Merits and Demerits
1.
Simple
in construction.
2.
Suitable
for low breaking capacity operation.
3.
It
is indoor type and the control is manual or automatic.
4.
It
is used up to 6.6 kV with a breaking capacity of 15 MVA.
5.
This
is suitable for repeated operation because medium of arc extinction is air.
6.
Operating
control is manual as well as automatic.
Air Blast Circuit Breaker (ABCB) (Or
Compressed Air Circuit Breaker)
(I)
Cross Blast ABCB, (2) Axial Blast ABCB.
(A) Cross Blast ABCB
When
moving contact separates the arc strikes and the blast of air is directed
transversally across the arc and the arc is blown to the arc splitters. These
arc splitters are placed in arc chute. Thus, the blast of air removes the heat
from the arc and the arc is cooled and also as the length of the arc is
increased the arc is interrupted.
Advantages and Disadvantages:
Advantages:
1.
High
speed of operation
2.
Short
arcing time.
3.
High
speed reclosing.
4.
Less
weight as compared to O.C.B.
5.
Very
less maintenance.
6.
No
possibility of explosion.
Disadvantages:
1.
Cost
is more
2.
For
complete compressor air system installation is required.
3.
These
breakers are more sensitive to RRRV.
4.
For
operation and maintenance highly skilled persons are required.
(B) Axial Blast ABCB
Air
is admitted in the arc extinction chamber it pushes the moving contact. The air
blast takes away the ionized gases along with it. Afterwards arc gets
extinguished. High pressure air has higher dielectric strength.The design is
such that the air expands into the low pressure (atmospheric pressure zone)
zone. The air at high sped removal of heat from arc, thus arc is quenched.
Diameter of arc is reduced.
Uses of air blast circuit breaker: As these are suitable for
repeated duty, these are used in: () Arc furnace, (2) Traction system.
SELECTION OF CIRCUIT BREAKERS
The
various circuit breakers arc quenching medium. Voltage range and breaking
capacity are summarized in the following table. Their design features are also
tabulated. The table also gives the comparison of various CBs.
Sn
|
Type
|
Arcing Quenching Medium
|
Voltage Breaking Capacity
|
Construction
|
Uses Remarks
|
1
|
Miniature CB
|
Air at
atmospheric pressure.
|
400-600V
current 5 to 55 Amp
|
Compact, occupy
small space easy fitting.
|
L.V.
circuit Protection Domestic, Commercial, Industrial purpose.
|
2
|
MCCB
|
--- do
----
|
--- do
----
|
Molded
case contains tripping mechanism and terminal contacts. Thermosetting power
is used Long lasting
|
--- do
----
Long lasting
high mechanical strength, high dielectric strength
|
3
|
ELCB
|
--- do
----
|
|
|
|
4
|
Air Blast CB
|
--- do
----
|
400 V –
11kV,
5-750
|
Arc
runners, splitters, magnetic coils used.
|
Low and
medium voltage power circuit. AC or DC in industries, Current limiting features.
|
5
|
Air Blast CB
|
Compressed
air at high pressure 20-30 kg/cm2
|
66kV-1100
kV 2500-60000 MVA
|
Auxiliary
compressed air system required unit type construction
|
Fast
operating, out-door applications. Arc furnace, also for Extra High Voltage
EHV) system.
|
6
|
Min. Oil CB
|
Transformer
oil
|
3.3kV-220kV
150 to 25000 MVA
|
Small arc
control device used. CB chamber is separate.
|
Outdoor
application up to 36kV
|
7
|
Bulk oil CB
|
--- do
----
|
12 kV,
3.6 kV
|
Tank
fitted with arc control device
|
HV power
system up to 12kV, 500 MVA
|
8
|
SF6 CB
|
Sulphur
Hexa-fluoride inert heavy gas at 5 kg/cm2 pressure
|
3.3-765kV
1000 to 50000 MVA
|
Puffer
system used to quench arc earlier with SF6 gas pressure.
|
Suitable
for medium and high voltage power system. Least maintenance.
|
9
|
Vacuum CB
|
Vacuum
|
3.3kV-33kV,
250-2000 MVA
|
Various
types of designs, Long life
|
Variety
of uses in the power supply system 3.6 to 33 kV
|
10
|
HVD CB
|
Oil or
air-blast
|
33kV, 2kA
|
Artificial
current zero by switching in capacitors.
