HAPPY NEW YEAR 2015 TO EVERY BODY.
PROTECTIVE TRANSFORMERS
These
are essential part of a protective system. The protective relays in AC power
system are connected in the secondary circuit of a Current Transformer (CT0 or
Potential Transformer (PT).
Figure
represents a simple protection scheme using CT. It uses a circuit breaker,
relay circuit (relay coil, trip coil) and a CT.
Refer
above figure, under normal working condition the normal load current flows
through the line. The line itself acts as a primary windings for CT i.e. bar
primary. And CT secondary is connected across relay coil. This coil also
carries current and produces magnetic flux. This flux is not sufficient to
close the relay contacts. So trip coil circuit opens and circuit breaker
contacts remain closed. Refer Fig. When a fault occurs, say short circuit
fault, current through the line (CT primary) increases to a large value. Hence,
CT secondary current also increases same current flows through relay coil
producing large flux, the relay contacts are now closed. The trip coil circuit
is now complete, this causes opening of circuit breaker contacts.
Thus,
faulty part is isolated from the bus bar. In most of the protective systems, CT
is utilized for protection purpose.
The
CT and PT can be classified into two groups.
1. Protective Transformers: Protective
transformers are used for protection along with relays, trip coils, pilot wires
etc.
2. Measuring transformers/instrument
transformers: They are used for metering purpose i.e. for range extension
for low range meters.
The
students already have a know how about range extension using CT, PT in
electrical measurements subject.
There
is difference in design of protective transformers and instrument transformers.
This is because the protective transformer has to carry fault current (heavy
current) for some duration of time, on the other hand instrument transformer
has to carry only current up to rated value only.
Requirements of CTs used for
protection:
1.
It
should have correct ratio even if the primary current is much greater than
rated current of CT.
2.
The
core should not saturate for high value of current.
3.
It
should maintain the ratio error and phase angle error in tolerable limits.
Cold
rolled grain oriented silicon steel (3%) i.e. CRGO is used for core material of
protective CT. This material has high permeability, high saturation level and
small magnetizing current. For very high value of fault currents nickel-iron
alloy material is used for core.
Some
important terms related to protective CT are follows:
CT
accuracy of 2% to 3% is essential for satisfactory working of distance
protection scheme and differential protection scheme. For other protection
schemes some higher percentage of error is permissible.
2. CT burden: It is defined as the load
connected across CT secondary. It is expressed in VA (Volt Ampere). It is also
expressed in terms of impedance at secondary rated current.
For
protection CT, relay coil, meters, connecting leads are there on secondary
side. So the total burden on CT will be that of relays + meters + connecting
leads + secondary winding resistance.
Construction of Protection CT: Different forms, shapes
of core are used.
(a) Ring type CT core: The core can have three
types of shapes as shown in figure. The core is made up of stampings. The core
material is nickel-iron alloy or CRG. This core uses bar primary Ample
amount of insulation is to be provided between core and the secondary winding.
Continuously Wound Core: These are available in
encapsulate form. Refer figure. Electrostatic
spraying is done on core so that insulation is formed between core and
secondary. Secondary winding is wound in toroidal form. Insulation tape is wrapped
around it. Number of tapings can be taken out from secondary winding as shown.
CTs used in high voltage system: These are generally oil
filled type. If operating voltage is above 400 kV, SF6 (Sulphur hexa
floride) gas insulation is used.
These
CTs are installed in out door switchyard. Figure shows the two types of high
voltage CTs. Dielectric oil is filled in the casing. Intermediate CTs: Sometimes the secondary
current of main CT is not sufficient to operate the protective devices. In such
cases, additional CT called intermediate CT is used. These are used for feeding
additional current to protective devices so that proper operation takes place.
Protective PT: Potential Transformers
are also known as voltage transformers. Similar to CT, these can be used for
metering and protection.
Types of PT: Following two types of
construction are used:
1.
Electromagnetic
type, 2. Capacitor type.
