INTRODUCTION
In order to generate electric power
and transmit it to customer’s millions of rupees must be spent on power system
equipment. The equipment is designed to work in normal conditions. But faults
may occur due to failure of insulation in the following cases:
1.
Over
voltages due to switching
2.
Over
voltage due to direct and indirect lightening strokes
3.
Bridging
of conductors by birds
4.
Breakdown
of insulation due to decrease of its dielectric strength
5.
Mechanical
damage to the equipment.
This
causes short circuit currents to flow. These short circuit currents may cause a
heavy damage to equipment. To protect the system under abnormal conditions
protective relays are used.
“Protective
relays are the devices that detect abnormal conditions in electrical circuits
by constantly measuring the electrical quantities which are different under
normal and fault conditions.”
Under
abnormal condition current, voltage, phase angle, frequency may change. The
relay operates when it detects the fault which completes the trip circuit and
thus opening the circuit breaker which disconnects the fault circuit.
PROTECTIVE RELAY
It
is a device that detects the fault and indicates the operation of C.B. to isolate the defective element from the
rest of the system as explained below.
A
typical relay circuit is shown when S.C. occurs at point F on transmission
line. C.T. current increases current in relay coil which closes trip coil of
C.B. and C.B. contacts get open. Thus faulty section is isolated.
Protective Zones
The
protective relaying of a power system is planned along with system design. The
C.Bs. are located at appropriate points. Depending upon the rating of the
machine, its location, importance, probability of faults and abnormal
conditions etc. each power system component of transmission line, e.g. bus bar,
cables, capacitors, loads etc, is covered by protective zone.
A
part of the system protected by a certain protective scheme is called as
protective zone or zone of protection.
The
entire part of a power system is covered by several protective zones and no
part of the system is left unprotected.
Overlapping
of protected zones is done to ensure safety of each and every element in the
system. If there is a fault in the region where overlapping is done, more
breakers will open than min. necessary to trip or disconnects the faulty part.
But if there were no overlaps between the zones then the region between the
zones would not lie in either region. Therefore, no C.B. will be opened and if
C.B. is not opened then this may cause damage to the rest of the healthy
system. For this reason certain amount of overlaps are provided between
adjacent zones.
Probability
of failures in overlapping regions is very low hence tripping of too many C.Bs.
will be quite infrequent.
Primary and Backup Protection
Primary
protection (main protection) is the first to act i,e. first line of defence and
is responsible to protect power system element from all types of fault. If
primary protection fails then backup protection comes into action and removes
the faulty part from the healthy system.
Backup
protection is provided for the following reasons:
i)
If
due to some reason (e.g. failure of relay, auxiliary relay failure, fault in
C.T., P.T., trip circuit, C.B. etc.) the main protection fails then there
should be an additional protection otherwise the fault will not be cleared and
it will damage the equipments.
ii)
If
maintenance, testing work is to be carried out on protective equipments, the
main protection. protection is made inoperative and backup protection acts like
main
The
arrangement of backup relay should be such that anything that might cause
failure in primary relaying should not cause failure in backup relaying. This
can be satisfied only if backup and primary relays have nothing common.
Therefore, generally backup relays are at different stations from primary
relays.
Another
important thing is that backup relaying must operate with sufficient time delay
so that primary relaying is given a chance to operate.
Generally,
backup protection is given against short circuit protection only for economy.
The Methods of backup Protection
1.
Relay backup: Same breaker is used for
primary and backup protection, only separate trip coils are provided.
2.
Breaker backup: Different breakers are
provided fro primary and backup protection and both are at the same station.
3.
Remote backup: Primary and backup
protection is provided at different stations and are completely independent.
4.
Centrally co-ordinate
backup:
Main protection is at various stations and backup protection is at central
control centre.
Backup by Time Grading Principle
This
is widely used. The current at various points in a path is measured e.g. at
source, intermediate location like substations etc., consumer’s end etc.
Consider
above figure. If fault occurs beyond ‘C’ region C.B. at ‘C’ region operates
i.e. primary protection. In the meanwhile relays at B and A may also start
operating. They have given enough time lag, so that if breaker at ‘C’ does not
operate, breaker at ‘B’ will operate providing backup protection.
