Advantages and
Disadvantages of Minimum Oil C.Bs.
Advantages:
1.
It
requires lesser quantity of oil.
2.
It
requires smaller space.
3.
Maintenance
is less.
4.
Fire
risk is reduced.
5.
Cost
per breaking capacity in MVA is less.
6.
Suitable
for both manual and automatic operation.
Disadvantages:
1.
Smaller
quantity of oil is used so the degree of carbonization is increased.
2.
It
is difficult to remove gases from the space between contacts.
3.
Carbonization
is more so oil deteriorates rapidly due to frequent operations.
4.
Difficulty
in locating CT.
5.
Possibility
of fire and explosion.
Maintenance of OCBs
The
main inspection is:
a)
Checking
of contacts.
b)
Checking
of dielectric strength of oil.
Due
to the switching ON-OFF on load and in case of tripping in faults, the contacts
get burnt by arcing. The insulating oil also lost by some amount and loses it
dielectric strength due to carbonization. This results in reducing rupturing
capacity of the breaker.
Following
is the maintenance schedule (every after 3 months/6 months).
1.
Inspect
the condition of contacts, if burnt replace.
2.
Check
dielectric str4ength of oil seeing the color of oil. If badly discolo9ured then
take it out for filtration or replace it by new one.
A good oil withstands 30kV
for 1 minute in a testing set of 4 mm
gap.
3.
Check
the insulation for possible damage, clean the surface to remove carbon deposits
with fabric cloth.
4.
Oil
level to be checked, if gone down make up the level by fresh oil.
5.
Mechanisms
shall be checked frequently.
Comparison of Bulk Oil C.B.
with Air Blast C.Bs.
Sn
|
Bulk
Oil C.B.
|
Sn
|
Air
Blast C.B.
|
1
|
Decomposed products are inflammable and explosive. If
arc is not extinguished explosion may occur.
|
1
|
No such danger exists because no products are formed.
|
2
|
Oil absorbs moisture and also get carbonized due to
frequent operations, hence needs regular replacement.
|
2
|
Air compressor takes air from atmosphere hence no
replacement i.e. arcing products are completely removed.
|
3
|
Not suitable for repeated operations because oil gets
deteriorated.
|
3
|
Suitable for repeated operations.
|
4
|
Used for medium capacities.
|
4
|
Used for high capacities.
|
5
|
Reliability is less as compared to ABCB.
|
5
|
Reliable operation.
|
6
|
If leakage occurs it can be detected easily.
|
6
|
If leakage occurs operation is not satisfactory.
|
7
|
Better design, hence contact remain smooth.
|
7
|
Complex design and contacts get eroded.
|
8
|
For single C.B. huge oil storage is required.
|
8
|
A single compressor unit can be used for multi C.B.
system.
|
9
|
Maintenance required is more.
|
9
|
Less maintenance.
|
10
|
Costly.
|
10
|
Less costly.
|
11
|
Transportation becomes difficult due to huge size and
large weight.
|
11
|
No such problem.
|
SF6 Circuit Breaker
(Sulphur Hexa Fluoride C.B.)
Prior
to study the constructional details let us know the SF6.
Properties of SF6 gas:
1.
Electronegative: It is the ability of an
atom to attract and hold electrons. Such gases have high dielectric strength SF6
is electronegative, it forms negative ions. Negative ions are heavy and
immobile so they do not flow easily. Hence, SF6 has high dielectric
strength.
2.
Due
to SF6 gas arc time constant is low. Because rate of rise of
dielectric strength of SF6 is very high.
3.
At
atmospheric pressure dielectric strength is 2.35 time more than air.
4.
It
can be liquidified at moderate temperature and can be stored in a steel tank.
5.
Dielectric
strength increases linearly with pressure
6.
SF6
has great heat transfer ability so arc can be cooled quickly.
7.
Gas
is inert. Therefore, contacts will not get eroded.
8.
Gas
is non-inflammable.
9.
Colorless.
10.
Odorless
11.
Non-toxic.
12.
Thermally
stable up to 5000C. The decomposed products (SF2 and SF4)
recombine to form same volume of original gas.
13.
Density
is 5 times more than air.
(A) Puffer Type SF6 Circuit
Breaker:
Principle: It makes use of puffer action.
Puffer means short and quick blast of gas or air. For this circuit breaker the
SF6 gas and blast is produced by puffer action which is passed on to
the arc and arc is extinguished.
Construction: The fixed and moving
contacts are kept in insulating nozzle section. The whole assembly i.e.
insulating nozzle, puffer action cylinder moves with the moving contact. A
fixed piston is provided at the other end of moving contact. The chamber is
filled up with SF6 gas.
Working: Under normal working conditions the
contacts are closed. On occurrence of fault, the contacts are opened, movable
contact moves towards right, the movable cylinder, insulating nozzle move simultaneously.
An
arc is struck between fixed contact and moving contact. The travel of movable
cylinder causes increase in pressure on SF6 gas, the SF6 gas is now
compressed i.e. it is under high pressure. The SF6 travels to left
towards the arc i.e. it puffs over the arc. This results in extinction of arc.
(B) Double Pressure Dead Tank Type SF6
Circuit Breaker:
The
gas from the compressor is taken into auxiliary H.P. reservoir through the
inlet as shown in figure. It is then admitted into main SF6
reservoir at 14 kg/cm2 from which it travels axially to the arc
extinction chamber where the arc is formed. The axial flow of this gas takes
away the heat and arc is cooled and is extinguished. The arcing time becomes
less as the dielectric strength is more. Finally, the gas reaches L.P. chamber
from which it is pumped to the compressor unit from which it is taken to the
auxiliary H.P. cylinder for the next operation.