Electromagnetic type voltage
transformer:
It is similar to conventional transformer with some additional features to
minimize errors. It can be conveniently used up to 132kV. For
lower voltages up to 3.2kV, dry type transformer with varnish impregnated and
taped windings are quite satisfactory. For higher voltages oil immersed PTs are
used. Recently PTs with windings impregnated and encapsulate in synthetic
resins have been used because of this technique dry type PTs can be used up to
66 kV. For voltages above 60 kV, the several PTs are connected in cascade
manner.
Capacitive Type PT/Capacitive Type
Voltage Transformer (CVT): At higher voltages, electromagnetic type PTs
are very expensive so CVT are used. It consists of a capacitive voltage divider
as shown in fig.
The
Capacitors C1 and C2 are connected in series so the high
voltage gets distributed across them. Thus, the voltage applied to primary (Vp)
is (high voltage) – (voltage across C1). To reduce phase angle error
and ratio error in inductor L is connected as shown.
INDUCTION RELAYS
These
relays work on principle of induction motor and use widely used for AC
protection system.
An
induction relay consists of a pivoted aluminum disc placed between two magnetic
fields (the two magnetic fields have a phase difference). Torque is produced in
the disc by the interaction of one magnetic field with currents induced in disc
by the other.
Torque equation:
The
two AC fluxes Φ1 and Φ2 having phase difference a produce eddy
currents i2
and
i1 respectively. The current lag respective fluxes by 900.
Induction Relays:
Induction Relays
Disc
type Cup type
1.
Shaded
pole station
2.
Watt
hour meter type
Shaded Pole
Structure:
The general arrangement of shaded pole
structure is as shown in fig. It consists of a pivoted Al disc free to rotate
in the air gap of electromagnet. One half of each pole of magnet is surrounded
by a copper shading ring. The copper shading ring, splits the exciting current
into two out of phase components. A shaded pole flux lags behind the un-shaded
pole flux normally by 400 to 500. Torque is produced on
the disc by interaction of one magnetic field with currents induced due to
other magnetic field.
Eu = emf induced
by un-shaded portion of pole
Es = emf induced
by shaded portion of pole
θu = flux in
un-shaded pole
θs = flux in
shaded pole
Iu = current in
un-shaded part
Is = current in
shaded part.
Watt-hour
meter type Arrangement
is the same as used in watt-hour meters. A pivoted Al disc rotates freely
between poles of two electromagnets. Upper magnet carries primary and secondary
winding. Primary winding carries current I1 i.e. relay current.
Secondary is connected to winding of lower magnet.
IDMT Relays: Current setting: The
method of adjusting pickup value is known as current setting. The operating
coil of relay is provided with several tapings as shown. By changing the
tapings torque on disc and hence time of operation of relay is changed.
The
value of each tap are expressed in percentage F.L. rating of CT.
Therefore,
pickup current = rated sec. current of CT x current setting.
Suppose
relay is connected to sec. of CT. of ratio 400/5 and taping of 125% is selected
then pickup value = 5 x 1.25 = 6.25A
Fault
current in relay coil
Plug setting multiplier =
---------------------------------
Pickup current
Fault current in relay coil
Fault current in relay coil
= --------------------------------------------------
Rated CT sec. current x current setting
e.g.
if relay is connected to 400/5 Amp. CT set at 150% with a fault current of 2400
Amp then plug setting multiplier is calculated as under
Pickup
value = 5 x 1.5 = 7.5
Fault
current in relay coil i.e. at sec. of CT = 2400 x 5/400 = 30 A
Hence P.S.M. = 30/7.5 = 4
Time setting multiplier A
relay is provided with a control for adjusting the time of operation.
The
actual operating time is obtained from P.S.M/time curve is 3 sec (see the
curve), then actual operating time = 3 x 0.1 = 0.3 sec.
Some Important Terms:
Relay Timing: An important
characteristic of a relay is its time of operation. By time of operation is
meant the length of time from the instant the actuating element is energized to
the instant when the relay contacts are closed.
