
of conductor length required for gradient control.
e)
Calculation
of resistance of earthing system.
f)
Checking
of design for various voltages.
EXERCISE
1.
What
is the general earthing and neutral grounding?
2.
What
are problems can arise in case of earth fault, if neutral is not provided with
grounding?
3.
State
the advantages of neutral grounding.
4.
State
the different methods of neutral grounding.
5.
Draw
the schematic diagram of the following and explain with drawing vector diagram
how the fault is cleared or reduced.
a)
Solid
grounding,
b)
Resistance
grounding,
c)
Arc
suppression coil grounding,
d)
Voltage
Transformer grounding.
6.
Explain
sub-station grounding.
7.
Compare
different neutral grounding systems.
8.
What
is earth electrode, earth lead and earth current?
No comments:
Post a Comment