Advantages of HRC with Tripping Device
Over HRC Without Tripping Type
1.
In
case of single phase fault the plunger operates and CB rips all the 3 phases
thus avoids single phasing.
2.
Relatively
inexpensive CB is required.
3.
Capable
of dealing with small fault currents itself. This avoids replacing
HRC Fuse with Indicator
Figure
shows an HRC fuse developed by General Electric Company. The cylindrical body
made of ceramic material is closed by metal end-caps and the copper
terminal-tags are electro-tinned. The fuse element made of pure silver is
surrounded by silica as the arc quenching medium. In order to increase the breaking capacity of
the fuse, two or more widely separated fuse elements are used in parallel. The breaking
capacity is increased due to a greater surface area of the fuse element in
contact with the silica filler. An indicating device consisting of a fine
resistance wire connected in parallel with the fuse element and led through a
small quantity of mild explosive held in a pocket in the side of the fuse and
covered by a label is also provided. It indicates whether the fuse has blown
out or not. When the fuse operates on occurrence of fault, the fine wire is
automatically fused resulting in the combustion of the explosive material. The
combustion of the explosive material chars the label, and thus indicates that
the fuse has blown out.
Applications of HRC fuse
1.
Protection
L.V. distribution systems against over load and short circuits.
2.
Protection
of bus-bars.
3.
Protection
of cables.
4.
Protection
of motors.
5.
Back
up protection to circuit breakers.
6.
Protection
of semi-conductor devices.
DROP OUT FUSE LINK
This
is also an expulsion type high voltage fuse with one pole in closed position.
When the fuse element gets fused on the occurrence of a fault, the fuse element
carrying tube drops down under gravity about its lower hinged support, and
hence the operation of the fuse can be readily spotted from distance. As the
fuse element carrying tube drops down on operation of the fuse, it provides
additional isolation. The blown fuse element is replaced by lifting the
complete tube from the hinge and bringing it down by means of a special
insulated rod. After replacing the fuse element, the tube is replaced in the
hinge and the device is closed in a way similar to closing of isolators. These
fuses are extensively used for protection of outdoor transformers, and the fuse
isolator combination is generally pole mounted.
EXPULSION FUSE
In an expulsion type fuse, the arc caused by
operation of the fuse is extinguished by expulsion of gases produced by the
arc.
As
expulsion fuse contains a hollow tube made of synthetic-resin-bonded paper in
which the fuse element is placed and the ends of the element are connected to
suitable fittings at each end. The length of the tube is generally longer than
the conventional enclosed fuses. On the occurrence of a fault, the arc produced
by fusing of the fuse element causes decomposition of the inner coating of the
tube resulting in the formation of gases which assist are extinction. Such
fuses are developed for 11 kV, 250 MVA and are commonly used for protection of
distribution transformers, overhead lines and cable terminating with overhead
lines.
DISCRIMINATION BETWEEN TWO FUSES
In
order to understand this type of discriminations consider a radial circuit
shown in the figure. The power to the radial line is being fed at the left end.
The fuse F1 which is nearer the feeder is called the major fuse, and
the fuse F2 which is far from the feeder is called the minor fuse.
If a fault occurs at the far end of the feeder, i.e. at point F, the fault
current will flow through both the fuses F1 and F2. If
the fuses used do not have discriminative character, there is a likelihood that
the major fuse F1 is blow out and thus supply to the whole line will
be interrupted, although there is no fault between F1 and F2.
Therefore, when a fault occurs beyond F2, only F2 should
operate and F1 should remain unaffected. This is called proper discrimination.
For proper discrimination in this case, the pre-arcing time of the major fuse F1
must be grater than the total operating time of the minor fuse F2.
DISCRIMINATION BETWEEN FUSES AND
OVER-CURRENT PROTECTIVE DEVICES
In
motor circuits, fuses provide short-circuit protection and the over-current
relay provides over-current (overload) protection. The characteristics of the
fuses and over-current relay are coordinated in such a way that the
over-current relay operates for currents within the breaking capacity of the
circuit breaker 9or the contactor), and the fuses operate for faults of larger
current. For this purpose, the characteristic of the over-current protective
device should be below the characteristic of the fuse, as shown in the figure.
The fuse is so selected that the intersection of the characteristics of these
two protective devices must take place at a point (A) corresponding to six
times the full-load current, keeping in view that the protective devices do not
operate unduly during starting. In this case, the fuse provides back-up
protection to the motor and is connected on the supply side.
COMPARISON OF FUSE WITH CIRCUIT
BREAKER
Points
|
Fuse
|
Circuit
Breaker
|
1.
