FUNDAMENTAL OF PROTECTIVE SYSTEM
FUNCTIONS OF PROTECTIVE SYSTEM
The function of protective systsem is to disconnet the faulty
part due to short circuit or to disconnect the circuit under abnormal
conditions which might cause a great damage to the rest of the power system.
For this purpose relays are usee. The relay senses the fault current through CT
and energises the trip coil which causes the opening of CB of that particular
system and the faulty section is disconnected. The remaining part of the power
system is not affected.
The CBs are located in such a way that each generator,
transformer, transmission line, feeders etc are completely disconnected from
the rest of the system till fault is cleared. The other function of protective
system is to provide indication, location of fault and type of fault. Thus
fault clearing process becomes more easier.
The protective system should have the following essentials
properties:
1.
Very quick
operation; If the protective system operates quickly and fault is
cleared in a shorter time, the components of the systems are protected from the
probable damage and insulation provided remains unaffected.
2.
Reliability:
The ability of the protective system to operate under the predestermined
conditions is called its reliability. It is an essential requirement for the
system to be protected.
3.
Discrimination:
The protective system should have the ability to discriminate between
faulty sections and healthy sections. It should immediately isolate the faulty
section from the system without affecting the healthy section so that
continuity of supply can be maintained.
4.
Provision
for instruments: The protective system shall provide the proper place for
the instruments like CTs, PTs etc on the panels easily accessible and seen for
observations/inspections.
NORMAL AND ABNORMAL
CONDITIONS (NORMAL/ABNORMAL OPERATION OF SYSTEM)
1.
Normal
Conditions: It is the state of the system network in which below normal
or normal current flows and voltage and frequency remains normal. The cudrrent
is not diverted to the other non-intended paths or earth and it is cdonfined to
pass in the devises path withoiut disturbance and the systsem works normally.
a)
In the normal condition the power producing device like
3-phase alternator should run at the proper speed by the prime mover with the
“speed govering arrangaement” so that it produces a desired voltage at he
desired frequency (my differe by + 1%).
b)
All the 3-phase voltage must be of equal in magnitude having
phase displacement of 1200. This is shown in the figure.
c)
All the three live voltages VRY, VYB
and VBR are also balanced and symmetrical.
d)
The provision of protectsive system should be such that it
should be most economical at the same time it should provide satisfactory
protection.
e)
Due to load variations impedance drop (IZ) varies
which varies the voltage at the consumer’s end. It should not cross the limits
of + 5% on load top changer shall be provided.
f)
Stand by generator is provided to add into the system in peak
load hours.
2.
Abnormal
Conditions: It is the defect in any part of the system which produce
abnormalities like, over current, over voltage, disturbance in frequnecies and
the elements are likely to be damaged and system is disturbed.
In the supply system, right from the generating station to
consumer though the generators produced balance symmetrical 3-phase voltages.
The operation becomes abnormal due to various faults in the system as mentioned
below. Due to abnormalities following are the defects observed:
a) Voltage and current unbalanced b) Over voltages, c) Reversal power
d) power swinging, e) Under frequency, f) Temperature rise,
g) Unstability of system.
REASONS FOR FAULT
OCCURRENCE
1.
Due to failure of insulation of pomponents and equipment
parts. It may lead to short circuit.
2.
Due to mechanical injuries and over temperature conductor may
break.
3.
Lightnings and switching surges may damage the transmission
and distribution lines. Lines are also affectged by birds and objects, tgrees
falling on them or due to wind pressure.
4.
Harmonics produced in rotating machines due to unbalanced
currernts produce over heating.
5.
Drawbacks in system designing, lack of selection of good
quality material, equipment machinery, protective elements etc. may acuse
damage to the system.
6.
Due to mal-operation by operators.
7.
Earthquakes, lightning,storms, ice forming are also
responsible to disturb the system.
No comments:
Post a Comment