Basics of MCCB
The
traditional molded-case circuit breaker uses electromechanical (thermal
magnetic) trip units that may be fixed or interchangeable. An MCCB provides
protection by combining a temperature sensitive device with a current sensitive
electromagnetic device. Both these devices act mechanically on the trip
mechanism.
Depending
upon the application and required protection, an MCCB will use one or a
combination of different trip elements that protect against the thermal
overload, short circuit and ground fault.
Thermal
overload, in an overload condition, there’s a temperature buildup between the
insulation and conductor. If left unchecked, the insulation’s life will
drastically reduce, ultimately resulting in a short circuit. This heat is a
function of I2RT.
Short-circuit condition: Usually, a short circuit
occurs when abnormally high currents flow as a result of the failure of an
insulation system. This high current flow, termed short-circuit current, is
limited only by the capabilities of the distribution system. To stop this
current flow quickly so that major damage can be prevented, the short circuit
element of an MCCB is used.
Ground fault condition: A ground fault actually
is a type of short circuit, only it’s phase-to-ground, which probably is the
most common type of fault on low-voltage system (600 V or less). Today’s modern
electronic CB has the ground fault protection as an integral part of the trip
unit.Overload trip action: Overload
or thermal trip action uses a piece of bimetal heated by the load current. This
bimetal is actually two strips of metal bonded together, with each having
a different thermal rate of heat
expansion. They are factory-calibrated and not field-adjustable.
Short-circuit trip action: Short-circuit trip action
uses an electromagnet having a winding that’s in series with the load current.
When a short circuit occurs, the current flowing through the circuit conductor
causes the magnetic field strength of the electromagnet to increase rapidly and
attract the armature. When this happens, the armature rotates the trip bar,
causing the CB to trip.
The
only time delay factor involves the time it takes for the contacts to
physically open and extinguish the arc, this usually is less than one cycle.
Magnetic
elements are either fixed or adjustable, depending upon the type of CB and
frame size. For example, most thermal magnetic breakers above the 150 A frame
size have adjustable magnetic trips.
A thermal
magnetic trip unit is best suited to most general purpose applications as it’s
temperature sensitive and automatically will follow safe cable and equipment
loadings. These loadings will vary With ambient temperatures. Thermal magnetic
units do not trip if the overload is not dangerous, but will trip instantly
with heavy short-circuit currents.
Electronic trip units: Electronic trip units
typically consist of a current transformer (CT) for each phase, a printed
circuit board, and a shunt trip. The CTs monitor current and reduce it to the
required ratio for direct input into the printed circuit board, the brains of
the electronic trip unit. The circuit-board then interprets current flow
information, makes trip decisions on predetermined parameters, and tells the
shunt trip unit to the trip the breaker.
Sn
|
Fuse
|
Sn
|
MCB
|
1
|
Action
prompt and quick
|
1
|
Action
takes short time.
|
2
|
Replacement
of element is required.
|
2
|
Resetting
is done.
|
3
|
Simple
construction.
|
3
|
Construction
is complicated.
|
4
|
Low cost.
|
4
|
Higher
cost.
|
5
|
Replacement
manually.
|
5
|
Resetting
or automatic resetting.
|
6
|
No other
protection.
|
6
|
Protection
against different faults.
|
7
|
Used in
old house connections.
|
7
|
Now
universally used for domestic as well as industrial purposes.
|
EARTH LEAKAGE CIRCUIT BREAKER (ELCB)
It
is used for the following purpose.
Many
electrical installations have a relatively high earth impedance. This may be
due to the use of a local earth rod (TT systems), or to dry local ground
conditions.
These
installations have a major problem. If no ELCB or RCD is used. During live to
earth fault current, two conditions occur. Because earth impedance is high:
1.
No
enough current exists to trip a fuse or circuit breaker, so the condition
persists un-cleared indefinitely.
2.
The
high impedance earth can not keep the voltage of all exposed CPC connected
metal work to a safe voltage – all such metal work may rise to close to live
conductor voltage.
This
is a dangerous conditions, and was a safety risk in historic electrical
installations. The ELCB makes such installations much safer by cutting the
power if these dangerous conditions occur.
History of ELCB: ELCBs were mainly used on
TT earthing systems. Now-a-days, ELCBs have been mostly replaced by
Residual-Current Devices (RCDs). However, many ELCBs are still in use.
ELCBs
responded to sine wave fault currents, but not to rectified fault current. Over
time, filtering against nuisance trips has also improved. Early ELCBs thus
offer a little less safety and higher risk of nuisance trip. The ability to
distinguish between a fault condition and non-risk conditions is called
discrimination.
Types of ELCB: There are two types of
ELCB.
(1)
Voltage
operated, (2) Current operated.
1.