Function
|
It
performs both detection and interruption function.
|
It
performs interruption function only. The detection of fault is made by relay
system.
|
2.
Operation
|
Inherently
completely automatic.
|
Requires
equipments (e.g. relays) for automatic operation.
|
3.
Breaking capacity
|
Small
|
Very
large
|
4.
Operating time
|
Very
small(0.002 sec or so)
|
Comparatively
large (0.1 to 0.2 sec)
|
5.
Replacement
|
Requires
replacement after every interruption
|
Bi
replacement after operation
|
CATEGORIES AND CLASSIFICATION OF FUSES
Class P - fusing
factor less than 1.25
Class Q - fusing
factor less than 1.75
Class K - fusing
factor less than 1.75
FACTORS FOR
SELECTING FUSE
Following
factors should be considered while selecting a fuse. Reliable fuse should be
used such that it will blow out under abnormal conditions only. It should
remain intact under short period over-loads or during switching surges.
Following
points should be considered for selection:
a)
Nature of Load:
1.
Normal
current.
2.
Starting
circuit.
3.
Permissible
overload.
4.
Whether
it is a steady load or fluctuating load.
b)
Nature of Protection
Required:
1.
Overload
or short circuit protection.
2.
Quick
opening or slow opening.
3.
Cut-off
value desired.
c)
Grading and Discrimination
Between other Fuses and CBs in the Circuit
Fluctuating loads: The current reaches to a
high value in short durations. So the fuses should not blow under transient
overloads. So current/time characteristic of fuse should be always above
transient current characteristic of load with an enough margin.
Fuses
of class Q having fusing factor greater than 1.75 are suitable for fluctuating
loads.
Switching surges: Caused by switching of
transformers, motors, capacitors, fluorescent lighting etc so rating of fuse
for this application should be 20 to 25% more that F.V. value of current.
For steady load: Class P fuses are used.
ISOLATORS (ISOLATING SWITCHES)
When
carrying out inspection of repairs in a sub-station or charged line repairs it
is essential to disconnect reliably that section of line on which the work to
be carried out. This disconnecting device is a isolator. As the name suggests
it isolates the part of the section from the live lines. It assures the safety
to the team of electricians and line-mans who are expected to work on such
sections. The isolator makes a visible break without any arcing/sparking.
So
isolator is defined as a device used to open or to close a circuit either when
negligible current is interrupted or when no significant charge in the voltage
across the terminals of each pole of isolator will result from the operation.
Vertical Break Type Isolator
The
contact arm is divided into two parts:
i)
Male contact i.e. moving contact.
ii) Female contact i.e. fixed contact.
The
moving contact is opened by a operating mechanism. The contacts are supported
on the solid core insulators. Operating blade is supported on the operating rod
insulator. All the insulators are fixed on the base. Earthing switches are also
fixed on the isolators and linked with the isolators. Isolators, earth switches
and circuit breakers are interlocked to avoid mal-operation to protect the
equipment and provide safety to the operating staff. The operation of isolator
may be manual and or with electrical/pneumatic mechanism.
Uses: Outdoor applications
including isolation of circuit breaker, transformer banks and surge arrestors
and line sectioning.
Horizontal Break [Centre Rotating
Double Break] Type Isolator
Construction: Fixed female contacts of
metal are supported on the stack of insulators. Male contact rod is connected
to the central insulating support which can be moved to have a horizontal
moment of the male contact for opening or closing into the female contacts. The
moment of the rod and its support may be done by manually or manually but
electricity or pneumatically by then operators. The operating mechanism
disengage or engage the rod in the female contacts for closing or opening
operation of isolator. The male contact’s moment is horizontal and hence this
type of isolator is named as horizontal break isolator. The assembly is
supported on the galvanized steel channel or steel frame. The moving male
contact can be moved through 900.
Use: This type is used indoor or outdoor
equipment of capacity above 245 kV.
Pantograph Type Isolator
This
type is for 245 kV 1200 Amp and occupy less space easy for operation.
The
supporting insulator is mounted on the concrete foundation pad. To this
foundation the operating mechanism is also fitted. A solid rotary insulator is
moved for isolator operation (make or break operation). The moment of the
pantograph for make-break of blade is shown by dots and dotted line. On closed
position the two arms of the pantograph close on the overhead station bus bar
giving a grip. The current is carried by the upper bus bar to the lower bus bar
through the conducting arm of the pantograph.
On
the opening position the pantograph arms collapse in the vertical plane and
vertical isolation is obtained between the line terminal and pantograph upper
terminal.
No comments:
Post a Comment