|
Used for
metallic return transfer breaker.
|
Selection of CB
Sn
|
Rated
Voltage
|
Choice
of.
|
Remarks.
|
1
|
Below 1
kV
|
Air
breaker CB, vacuum CB, SF6 CB
|
------
|
2
|
3.3 kV –
33 kV
|
Vacuum
CB, SF6 CB, vacuum CB
|
Vacuum CB
preferred
|
3
|
132 kV –
230 kV
|
SF6,
Air blast CB, MOCB
|
SF6
preferred
|
4
|
400 kV –
760 kV
|
SF6,
Air blast CB
|
SF6
is preferred.
|
MINIATURE CIRCUIT BREAKERS (MCB)
Miniature: Circuit breakers area used in
residential and light commercial installations. Miniature circuit breakers are
commonly used to protect and control the electrical supply to respective
electrical circuits of the building. Miniature circuit breakers often are
single pole breaker and are installed in a cabinet. MCB typically include an
electrical contact mounted on a movable contact carrier which rotates away from
a stationary contact in order to interrupt the current path . Such circuit
breakers have molded insulated housings of standard dimensions sized to
interchangeably plug into or bolt onto panel board. Typically, there is a fixed
contact attached to the housing and a movable contact coupled to an operating
mechanism. The operating mechanism includes a movable handle that extends
outside of the housing the handle has essentially three stable positions : on,
off, and tripped. These three positions tell the operator what condition the
contacts are in when the handle is viewed. The operating mechanism may be
actuated to move the contact into a second, open position. The trip mechanism
is automatically releasable to effect tripping operation and manually
resettable following tripping operations. The trip mechanism may include a
thermal trip capability, which responds to persistent low level over currents,
and/or a magnetic trip capability, which responds instantaneously to higher
over load currents, the thermal magnetic device includes a ‘bimetal” which heats up and bends in response to persistent over
current conditions to unlatch a spring powered operating mechanism which opens
the contacts which opens the separable contacts of the circuit breaker to
interrupt current flow in the protected power system. For short circuit
protection, an armature, which is attracted by the sizable magnetic force
generated in a magnetic core by a short circuit; unlatches the operating
mechanism.
In
some modern types of MCBs arc fault or ground fault mechanism are operative.
The tripping is effected in the event of a line to ground fault or neutral to
ground fault. In such case a torridly CT is used for differential current
sensing.
Now-a-days
a Molded Case Circuit Breaker (MCCB) is available which is the same as MCB and
hence the further operation of MCB is explained in MCCB.
MOLDED CASE CIRCUIT BREAKER (MCCB)
Although
there are many types of molded case circuit breakers manufactured, all are made
up of five main components. There are:
·
Molded
Case of Frame
·
Operating
Mechanism
·
Arc
Extinguishers
·
Contacts
·
Trip
Units.
Five
Main Components of an MCCB.
The
function of the frame is to provide an insulated housing to mount all of the
circuit breaker components. The frame is often a glass-polyester material or
thermo set composite resign that combines ruggedness and high electric strength
in a compact design. The frame is also known as a molded case.
A frame designation is assigned for
each different type and size of molded case: This designation is used to describe
the breaker’s characteristics such as maximum voltage and current ratings,
however, each manufacturer has their own identification system to account for
the differences between breaker characteristics.
Operating Mechanism: Increasingly, molded case
circuit breakers with conventional thermal magnetic trip units are being
replaced by breakers with electronic trips units. These units provide increased
accuracy and repeatability. Some units have built-in ground fault protection,
removing the need for separate ground fault relays and Shunt Trips. Some units
can also provide system monitoring, data gathering and communication to energy
management system.
In
general, electronic trip systems are composed of three components:
·
A
current transformer (sensor) is used on each phase to monitor the current. It
also reduces the current to the proper level for a input to a printed circuit
board.
·
Electronic
circuitry (printed circuit board) that interprets the input and makes a
decision based on predetermined values. A decision to trip results in sending
an output to the next component.
·
A
low power flux-transfer internal shunt trip that trips the breaker. This is
typically a mechanical, spring loaded device held in place by a permanent
magnet.
When
a tripping signal is received from the electronic circuitry, the effects of the
permanent magnet are momentarily counteracted by the tripping pulse, allowing
the mechanical tripping action to take place. There is no need for an external
source of tripping power because the entire tripping system has very low power
requirements.
No comments:
Post a Comment