For
controlling this time some mechanical accessories need to be provided.
1. Instantaneous relay; When the current in the
relay coil exceeds the minimum calibrated value of current, relay contacts are
instantly closed. This time is less than 0.1 second.
2. Inverse time relay; In this type, the
operating time is approximately inversely proportional to the magnitude of
actuating quantity. This is achieved by the provision of a drag magnet or oil
dash pot or time limit fuses.
3. Definite time lag relay; In this type there is a
definite time elapsed between the instant of pickup and the closing of the
relay contacts.
Time/P.S.M. Curve:
Figure
shows the curve between time of operation and plug setting multiplier of a
typical relay. The horizontal scale is marked in terms of plug-setting
multiplier and represents the number of times the relay current is in excess of
the current setting. The vertical scale is marked in terms of the time required
for relay operation. If the P.S.M. is 10, then the time of operation (from the
curve) is 3 seconds. The actual time of operation is obtained by multiplying
this time by the time-setting multiplier.
It
is evident from fig that for lower values of over current, time of operation
varies inversely with the current but as the current approaches 20 times
full-load value, the operating time of relay tends to become constant. This
feature is necessary in order to ensure discrimination on very heavy fault
currents flowing through sound feeders.
Calculation of Relay Operating Time: In order to calculate the
actual relay operating time, the following things must be known:
(a) Time/P.S.M. curve. (b) Current setting
(c)
Time setting (d)
Fault current
(e)
Current transformer ratio
The
procedure for calculating the actual relay operating time is as follows:
1.
Convert
he fault current into the relay coil current by using the current transformer
ratio.
2.
Express
the relay current as a multiple of current setting i.e. calculate the P.S.M.
3.
From
the time/P.S.M. curve of he relay, read off the time of operation for the
calculated P.S.M.
4.
Determine
the actual time of operation by multiplying the above time of the relay by
time-setting multiplier in use.
Example:
Determine the time of operation of a 5 ampere, 3 second over current relay
having a current setting of 125% and a time multiplier of 0.6 connected to
supply circuit through a 400/5 current transformer when the circuit carries a
fault current of 4000 A. Use the curve
as shown in fig.
Solution: Rated secondary current of CT = 5 A
Pickup
current = 4 x 1.25 = 6.25 A
Fault current in relay coil, = 4000 x 5/400 = 50A
Hence Plug-setting multiplier
(P.S.M.) = 50/6.25 = 8
Corresponding to the plug-setting
multiplier of 8 the time of operation is 3.5 seconds.
So Actual relay operating time = 3.5 x Time setting
= 3.5 x 0.5 = 21 seconds.
Induction
Type Over Current Relays (Non-Directional) Construction: The relay works on
induction principle. Actuating quantity is current (from CT secondary). The primary winding is connected to secondary
of CT in the line to be protected. A tapped (1……..7). The tapings are connected
to plug setting bridge so that number of active turns on relay can be changed
and desired current setting can be obtained. Secondary winding is connected to
lower magnet by series connection. Due to induction principle emf is induced in
secondary due to current in primary. The torque exerted on the disc is due to
interaction of eddy currents in the disc and flux produced by upper and lower
magnet. The two fluxes have phase displacement. The spindle carries moving
contact which bridges the two fixed contacts which are connected to trip
circuit. The moving contacts move through a preset angle. By adjusting this
angle (From 00 to 3600) travel of moving contact can be
adjusted and hence time setting is also possible. Restraining torque is
provided with the help of spring.
Operation: Torque is produced on Al disc due to
interaction of eddy current in the disc and two fluxes produced by upper and
lower magnet. Under normal working condition restraining torque is greater than
driving torque which is produced by relay coil current. Si Al disc doesn’t
rotate. If current exceeds preset value, driving torque is greater than
restraining torque. And disc rotates through preset angle causing bridging of
trip circuit contacts. The trip circuit operation causing the opening of CB,
fault is cleared.