Voltage operated ELCBs were introduced in the early 20th century,
and provided a major advance in safety for mains electrical supplies with
inadequate earth impedance. V-ELCBs
have been in widespread use since then, and many are still in operation.
2.
Current-operated ELCBs are generally known today as RCDs (Residual Current Device). These also protect against earth
leakage, though the details and method of operation are different.
When
the term ELCB is used it usually means a voltage-operated device. Similar
devices that are current operated are called Residual-current devices.
Connection of ELCB: The earth circuit is
modified when an ELCB is used; the connection to the earth rod is passed through the ELCB by connecting to its two earth
terminals. One terminal goes to the installation earth CPC (Circuit Protective
Conductor, aka earth wire), and the other to the earth rod (or sometimes other
type of earth connection). Thus, the earth circuit passes through the ELCB’s
sense coil.
Operation of ELCB: An ELCB is a specialized
type of latching relay that has a building’s incoming mains power connected
through its switching contacts so that the ELCB disconnects the power in an
earth leakage (unsafe) condition.
The
ELCB detects fault current from live (hot) to the earth (ground) wire within
the installation it protect. If sufficient voltage appears across the EWLCG’s
sense soil, it will switch off the power, and remain off until manually reset.
An ELCB however, does not sense fault currents from live to any other earthed
body.
Advantages of ELCB: ELCBs have one advantage over
RCDs: They are less sensitive to fault conditions, therefore they have less
nuisance trips. (This does not mean they always do, as practical performance
depends on installation details and the discrimination enhancing filtering in
the ELCB). Therefore, by electrically
separating cable armour from cable CPC, an ELCB can be arranged to protect
against cable damage only, and not trip on faults in down line installations.
Disadvantages of ELCB: ELCBs have the some
disadvantages:
1.
They
do not detect faults that don’t pass current through the CPC to the earth rod.
2.
They
do not allow a single building system to be easily split into multiple sections
with independent fault protection, because earthing systems are usually bonded
to pipe-work.
3.
They
may be tripped by external voltages from something connected to the earthing
system such as metal pipes, a TN-S earth or a TN-C-S combined neutral and earth
4.
As
with RCDs, electrically leaky appliances such as some water heaters, washing
machines and cookers may cause the ELCB to trip.
5.
ELCBs
introduce additional resistance and an additional point of failure into the
earthing system.
Earth bypassing: It is not unusual for
ELCB protected installation to have a second unintentional connection to earth
somewhere, one that does not pass through the ELCB sense coil. This can occur
via metal pipe-work in contact with the ground, metal structural framework,
outdoor appliance in contact with soil, and so on.
When
this occurs, fault current may pass to earth without being sensed by the ELCB.
Despite this, perhaps counter intuitively, the operation of the ELCB is not
compromised. The purpose of the ELCB is to prevent earthed metal work rising to
a dangerous voltage during fault conditions.
How the ELCB Works When Earth Faults
Occur?
If
there is no leakage of electricity in the equipment, vector quantity of the
current flowing is each phase becomes Ia + Ib + Ic
= 0, and no voltage will be induced in the secondary winding of the zero-phase
current transformer (some results even when the current of each phase is not in
balance). However, if a ground fault current Ig, should run due to
deterioration of the insulation of the equipment and circuit, vector quantity
of the current will be Ia + Ib + Ic +Ig,
thus including a voltage equivalent to Ig in the secondary winding
of the ZCT. On the other hand, this voltage is so little that it cannot
directly trip the breaker. Consequently, it is fed to the amplifier. Through
amplification, it excites the shunt trip coil and activates breaking motion of
the breaker.
RESIDUAL CURRENT CIRCUIT BREAKER
(RCCB)
Earth
leakage is an electrical hazard, which is responsible for electric shock and
fire risk. Earth leakage and its associated hazard can be prevented by the use
of Residual Current Circuit Breaker (RCCB), ALSO POPULARLY KNOWN AS THE Earth
Leakage Circuit Breaker.
Principle of Working: The RCCB works on he
current balance principle. The supply conductors, i.e. the phase and the
neutral, are passed through a torrid and form the primary windings of a current
transformer. Its secondary winding is connected to a highly sensitive
electromagnetic trip relay, which operates the trip mechanism.In a healthy
circuit, sum of the currents in phases, is equal to the current in the neutral
and vector sum of all currents is equal to zero. If there is any insulation
fault in the circuit and leakage current flows to earth, the currents do not
balance and their vector sum is not equal to zero. This imbalance is detected
by the current transformer, the RCB is tripped and supply to load is
interrupted. The trip mechanism is operated at a residual current of between
50-100% of its rated tripping current.
According
to the IS: RCCBs must automatically disconnect an electrical installation
within 0.2 sec. in the event of an earth fault. Havel’s RCCBs break is less
than (0.03 sec) when the fault current, which flows to earth exceeds the
tripping current.
No comments:
Post a Comment