The
CB consists of:
1.
Gas
system.
2.
Tank.
3.
Interrupted
or arc extinction chamber.
1. Gas system: The gas follows closed
path as indicated above and do not escape to the atmosphere. The activated
alumina (AL2O3) filters the gas and absorbs the products
which have failed to recombine. Further the moisture also is removed by
alumina.
2. Tank: The tank is earthed.
3. Arc Extinction Chamber: The chamber is located
axially in the tank and is supported by insulators. The arc extinction process
takes place in this chamber by the axial flow of SF6 gas.
The
type is becoming absolute and puffer type is coming up as explained here after.
Advantages and Disadvantages of SF6
C.B.:
1.
It’s
working is silent with good overload capacities. The failure from moisture can
be avoided by using sealed constructions.
2.
It
has ability to interrupt low and high fault current inductive and capacitive
current with minimum fault clearing time.
3.
Some
gas is re-circulated; hence the quantity of SF6 gas required in the
long run is small.
4.
Maintenance
is a minimum.
5.
No
over voltage problems and no contact replacement because the contact corrosion
is very small (Because gas is inert).
6.
For
the same rating size of SF6 C.B. is small as compared to ABCB
because dielectric strength of SF6 is high. Hence, clearance is less
and size is smaller.
7.
Excellent
arc extinction capacity, the insulating physical and chemical properties are
advantageous and the possibility of fire and explosion is very less.
i)
Special
material is required for construction because of the sealing problems.
ii)
The
entry of moisture in a gas cause the failure of C.B. but the latest design
takes due care about it.
Comparison of SF6 C.B. with
Air Blast C.B.
Sn
|
Features
|
Air blast C.B.
|
SF6 C.B.
|
1
|
Compressed
air
|
Required
|
Not
required
|
2
|
Gas
|
Not
required
|
SF6
gas required
|
3
|
Number of
interrupters
|
6 to 12
|
2 to 4
|
4
|
Maintenance
|
More
|
Less
|
5
|
Pressure
|
30 bars
|
5 bars
|
6
|
Switching
|
Excellent
|
Excellent
|
7
|
Breaking
time
|
2 cycles
|
2.5
cycles
|
8
|
Medium
|
Fresh
every time
|
Same
forever
|
9
|
Construction
|
Comp0lex
|
Compact/simple
|
10
|
Cost
|
Very high
|
Medium
|
11
|
Use
|
Used
early days
|
Used
now-a-days
|
Vacuum Circuit Breaker
Principle: When two contacts of this circuit
breaker and separated in vacuum an arc is struck and hot spots are formed on
the surface of contacts. These hot spots produce metal vapor and plasma. The
amount of vapor in the plasma depends on how rapidly the vapor is emitted from
contact surface which indeed depends on arc current. The current is of
alternating nature, it passes through zero several time, so the rate of vapor
emission also becomes zero, and the vapor already emitted gets condensed.
During this process the dielectric strength builds up rapidly and re-striking
of arc is prevented.
Construction: It consists of a
enclosure made up of insulating material like glass. The vacuum retained inside
the container is about 10-7 torr. The enclosure is supported by means of end
flanges made up of non-magnetic material. The contacts are disc shaped. The
contact tips are made of a copper-chromium or copper-bismuth alloy. The contact
region is surrounded by vapor condensing shield. It does not allow the
condensed vapor to pass on to the glass enclosure.
The
metallic bellows are used which can permit the movement of moving contact
without disturbing the vacuum. Metal ceramic seals are used a respective points
to be sealed.
Working: Under normal working conditions the
contacts are closed. On occurrence of fault, the moving contact moves upwards.
An arc is produced between the contacts due to ionization of metal vapor. The
arc gets extinguished. The arc extinction process is already explained in
principle of working of vacuum C.B.
Advantage:
1.
Vacuum
C.Bs. are compact in size.
2.
Reliable
and longer life.
3.
Heavy
fault current can be interrupted effectively.
4.
No
gas is generated after arc extinction operation.
5.
Operation
is not noisy.
6.
Arc
energy is low
7.
Inertia
is low.
8.
No
risk of fire.
Disadvantages;
Vacuum
has to be maintained at desired level always.
Application: Outdoor application where
maintenance required si minimum. In the high voltage system from 22 kV to 66 kV
power circuits. This breaker is also useful in rural area with limited rating
60 to 100 MVA.
L.T. CIRCUIT BREAKER
Air Break Circuit Breaker
The
main contact carries current when C.B. is closed. When the fault occurs first
the main contacts operate and then the arcing contacts. When the arcing
contacts separate out the blow out coils which are provided across the arcing
contacts are brought into circuit and the current will flow through the blow
out coil. When the arcing contacts separate, the arc strikes across and will be
placed in the magnetic field provided by the blow out coil. The arc being a
path of current it becomes as if a current carrying conductor placed in a
magnetic field. Hence, the arc experiences electromagnetic force. The arc
experiences electromagnetic force. The arc heats the air around the contacts
and hence due to thermal action, arc travels upward and will be directed along
he arc runners. Finally, arc will reach the arc splitter plates and these
plates increase the length of the arc therefore an resistance is increased, arc
voltage drop is increased and arc is cooled down when the recovery voltage is
less than the arc voltage the arc is extinguished and the C.B. opens the
circuit.
These
breakers are available in different ratings:
460
volts, 400 to 3500 Amp, 40 to 75 kA
3.3
kV, 400 – 3500 Amp., 13.1 – 31.5 kA
6.6
kV, 400
– 2400 Amp., 13.1 – 20 kA
No comments:
Post a Comment