Induction Type Directional Power Relay: This relay operates when
power in the circuit flows in specific direction. Construction: Upper magnet carries
potential coil energized by PT secondary and lower magnet carries current coil
energized by secondary of CT. The current coil is provided with number of
tapings (not shown for simplicity of figure.) which is connected to plug
setting bridge so that any desired current setting is obtained. The restraining
torque is produced by spiral spring. Spindle carries moving contact which
bridges the two fixed contacts when disc is rotated through preset angle. By
adjusting this angle, travel of moving disc is adjusted and any desired time setting
can be given to the relay.
Operation: Ø is produced due to current
in potential coil lags V by 900.
Ø2 produced by current coil is in phase
with I. The interaction of Ø1 and Ø2 with eddy current
in the disc, produce driving torque. The direction of driving torque depends upon
direction of power flow. When power in circuit is in normal direction, driving
torque and restraining torque (due to spring) help each other to turn away
moving contacts from fixed contacts. So relay is inoperative. If reverse power
flow is there and driving torque is large enough then disc rotates in the
reverse direction and moving contacts close the trip circuit. Thus C.B.
operates and fault is cleared.
The
directional power relay is unsuitable to
used under short circuit condition., Because when S.C. occurs voltage is
very very low so driving torque is very less. This difficulty is overcome in
directional over current relay which is designed such that operation is
independent of voltage and pf.
Induction Type Directional Over
current Relay (or Earth Fault Relay) Construction: It consists of two elements –directional,
non-directional.
Directional element: This is similar to
directional power relay. This operates when power flow is in specific
direction. The potential coil is connected to P.T. secondary. The current coil
is connected to C.T. secondary. This winding is also wound to central limb of
upper magnet of non-directional element and back to C.T. as shown. The trip
contacts 1 and 2 are connected in series with secondary circuit of
non-directional element. So if 1 and 2 are shorted by moving contact then only
secondary circuit of non-directional element will be completed i.e. directional
element operates first and then non-directional element.
Non-directional element: Similar to
non-directional over current relay circuit. Plug setting bridge is also
provided for current setting (not shown in above diagram for simplicity)/ the
tapings are provided on upper magnet (primary). Spindle carries moving contacts.
Operation: Under normal working conditions
power flows in normal direction. So upper element (directional)does not
operate. There fore, lower element can not operate. When short circuit occurs
there is a tendency of current to flow in the reverse direction. There fore,
element operates closing the contacts 1 and 2 and thus completing circuit to
over current relay. This operates the C.B. because trip circuit is closed and
fault is cleared.
Induction Cup Type Relays: Relay has 2-4 or more
electromagnets energized by relay coil. There is stationary iron core and
hollow metallic cylindrical cup which is free to rotate in the gap between iron
core and poles of electromagnet. The eddy currents are induced in metallic cup
and these currents interact with the flux produced by other magnets and hence
torque is produced.
Modern
induction cup relay consists of four or more poles, a control spring and moving
contacts are mounted on the arm attached to spindle of cup.
The
relay responses for V and I. It has inverse current time characteristic.
Operating time is of the order of 0.01 sec.
These
are used for distance protection. The characteristic depends on type of
structure used.
Distance
or impedance relays.
In impedance relay torque produced by V is in opposite directed to that produced by I. The
relay operates if V/I ratio is less then predetermined value. Under normal working conditions impedance is Z1. If fault F1
occurs impedance
Z = V/I = Voltage at substation/Fault current.
So Z < ZL so relay operates.
Type of Distance Relays:
Definite Distance Relay: Operates instantaneously
for faults up to a predetermined distance from relay.
The
armatures of two magnets are mechanically coupled to the beam.
The
torque produced by two electromagnets is in opposite direction.
Dear admin you done a great job because you shared a valuable information about Protective Transformers. It is very usefull to the Employers as well as Workers who are worked in the Hazardious location. If you have any queries about Relay Coordination and at the same time Relay Calculations, Please visit
ReplyDeleteRelay Coordination