Backup by Duplication Principle
Very
popular in U.S.A. Both primary and backup protections are provided at same
station. The protective devices (C.T., P.T., relays etc.) are duplicated.
Primary and backup protections operate at same speed. This protection scheme is
costly and used in EHV lines after considering economy.
REQUIREMENTS AND QUALITIES OF
PROTECTIVE RELAYING
1. Selectivity and Discrimination: Selectivity is the
ability of the protective system to select correctly the faulty part of the system
and disconnect the faulty part without disturbing rest of the system.
And
in order too provide selectivity to the system entire system is divided into
several protection zones.
Discrimination
means ‘distinguishing the difference between’. This property of protective
relaying enables it to distinguish between the normal condition and abnormal
condition. The protective scheme should operate during abnormal condition and
not during normal condition.
Refer
above figure. If fault occurs at F1 the CB1 only should
trip and other system continues to work. Similarly for F2 both CB3
and CB2 should open. Thus, the protective relaying should isolate
only the faulty part of line without disturbing neighboring line.
2. Speed: The relay system should disconnect
the faulty section as fast as possible.
Relay time; It is the time from the instant of
actuating element is energized to the instant when relay contacts are closed.
This
is important for the following reasons:
a)
Electric
equipment may be damaged if it carries fault current for a long time.
b)
Chances
of developing other fault due to previous fault are reduced.
c)
Power
system stability is improved if speed is high.
3. Sensitivity: It is the ability of the
system to operate for lower values of actuating quantity.
Sensitivity
of a relay is a function of volt ampere input to the coil of relay necessary
for its operation. The smaller the volt ampere the more is the sensitivity of
relay. Thus, 1VA relay is more sensitive than 3 VA relay.
4. Reliability: It is the ability of the
relay system to operate under predetermined conditions.
The
protective relaying should not fail to operate in the events of fault, there
should not be any fault in protective relaying components and the protective
relaying should not operate unnecessarily.
5. Simplicity: The relaying system
should be simple so that it can easily be maintained.
Reliability
is closely related to simplicity, the simpler the protective scheme, greater is
its reliability.
6. Adequateness: The relay should provided
sufficient protection to the system under abnormal conditions.
7. Economy: The most important factor in choice
of protective relaying is economic factor.
As
a rule the protective gear should not cost more than 5% of total cost. However,
the equipment to be protected is of utmost important e.g. generator, main
transmission line etc. then more expenses are allowable.
In
this course, we are expected to learn in brief some of the important types of
relays, their circuit operation and how the circuit is protected in abnormal
conditions/faults by the relay operation.
CLASSIFICATION OF RELAYS
a)
As
per construction and operation
b)
On
the basis of applications.
c)
According
to time required for operation.
d)
D)
Microprocessor based relays.
A) As Per Construction and Operation:
Following
are the different types:
(a) Electromagnetic attraction type:
1.
Attraction armature type:
i)
Plunger
type:
ii)
Hi8nged
armature
iii)
Balanced
beam relay
iv)
Polarized
relay.
2.
Moving iron type
i)
Rotating vane type
3.
PMMC relays
i)
Coil rotating between poles
ii)
Rotating vane type.
b)
Electromagnetic induction type
1.
Induction disc type
i) Plunger type
ii)
Watt-hour meter type
2.
Induction cup type
(C) Thermal relays
i)
Thermo
couple
ii)
Bimetallic
strip
(d)
Static relays
(e)
Gas actuated relays
i)
Buchholz relay.
ii)
Pressure release valve type
(f)
Rectifier relay
(g)
Digital relay
(B) On the basis of Application:
Following
are the different types
1.
Under
voltage, under current, under power relays
2.
Over
voltage, over current, over power and reverse power relays
3.
Distance
relays.
4.
Differential
relays
5.
Directional
relays
(C) According to the Required for
Operation:
1.
Instantaneous relays
2.
Definite time-lag relay
3.
Inverse time relay
4.
Inverse Definite Minimum Time relay (I.D.M.T)
(D) Microprocessor Based Relays:
1.
Micro process (μp)
based relay
2. μp
based over current relay
3. μp
based static relay.
No comments:
Post a Comment